Plan Review Details - Permit 12040736
Plan Review Stops For Permit 12040736
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-11 Cont ID  
Sent By shill Date 2012-06-11 Time 13:55 Rev Time 0.00
Received By shill Date 2012-06-11 Time 13:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-14 Cont ID  
Sent By shill Date 2012-05-14 Time 16:49 Rev Time 0.00
Received By shill Date 2012-05-11 Time 15:30 Sent To  
Notes
2012-05-14 17:22:31****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. INCLUDE WIND DESIGN DATA FBC 1603.1.4 INCLUDING
 DESIGN PRESSURES FOR STOREFRONT AND DOOR.
  
 2. THE STOREFRONT REFERENCED ON A3.01 IS A DOOR, PLEASE
 REVISE FBC 106.3.3.
  
 3. PROVIDE A LIFE SAFETY PLAN, FBC CHAPTER 10. LS 1.01
 AND 1.02 ARE REFERRED TO ON A .01, PLEASE PROVIDE.
  
 4. THE DOOR D2 APPEARS TO OBSTRUCT EGRESS WIDTH, REVISE
 OR SHOW COMPLIANCE WITH FBC 1005.2 BY PROVIDING
 DIMENSIONS.
  
 5. INCLUDE THE CERTIFICATE OF AUTHORIZATION FOR HRC
 DESIGNS REQUIRED BY FS 471.023 ON THE TITLE BLOCK,
 FAC61G15-23.002(3)(B).
  
 6. THE CITY OF WEST PALM BEACH LIES BETWEEN THE 160MPH
 AND 170MPH LINES, PLEASE REVISE WIND SPEED FBC 1609A.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-06-06 Cont ID  
Sent By rlecky Date 2012-06-06 Time 16:17 Rev Time 0.00
Received By rlecky Date 2012-06-06 Time 15:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-05-02 Cont ID  
Sent By rlecky Date 2012-05-02 Time 15:11 Rev Time 0.00
Received By rlecky Date 2012-05-02 Time 14:48 Sent To  
Notes
2012-05-02 15:05:57PROVIDE AN ELECTRICAL PLAN WITH AN ELECTRICAL RISER
 PLAN SHOWING IN DETAIL THE CHANGES TO THE EXISITING
 SYSTEM. PROVIDE A PANEL SCHEDULE FOR THE NEW AND
 EXISTING OFFICE SPACES WITH A SUMMARY LOAD CALCULATION.
 NEC 215.5
 ELECTRICAL PANELS CANNOT BE LOCATED IN CLOSETS AND
 STORAGE ROOMS. SHOW LOCATION OF RELOCATED PANEL A-2NEC
 408.17
 ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST
 BE GFCI PROTECTED. NEC 210.8
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-06-14 Cont ID  
Sent By wjolin Date 2012-06-14 Time 11:22 Rev Time 0.00
Received By wjolin Date 2012-06-14 Time 10:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-05-16 Cont ID  
Sent By ddaniels Date 2012-05-16 Time 10:20 Rev Time 0.00
Received By ddaniels Date 2012-05-16 Time 10:20 Sent To  
Notes
2012-05-16 10:27:15FIRE DEPARTMENT REVIEW ***DENIED***
  
 1. PROVIDE LIFE SAFETY PLANS SHEETS LS1.01 & LS1.02
 2. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
 3. THE SCOPE OF WORK SHALL BE INDICATED ON PLANS.
 4. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 5. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
 6. FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmartine Date 2012-05-29 Time 12:02 Sent To  
Notes
2012-05-31 12:25:31EXPEDITED
 2ND RUN
 B--1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-17 Cont ID  
Sent By shill Date 2012-05-17 Time 09:53 Rev Time 0.00
Received By shill Date 2012-04-30 Time 14:16 Sent To  
Notes
2012-04-30 14:17:07SENT TO B2 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-06-12 Cont ID  
Sent By hmoser Date 2012-06-12 Time 13:36 Rev Time 0.00
Received By hmoser Date 2012-06-12 Time 13:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-15 Cont ID  
Sent By hmoser Date 2012-05-15 Time 15:45 Rev Time 0.00
Received By hmoser Date 2012-05-15 Time 15:16 Sent To  
Notes
2012-05-15 15:45:11PLANS DENIED
 NOTES SAY YOU ARE RELOCATING 22 RETURN AIR GRILLES
 PLAN ONLY SHOWS ONE
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-07 Cont ID  
Sent By lwagner Date 2012-06-07 Time 16:22 Rev Time 0.00
Received By lwagner Date 2012-06-07 Time 15:14 Sent To  
Notes
2012-06-07 16:12:49***PROVISO***
 IN SUITE 5 PLEASE MOVE THE LAVATORY IN THE WOMENS ROOM
 TO OUTSIDE OF THE 60" CLEAR FLOOR SPACE FOR THE WATER
 CLOSET.
 FBC ACCESSIBILITY 604.3.2

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-05-07 Cont ID  
Sent By lwagner Date 2012-05-07 Time 10:19 Rev Time 0.00
Received By lwagner Date 2012-05-04 Time 15:06 Sent To  
Notes
2012-05-07 09:11:30FBC 2010 PLUMBING
 FBC 2010 ACCESSIBILITY
 REVIEW #1
 DENIED:
  
 SEET A2.01 TABLE FOR SUITE 5 LISTS RESTROOMS AS UNISEX.
 SEPARATE FACILITIES ARE REQUIRED AND SHALL MEET THE
 REQUIREMENTS OF THE ACCESSIBILITY CODE.
 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE
 REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR
 EACH SEX.
  
 SHEET A2.01 FOR SUITE 1 THE RESTROOMS HAVE BEEN
 RECONFIGURED. THE MENS ROOM WOULD NOT COMPLY WITH FBC
 ACCESSIBILITY 603.2 TURNING SPACE AND 602.3 DOOR SWING.
 ALSO, SEE FBC ACCESSABILITY 202.4.1 AND 202.4.2
 DISPROPORTIONATE COST.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-05-10 Cont ID  
Sent By lfranco Date 2012-05-10 Time 10:22 Rev Time 0.00
Received By lfranco Date 2012-05-10 Time 10:22 Sent To  
Notes
2012-05-10 10:22:47PLANNING: **** ZONING REVIEW NOT REQUIRED: INTERIOR
 WORK ONLY AND THE VALUE OF PROPOSED WORK DOES NOT
 EXCEED 50% OF THE IMPROVEMENT VALUE. ****