Plan Review Details - Permit 12040743
Plan Review Stops For Permit 12040743
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-01 Cont ID  
Sent By jwitmer Date 2012-06-01 Time 14:05 Rev Time 0.00
Received By jwitmer Date 2012-06-01 Time 14:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-21 Cont ID  
Sent By jwitmer Date 2012-05-21 Time 12:38 Rev Time 0.00
Received By jwitmer Date 2012-05-18 Time 16:46 Sent To  
Notes
2012-05-21 13:19:03BUILDING PLAN REVIEW
 PERMIT: 12040743
 ADD: 319 CLEMATIS ST
 CONT: CLAY KOHLMEYER CGC
 TEL: (561)719-3429
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE COVER-SHEET CS-1 & LS-1 INDICATES THIS TO BE A
 LEVEL 1 ALTERATION, PLEASE REVIEW LEVEL II
 ALTERANITIONS, NEW WALLS WERE ADDED CREATING A LEVEL II
 ALTERATION. 404.1 EXISTING BUILDING CODE.
  
 2) SHEET A-1.0:
 2A) NEW DOORWAY BETWEEN HALLWAY 2 & 5 IS MISSING THE
 REQUIRED 18" LATCH SIDE OF THE DOORWAY. 2010
 ACCESSIBILITY CODE, EXIST BUILDING CODE 701.3 & 2010
 ACCESSIBILITY CODE 404.2.4 & FIGURE
 404.2.4.1(A).
  
 2B) 2010 EXISTING BUILDING CODE SECTION 706.1 WHICH
 REFERS TO THE FLORIDA ACCESSIBILITY CODE, PLEASE
 REVIEW202.4.1-2 , 20% DISPROPORTIONATE COST AND
 ACCESSIBLE FEATURES IN TTHE EVENT OF
 DISPROPORTIONALITY.
 THE FRONT ENTRY DOUBLE DOORS AND RECEPTION DOORS DO NOT
 MEET THE REQUIREMENTS OF THE 2010 FLORIDA ACCESSIBILITY
 CODE DOORS IN SERIES 404.2.6.A MINIMUM OF 4'-0" WOULD
 BE REQUIRED WHEN BOTH SETS OF DOORS ARE IN THE OPEN
 POSITION.
  
 2C)FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND
 SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE
 PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH
 IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING
 AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND
 SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL
 OPENINGS."
  
 3) DISCREPANCY BETWEEN A-2.0 & E-3 FOR THE EMERGENCY
 BACK UP BATTERY PACK LIGHTS TO QUANTITY AND LOCATION,
 FBC-B 106.1.2* ADDITIONAL INFORMATION & TABLE 1006.1 &
 1006.1.2.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-01 Cont ID  
Sent By rlecky Date 2012-05-01 Time 15:15 Rev Time 0.00
Received By rlecky Date 2012-05-01 Time 14:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-06-01 Cont ID  
Sent By rferguso Date 2012-06-01 Time 12:33 Rev Time 0.00
Received By rferguso Date 2012-06-01 Time 12:33 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-05-21 Cont ID  
Sent By wjolin Date 2012-05-21 Time 14:23 Rev Time 0.00
Received By wjolin Date 2012-05-21 Time 14:10 Sent To  
Notes
2012-05-21 14:20:45319 CLEMATIS STREET - SUITE #300
 PERMIT #12040743
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 TRAVEL DISTANCE TO PORTABLE EXTINGUISHERS APPEAR TO
 EXCEED 75 FEET.
  
 NOTE: FIRE ALARM DEVICES SHOWN IN CORRIDOR ONLY;
 ADDITIONAL NOTIFICATION APPLIANCES WILL BE NEEDED
 WITHIN THE SUITE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-01 Cont ID  
Sent By jwitmer Date 2012-06-01 Time 14:05 Rev Time 0.00
Received By jwitmer Date 2012-06-01 Time 11:57 Sent To  
Notes
2012-06-01 11:57:14TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-29 Cont ID  
Sent By lmartine Date 2012-05-29 Time 08:59 Rev Time 0.00
Received By lmartine Date 2012-04-30 Time 12:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-05-03 Cont ID  
Sent By hmoser Date 2012-05-03 Time 13:23 Rev Time 0.00
Received By hmoser Date 2012-05-03 Time 11:57 Sent To  
Notes
2012-05-03 13:12:50PROVISO
 1) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR
 FIRE DAMPERS AT ROUGH INSPECTION. PER SECTION 607.2
 2010 FBC (M)
 2) REFER TO SECTION 601.4 BALANCED RETURN AIR 2010
 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2012-05-29 Cont ID  
Sent By aaponte Date 2012-05-29 Time 08:58 Rev Time 0.00
Received By lmartine Date 2012-05-29 Time 08:58 Sent To  
Notes
2012-05-29 08:59:01INTERIOR ONLY