| 2012-05-21 13:19:03 | BUILDING PLAN REVIEW |
| | PERMIT: 12040743 |
| | ADD: 319 CLEMATIS ST |
| | CONT: CLAY KOHLMEYER CGC |
| | TEL: (561)719-3429 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE COVER-SHEET CS-1 & LS-1 INDICATES THIS TO BE A |
| | LEVEL 1 ALTERATION, PLEASE REVIEW LEVEL II |
| | ALTERANITIONS, NEW WALLS WERE ADDED CREATING A LEVEL II |
| | ALTERATION. 404.1 EXISTING BUILDING CODE. |
| | |
| | 2) SHEET A-1.0: |
| | 2A) NEW DOORWAY BETWEEN HALLWAY 2 & 5 IS MISSING THE |
| | REQUIRED 18" LATCH SIDE OF THE DOORWAY. 2010 |
| | ACCESSIBILITY CODE, EXIST BUILDING CODE 701.3 & 2010 |
| | ACCESSIBILITY CODE 404.2.4 & FIGURE |
| | 404.2.4.1(A). |
| | |
| | 2B) 2010 EXISTING BUILDING CODE SECTION 706.1 WHICH |
| | REFERS TO THE FLORIDA ACCESSIBILITY CODE, PLEASE |
| | REVIEW202.4.1-2 , 20% DISPROPORTIONATE COST AND |
| | ACCESSIBLE FEATURES IN TTHE EVENT OF |
| | DISPROPORTIONALITY. |
| | THE FRONT ENTRY DOUBLE DOORS AND RECEPTION DOORS DO NOT |
| | MEET THE REQUIREMENTS OF THE 2010 FLORIDA ACCESSIBILITY |
| | CODE DOORS IN SERIES 404.2.6.A MINIMUM OF 4'-0" WOULD |
| | BE REQUIRED WHEN BOTH SETS OF DOORS ARE IN THE OPEN |
| | POSITION. |
| | |
| | 2C)FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND |
| | SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE |
| | PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY |
| | IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER |
| | ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH |
| | IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING |
| | AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND |
| | SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL |
| | OPENINGS." |
| | |
| | 3) DISCREPANCY BETWEEN A-2.0 & E-3 FOR THE EMERGENCY |
| | BACK UP BATTERY PACK LIGHTS TO QUANTITY AND LOCATION, |
| | FBC-B 106.1.2* ADDITIONAL INFORMATION & TABLE 1006.1 & |
| | 1006.1.2. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |