Plan Review Details - Permit 12050036
Plan Review Stops For Permit 12050036
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-08-13 Cont ID  
Sent By shill Date 2012-08-13 Time 18:13 Rev Time 0.00
Received By shill Date 2012-08-13 Time 18:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-06-07 Cont ID  
Sent By shill Date 2012-06-07 Time 17:09 Rev Time 0.00
Received By shill Date 2012-06-07 Time 17:09 Sent To  
Notes
2012-06-07 17:09:56PLEASE REVISE THE INSTALLATION SHEDULE.
  
 SHUTTER TO GLASS SEPARATION - 4 1/2" CIRCLED ON PRODUCT
 APPROVAL SHEET 5 (SEE ATTACHED), BUT 3 1/2" PROPOSED.
  
 SEE SHEET 6, ANCHOR SPACING CIRCLED BUT NOT CONSISTENT
 WITH SPANS/SPACING ON THE INSTALLATION SHEDULE. A
 COUPLE EXAMPLES:
  
 OPENING 1, TOP (CONNECTION TYPE 1) 60.3 PSF, 10`.2"
 SPAN, NEED TO USE 11' ROW AND 70PSF COLUMN, 4"
 REQUIRED.
 BOTTOM, 5.5" REQUIRED FOR CONNECTION TYPE 6
 OPENINGS 2&3, 72.5PSF, 7.5' SPAN, 9" PROPOSED, NEED TO
 USE 80PSF AND 8' ROW, CANNOT USE.
  
 FIRST SUBMITTAL USED LOWER PRESSURES. SECOND SUBMITTAL
 HAS HIGHER PRESSURES PROPOSED. IT APPEARS THAT YOU ARE
 USING V(ULT) PRESSURES WITHOUT CONVERTING TO V(ASD) FOR
 USE WITH PRODUCT APPROVALS. IF YOU WOULD LIKE, YOU CAN
 USE FBC RESIDENTIAL TABLE 301.2(2) TO CALCULATE EACH
 OPENING OR YOU CAN USE +37.9/-50.7 "WORST CASE" (ZONE
 5, 10SF, 15MRH, EXPOSURE C).
  
 SAMANTHA HILL
 561-805-6724
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-05-29 Cont ID  
Sent By shill Date 2012-05-29 Time 17:31 Rev Time 0.00
Received By shill Date 2012-05-29 Time 17:23 Sent To  
Notes
2012-05-29 17:31:14****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. OK
  
 2. 9" SPACING DOES NOT MEET MINIMUMS IN PRODUCT
 APPROVAL FOR OPENINGS 8' AND GREATER, SEE SHEET 6,
 CONNECTION TYPE 1.
  
 ANCHOR SPACING FOR OPENINGS 5 THROUGH 8 WERE LEFT
 BLANK, PLEASE REVISE TO SHOW COMPLIANCE WITH FBC
 RESIDENTIAL 301.1, WIND.
  
 3. OK
  
 4. PLEASE INCLUDE INFORMATION REGARDING TYPE OF
 INSTALLATION; KNUCKLE OR LOCK/CENTERMATES IN ORDER TO
 DETERMINE SHUTTER GLASS SEPARATION REQUIRED, SEE SHEET
 5 OF PRODUCT APPROVAL.
  
 WIND ZONE 3 WAS MARKED ON PRODUCT APPROVAL, WEST PALM
 BEACH IS IN WIND ZONE 4 PER FBC RESIDENTIAL
 301.2.1.2.1. FIRST SUBMITTAL HAD A 4.5" SHUTTER GLASS
 SEPARATION BUT WAS REDUCED TO 3" ON THE SECOND
 SUBMITTAL. 3" DOES NOT COMPLY WITH THE TWO DIFFERENT
 OPTIONS ON SHEET 5.
 PLEASE PROVIDE REQUESTED INFORMATION (KNUCKLE OR
 CENTERMATE) AND REVISE INSTALLATION SCHEDULE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-10 Cont ID  
Sent By shill Date 2012-05-10 Time 12:45 Rev Time 0.00
Received By shill Date 2012-05-10 Time 12:45 Sent To  
Notes
2012-05-10 13:39:55****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SEE WIND MAP, WEST PALM BEACH LIES BETWEEN THE LINE
 FOR 160MPH AND 170MPH. FBC RESIDENTIAL 301.2. PLEASE
 USE 170MPH OR IF ANOTHER WIND SPEED BETWEEN 160MPH AND
 170MPH IS USED, PROVIDE INFORMATION REGARDING HOW THE
 WIND SPEED WAS DETERMINED.
  
 2. 9" SPACING DOES NOT MEET MINIMUMS IN PRODUCT
 APPROVAL FOR OPENINGS 8' AND GREATER, SEE SHEET 6,
 CONNECTION TYPE 1.
  
 3. SPANS SHOULD EQUAL BLADE LENGTH, SHOULD NOT BE THE
 SAME AS OPENING SIZE FOR A WALL MOUNT. PLEASE REVISE
 INSTALLATION SCHEDULE.
  
 4. PLEASE INCLUDE INFORMATION REGARDING TYPE OF
 INSTALLATION; KNUCKLE OR LOCK/CENTERMATES IN ORDER TO
 DETERMINE SHUTTER GLASS SEPARATION REQUIRED, SEE SHEET
 5 OF PRODUCT APPROVAL.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-08-13 Cont ID  
Sent By shill Date 2012-08-13 Time 18:13 Rev Time 0.00
Received By shill Date 2012-07-27 Time 12:15 Sent To  
Notes
2012-07-30 12:16:40GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-29 Cont ID  
Sent By shill Date 2012-05-29 Time 17:36 Rev Time 0.00
Received By shill Date 2012-05-23 Time 10:49 Sent To  
Notes
2012-05-23 10:49:20TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-10 Cont ID  
Sent By shill Date 2012-05-10 Time 13:40 Rev Time 0.00
Received By shill Date 2012-05-01 Time 16:23 Sent To  
Notes
2012-05-01 16:26:14MISC 1
  
  