Plan Review Details - Permit 12050218
Plan Review Stops For Permit 12050218
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-07-09 Cont ID  
Sent By jwitmer Date 2012-07-09 Time 11:16 Rev Time 0.00
Received By jwitmer Date 2012-07-09 Time 11:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-07-06 Cont ID  
Sent By jwitmer Date 2012-07-06 Time 11:42 Rev Time 0.00
Received By jwitmer Date 2012-07-06 Time 11:42 Sent To  
Notes
2012-07-06 11:55:50BUILDING PLAN REVIEW
 PERMIT: 12050218
 ADD: 2465 MERCER AVE # 105
 CONT: CROSSROADS CONSTRUCTION
 TEL: (561)346-6160
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1:
  
 1) THE PROPERTY APPRAISERS SITE INDICATES THIS TO BE A
 COMMERCIAL CONDOMINIUM SITE WITH SEPERATE UNITS,
 PROPERTY LINES AND OWNERSHIP. PLANS WILL NEED TO
 IDENTIFY UNITS AND ASSOCIATED PROPERTY LINES TO COMPLY
 WITH 2010 FBC-B 709.1(6) TENANT SEPERATION WALLS. THE
 DESIGNER WILL NEED TO IDENTIFY THE TENANT SEPERATION
 WALL AS A 1 HOUR RATED WALL BETWEEN THE TWO UNITS PER
 2010 FBC-B 709.1.(6) WALLS SEPERATING TENANT SPACES.
 THE DOOR ON MAG HOLD OPEN DEVICES SEPERATING THE TWO
 TENANCIES WILL ALSO NEED TO BE A FIRE RATED DOOR SEE
 TABLE 715.4 FIRE DOORS AND FIRE SHUTTERS.
  
 7/09/20112 CONDO DOCS SUBMITTED PART OF PERMIT PACKAGE.
 OK TO PASS.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-22 Cont ID  
Sent By jwitmer Date 2012-05-22 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2012-05-22 Time 11:23 Sent To  
Notes
2012-05-22 12:17:28BUILDING PLAN REVIEW
 PERMIT: 12050218
 ADD: 2465 MERCER AVE # 105
 CONT: CROSSROADS CONSTRUCTION
 TEL: (561)346-6160
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1:
  
 1A) THE PROPERTY APPRAISERS SITE INDICATES THIS TO BE A
 COMMERCIAL CONDOMINIUM SITE WITH SEPERATE UNITS,
 PROPERTY LINES AND OWNERSHIP. PLANS WILL NEED TO
 IDENTIFY UNITS AND ASSOCIATED PROPERTY LINES TO COMPLY
 WITH 2010 FBC-B 709.1(6) TENANT SEPERATION WALLS.
 EXCEPTION # 6 FOR TENANT SEPERATION WALLS WILL NOT BE
 APPLICABLE EVEN IF THE ASSUMED 3 SPACES WERE UNDER
 3,000 SQ FT THERE ARE 3 SEPERATE PCN NUMBERS, THESE ARE
 NOT RENTAL UNITS UNDER ONE OWNERSHIP.
  
 NOTE 5/22/12 WAITING ON E-MAIL FOR LEASE AGREEMENT. JW
 NOTE 5/23/12 RECEIVED LEASE AGREEMENT SPOKE WITH BO
 DOUG WISE ABOUT LEGALLITY.
 NOTE 5/24/12 SPOKE WITH OWNERS, OWNERS ARE TO COMBINE
 UNITS UNDER ONE OWNERSHIP, WILL NEED TO COMPLETE A
 UNITY OF TITLE UNDER OWN PCN.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-09 Cont ID  
Sent By rlecky Date 2012-05-09 Time 11:18 Rev Time 0.00
Received By rlecky Date 2012-05-09 Time 11:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-07-14 Cont ID  
Sent By wjolin Date 2012-07-14 Time 18:23 Rev Time 0.00
Received By wjolin Date 2012-07-14 Time 18:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-06-22 Cont ID  
Sent By wjolin Date 2012-06-22 Time 11:37 Rev Time 0.00
Received By wjolin Date 2012-06-22 Time 11:17 Sent To  
Notes
2012-06-22 11:36:032465 MERCER AVENUE - SUITE #105
 PERMIT #12050218
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: ALL DEMOLITION OR CONSTRUCTION AREAS
 SHALL HAVE "NO SMOKING" SIGNS POSTED.
  
 REPEAT COMMENT: ALL EXTERIOR DOORS NOT FUNCTIONING AS
 EXITS SHALL BE PERMANENTLY MARKED AND CLEARLY INDICATED
 AS, "NOT AN EXIT."
  
 REPEAT COMMENT: SHEET A-2: PROVIDE FIRE ALARM
 NOTIFICATION APPLIANCE IN CONFERENCE ROOM #2 AND IN
 HALLWAY NEAR BREAK ROOM/COPY ROOM.
 NEW COMMENT: ALL THE FIRE ALARM NOTIFICATION APPLIANCES
 ORIGINALLY SHOWN ON SHEET A-2 ARE NO LONGER SHOWN.
  
