Plan Review Details - Permit 12050215
Plan Review Stops For Permit 12050215
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-07-05 Cont ID  
Sent By jgomez Date 2012-07-05 Time 17:00 Rev Time 0.00
Received By jgomez Date 2012-07-05 Time 11:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-06-08 Cont ID  
Sent By jgomez Date 2012-06-08 Time 15:14 Rev Time 0.00
Received By jgomez Date 2012-06-08 Time 15:09 Sent To  
Notes
2012-06-08 15:36:49BUILDING REVIEW 2ND REVIEW.
 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 AND 401 OF 2010 FBC-ENERGY CONSERVATION.
  
 2-WALL SECTION ON SHEET #2:
 A) REVISED CLOSET WALL SECTION SPECIFIES R-19 ROOF
 INSULATION. R-19 INSULATION DOESN'T FIT ON THE 2X6
 RAFTERS. REVISE AS REQUIRED. COORDINATE R-VALUE WITH
 THE ONE REQUIRED ON THE ENERGY CALCULATIONS.
 ***NOTE: ENERGY CALCULATIONS REQUIRE R-30 MIN. FOR
 CEILING INSULATION. SEE TABLE 402.1.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-16 Cont ID  
Sent By jgomez Date 2012-05-16 Time 09:59 Rev Time 0.00
Received By jgomez Date 2012-05-16 Time 09:17 Sent To  
Notes
2012-05-16 10:15:59RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE AND 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 401
 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3- WALL SECTION ON SHEET #2:
 A) CLOSET WALL SECTION SPECIFIES R-30 ROOF INSULATION.
 R-30 INSULATION DOESN'T FIT ON THE 2X6 RAFTERS. REVISE
 AS REQUIRED. COORDINATE R-VALUE WITH THE ONE REQUIRED
 ON THE ENERGY CALCULATIONS.
  
 B) SPECIFY 7/8" MIN. STUCCO THICKNESS AS REQUIRED BY
 TABLE R702.1(1).
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA 08-0410.09 SUBMITTED. CALCULATIONS ARE
 REQUIRED TO MEET THE DESIGN PRESSURES REQUIRED BY SEC.
 R301.2.1.4.3.
 NOTE: PROVIDE 2 COPIES OF RAS 117 CALCULATIONS AND ONE
 MORE COPY OF THE NOA. ONLY ONE NOA WAS SUBMITTED.
  
 B) CASEMENT WINDOW. PROVIDE 2 COPIES. ONLY ONE NOA WAS
 SUBMITTED.
  
 C) HORIZONTAL SLIDING WINDOW. PROVIDE 2 COPIES. ONLY
 ONE NOA WAS SUBMITTED.
  
 D) FIXED WINDOW. PROVIDE 2 COPIES. ONLY ONE NOA WAS
 SUBMITTED.
  
 E) SINGLE HUNG WINDOW. PROVIDE 2 COPIES. ONLY ONE NOA
 WAS SUBMITTED.
  
 F) WINDOW MULLIONS. PROVIDE 2 COPIES. ONLY ONE NOA WAS
 SUBMITTED.
  
 5- ENGINEER OF RECORD IS SPECIFYING 2500 PSF SOIL
 BEARING CAPACITY. SOIL TEST PROVIDED SPECIFIES 2000 PSF
 SOIL BEARING CAPACITY. ENGINEER OF RECORD TO REVIEW
 SOIL TEST REPORT AND REVISE PLANS AS REQUIRED. REVISE
 SPECIFICATIONS ON THE DESIGN STANDARDS ON SHEET 1,
 FOUNDATION NOTES ON SHEET 1 AND CLOSET WALL SECTION ON
 SHEET 2.
  
 6- SOIL TEST REPORT TO HAVE ENGINEER'S ORIGINAL SEAL
 AND SIGNATURE (NO COPIES) AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES. AND, PROVIDE 2 COPIES. ONLY ONE COPY
 WAS SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-09 Cont ID  
Sent By rlecky Date 2012-05-09 Time 12:56 Rev Time 0.00
Received By rlecky Date 2012-05-09 Time 12:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-07-05 Cont ID  
Sent By jgomez Date 2012-07-05 Time 17:00 Rev Time 0.00
Received By jgomez Date 2012-07-03 Time 18:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-08 Cont ID  
Sent By jgomez Date 2012-06-08 Time 16:01 Rev Time 0.00
Received By jgomez Date 2012-06-04 Time 08:47 Sent To  
Notes
2012-06-05 08:47:49SENT TO JULIO'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-16 Cont ID  
Sent By jgomez Date 2012-05-16 Time 14:04 Rev Time 0.00
Received By jgomez Date 2012-05-07 Time 13:58 Sent To  
Notes
2012-05-08 13:59:02SENT TO SHELF R4 FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-06-08 Cont ID  
Sent By jgomez Date 2012-06-08 Time 16:00 Rev Time 0.00
Received By jgomez Date 2012-06-08 Time 16:00 Sent To  
Notes
2012-06-08 16:01:06NO FEES MU-2012-9129 ON MAY 17,2012. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-05-16 Cont ID  
Sent By jgomez Date 2012-05-16 Time 09:56 Rev Time 0.00
Received By jgomez Date 2012-05-16 Time 09:56 Sent To  
Notes
2012-05-16 09:57:45PLEASE BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.

Review Stop Z ZONING
Rev No 1 Status P Date 2012-05-15 Cont ID  
Sent By jroach Date 2012-05-15 Time 13:32 Rev Time 0.00
Received By jroach Date 2012-05-15 Time 13:26 Sent To  
Notes
***NONE***