Plan Review Details - Permit 12040677
Plan Review Stops For Permit 12040677
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-14 Cont ID  
Sent By shill Date 2012-05-14 Time 09:43 Rev Time 0.00
Received By shill Date 2012-05-14 Time 09:43 Sent To FIRE
Notes
2012-05-14 09:53:53****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THE PROPOSED CONSTRUCTION OBSTRUCTS THE EXIT
 DISCHARGE. PROVIDE THE OCCUPANT LOAD WHICH THIS DOOR
 SERVES AND DOOR WIDTH, AS WELL AS MORE INFORMATION
 REGARDING THE EXIT DISCHARGE, SEE FBC1003.3.3, 1003.6,
 1027.6.2.
  
 2. THE PLAN IS TO BE PREPARED BY A DESIGN PROFESSIONAL,
 FS471, 481. IT APPEARS THAT A PARTIAL LIFE SAFETY PLAN
 IS REQUIRED IN ORDER TO DEMONSTRATE CODE COMPLIANCE.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-05-16 Cont ID  
Sent By ddaniels Date 2012-05-16 Time 09:44 Rev Time 0.00
Received By ddaniels Date 2012-05-16 Time 09:43 Sent To  
Notes
2012-05-16 09:50:22FIRE DEPARTMENT REVIEW ***DENIED***
  
  
 1. THE SCOPE OF WORK SHALL BE INDICATED ON PLANS.
  
 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
  
 3. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK
 INFORMATION.
  
 5.THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2010.
  
 6. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-21 Cont ID  
Sent By shill Date 2012-05-21 Time 11:38 Rev Time 0.00
Received By shill Date 2012-04-26 Time 14:24 Sent To  
Notes
2012-04-26 14:24:57ZONING

Review Stop Z ZONING
Rev No 1 Status F Date 2012-05-02 Cont ID  
Sent By eschneid Date 2012-05-02 Time 16:55 Rev Time 0.50
Received By eschneid Date 2012-04-30 Time 10:27 Sent To B
Notes
2012-05-02 16:51:30FAILED
  
 1) PROVIDE WRITTEN PROOF THAT THE PROPOSED COLUMBARIUM
 WILL COMPLY WITH ALL APPLICABLE STATE AND COUNTY
 REQUIREMENTS.
  
 2) PROVIDE A COPY OF THE WRITTEN STATEMENT FROM THE
 GOVERNING BODY OF THE CHURCH ON HOW THE PROPOSED
 COLUMBARIUM WILL BE OPERATED AND MAINTAINED.
  
 3) PROVIDE A SITE PLAN SHOWING WHERE THE COLUMBARIUM
 WILL BE LOCATED. THE CUT SHEET PROVIDED WITH THE
 APPLICATION DOES NOT PROVIDE ENOUGH INFORMATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
  
  
2012-04-30 10:27:39GIVEN TO ES