 IN ORDER TO ISSUE A GENERAL BUILDING PERMIT, THE FIRE
 ALARM AND FIRE SPRINKLER SCOPE OF WORK WOULD NEED TO BE
 SHOWN OR DESCRIBED ON THE DESIGN DOCUMENTS. AFTER THE
 GENERAL BUILDING PERMIT HAS BEEN ISSUED, THE
 SUB-CONTRACTORS WILL NEED TO SUBMIT SHOP DRAWINGS (FIRE
 ALARM AND FIRE SPRINKLER) FOR SPECIFIC SUB-PERMITS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-05-29 Cont ID  
Sent By wjolin Date 2012-05-29 Time 10:34 Rev Time 0.00
Received By wjolin Date 2012-05-29 Time 09:51 Sent To  
Notes
2012-05-29 10:26:332465 MERCER AVENUE - SUITE #105
 PERMIT #12050218
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH
 FLORIDA AMENDMENTS SHOULD BE REFERENCED IN THE CODE
 LIST.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PLANS DO NOT INDICATE THE SCOPE OF WORK FOR THE FIRE
 SPRINKLER SYSTEM. ANY RESIDENTIAL TYPE SPRINKLERS WOULD
 NEED TO BE REPLACED WITH COMMERCIAL STYLE SPRINKLERS.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 ALL EXTERIOR DOORS NOT FUNCTIONING AS EXITS SHALL BE
 PERMANENTLY MARKED AND CLEARLY INDICATED AS, "NOT AN
 EXIT."
  
 SHEET A-2: PROVIDE FIRE ALARM NOTIFICATION APPLIANCE IN
 CONFERENCE ROOM #2 AND IN HALLWAY NEAR BREAK ROOM/COPY
 ROOM.
  
 SHEET A-3: PROVIDE EMERGENCY LIGHTING FOR EXIT PATH IN
 MTC ROOM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-07-14 Cont ID  
Sent By wjolin Date 2012-07-14 Time 18:23 Rev Time 0.00
Received By wjolin Date 2012-07-13 Time 12:56 Sent To  
Notes
2012-07-13 12:56:32TO WJ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-07-11 Cont ID  
Sent By hmoser Date 2012-07-11 Time 09:13 Rev Time 0.00
Received By hmoser Date 2012-07-02 Time 09:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-11 Cont ID  
Sent By hmoser Date 2012-06-22 Time 09:11 Rev Time 0.00
Received By hmoser Date 2012-06-15 Time 15:01 Sent To  
Notes
2012-06-18 15:25:12B--11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-07 Cont ID  
Sent By shill Date 2012-06-07 Time 17:42 Rev Time 0.00
Received By shill Date 2012-05-08 Time 18:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-07-11 Cont ID  
Sent By hmoser Date 2012-07-11 Time 09:05 Rev Time 0.00
Received By hmoser Date 2012-07-11 Time 09:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-18 Cont ID  
Sent By hmoser Date 2012-05-18 Time 13:57 Rev Time 0.00
Received By hmoser Date 2012-05-18 Time 13:24 Sent To  
Notes
2012-05-18 14:17:01PLANS DENIED
 PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER TABLE
 403.3 FBC (M) 2010
 REFER TO SECTION 503.2.1 CALCULATIONS OF HEATING AND
 COOLING LOADS.
 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-20 Cont ID  
Sent By lwagner Date 2012-06-20 Time 09:33 Rev Time 0.00
Received By lwagner Date 2012-06-20 Time 09:15 Sent To  
Notes
2012-06-20 09:34:39SINK TO BE INSTALLED DOWNSTREAM FROM WET VENT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-05-11 Cont ID  
Sent By lwagner Date 2012-05-11 Time 14:49 Rev Time 0.00
Received By lwagner Date 2012-05-11 Time 14:02 Sent To  
Notes
2012-05-11 14:49:21FBC PLUMBING 2010
 FBC ACCESSIBILITY 2010
 REVIEW #1
 DENIED:
  
 1. SHEET A-1 SHOWS RESTROOMS 5'-7" WIDE
 FBC ACCESSIBILITY 2010 - 604.3.1 AND 604.3.2 REQUIRE A
 5' CLEAR SPACE FOR THE WATER CLOSET WITH NO OTHER
 FIXTURES WITHIN THAT SPACE.
  
 2. SHEET A-5 SHOWS A SINK ATTACHED TO A WET VENT
 SYSTEM. THE SINK IS REQUIRED TO CONNECT DOWNSTREAM OF
 THE WET VENTED RESTROOM.
 FBC PLUMBING 909.1 HORIZONTAL WET VENT PERMITTED. ANY
 COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT.....ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2012-07-02 Cont ID  
Sent By jroach Date 2012-07-02 Time 14:54 Rev Time 0.00
Received By jroach Date 2012-07-02 Time 14:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-05-15 Cont ID  
Sent By jroach Date 2012-05-15 Time 13:25 Rev Time 0.00
Received By jroach Date 2012-05-15 Time 13:25 Sent To  
Notes
***NONE***