| 2012-05-16 10:15:59 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS. |
| | 2010 FLORIDA RESIDENTIAL CODE AND 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 401 |
| | OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| | VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 3- WALL SECTION ON SHEET #2: |
| | A) CLOSET WALL SECTION SPECIFIES R-30 ROOF INSULATION. |
| | R-30 INSULATION DOESN'T FIT ON THE 2X6 RAFTERS. REVISE |
| | AS REQUIRED. COORDINATE R-VALUE WITH THE ONE REQUIRED |
| | ON THE ENERGY CALCULATIONS. |
| | |
| | B) SPECIFY 7/8" MIN. STUCCO THICKNESS AS REQUIRED BY |
| | TABLE R702.1(1). |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117 |
| | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON |
| | LAST PAGE OF NOA 08-0410.09 SUBMITTED. CALCULATIONS ARE |
| | REQUIRED TO MEET THE DESIGN PRESSURES REQUIRED BY SEC. |
| | R301.2.1.4.3. |
| | NOTE: PROVIDE 2 COPIES OF RAS 117 CALCULATIONS AND ONE |
| | MORE COPY OF THE NOA. ONLY ONE NOA WAS SUBMITTED. |
| | |
| | B) CASEMENT WINDOW. PROVIDE 2 COPIES. ONLY ONE NOA WAS |
| | SUBMITTED. |
| | |
| | C) HORIZONTAL SLIDING WINDOW. PROVIDE 2 COPIES. ONLY |
| | ONE NOA WAS SUBMITTED. |
| | |
| | D) FIXED WINDOW. PROVIDE 2 COPIES. ONLY ONE NOA WAS |
| | SUBMITTED. |
| | |
| | E) SINGLE HUNG WINDOW. PROVIDE 2 COPIES. ONLY ONE NOA |
| | WAS SUBMITTED. |
| | |
| | F) WINDOW MULLIONS. PROVIDE 2 COPIES. ONLY ONE NOA WAS |
| | SUBMITTED. |
| | |
| | 5- ENGINEER OF RECORD IS SPECIFYING 2500 PSF SOIL |
| | BEARING CAPACITY. SOIL TEST PROVIDED SPECIFIES 2000 PSF |
| | SOIL BEARING CAPACITY. ENGINEER OF RECORD TO REVIEW |
| | SOIL TEST REPORT AND REVISE PLANS AS REQUIRED. REVISE |
| | SPECIFICATIONS ON THE DESIGN STANDARDS ON SHEET 1, |
| | FOUNDATION NOTES ON SHEET 1 AND CLOSET WALL SECTION ON |
| | SHEET 2. |
| | |
| | 6- SOIL TEST REPORT TO HAVE ENGINEER'S ORIGINAL SEAL |
| | AND SIGNATURE (NO COPIES) AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTES. AND, PROVIDE 2 COPIES. ONLY ONE COPY |
| | WAS SUBMITTED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |