Plan Review Details - Permit 12050060
Plan Review Stops For Permit 12050060
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-05-16 Cont ID  
Sent By lmartine Date 2012-05-16 Time 10:28 Rev Time 0.00
Received By lmartine Date 2012-05-16 Time 10:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-14 Cont ID  
Sent By shill Date 2012-05-14 Time 14:08 Rev Time 0.00
Received By shill Date 2012-05-14 Time 14:08 Sent To  
Notes
2012-05-14 14:18:14****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. PLEASE SUBMIT TWO SEPARATE PERMITS, ONE FOR EACH
 STRUCTURE, PER BUILDING OFFICIAL'S POLICY.
  
 2. PROVIDE A STRUCTURAL DETAIL FOR PROPOSED WOOD
 REPAIR. IN THE DETAIL SPECIFY STRAPS/CONNECTORS AS PER
 INSPECTOR'S INSTRUCTIONS. PROVIDE SPEC SHEETS FOR EACH
 STRAP/CONNECTOR, FBC RESIDENTIAL 301.1. INCLUDE WIND
 DESIGN CRITERIA (MINIMUM 170MPH EXPOSURE C).
  
 3. I WAS UNABLE TO LOCATE NS2Z; MP-36, MP-14, A23Z ARE
 NOT FOR UPLIFT USE. SPECIFY STRAPS/CONNECTORS
 APPROPRIATE FOR THE PROPOSED USE TO MEET WIND LOAD
 REQUIREMENTS (170MPH EXPOSURE C MINIMUM), CALCULATIONS
 SHOWING HOW UPLIFT REQUIREMENTS HAVE BEEN DETERMINED
 MAY BE REQUIRED.
  
 4. REVISE THE WINDOW PLAN TO SHOW SIZES OF PROPOSED
 WINDOW REPLACEMENT.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-16 Cont ID  
Sent By lmartine Date 2012-05-16 Time 10:27 Rev Time 0.00
Received By lmartine Date 2012-05-02 Time 08:05 Sent To  
Notes