Plan Review Details - Permit 12050273
Plan Review Stops For Permit 12050273
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-05-15 Cont ID  
Sent By lmartine Date 2012-05-15 Time 09:25 Rev Time 0.00
Received By lmartine Date 2012-05-15 Time 09:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2012-05-10 Time   Rev Time  
Received By   Date 2012-05-10 Time   Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-15 Cont ID  
Sent By hmoser Date 2012-05-15 Time 08:43 Rev Time 0.00
Received By hmoser Date 2012-05-09 Time 15:57 Sent To  
Notes
2012-05-09 15:57:29SENT TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-05-16 Cont ID  
Sent By hmoser Date 2012-05-15 Time 08:42 Rev Time 0.00
Received By hmoser Date 2012-05-14 Time 15:03 Sent To  
Notes
2012-05-15 08:42:33PROVISO
 1) PROVIDE A DETAIL ON SUPPLY FAN CURB TIEDOWN TO ROOF
 ( WHAT SIZE LAGS ARE GOING ARE YOU USING).PER SECTION
 301.12 WIND RESISTANCE 2010 FBC (M)
 2) REFER TO SECTION 506.3.8.2 CLEANOUTS SERVING
 INLINE FANS 2010 FBC (M)
 3) REFER TO SECTION 506.3.11 GRACE DUCT FIRE RESISTIVE
 OPENING
 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  