Plan Review Details - Permit 12040652
Plan Review Stops For Permit 12040652
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-05 Cont ID  
Sent By jwitmer Date 2012-06-05 Time 16:38 Rev Time 0.00
Received By jwitmer Date 2012-06-05 Time 16:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-30 Cont ID  
Sent By jwitmer Date 2012-04-30 Time 14:53 Rev Time 0.00
Received By jwitmer Date 2012-04-30 Time 14:33 Sent To  
Notes
2012-04-30 15:06:44BUILDING PLAN REVIEW
 PERMIT:12040652
 ADD: 7422 S DIXIE HWY
 CONT: LANTANA CONSTRUCTION
 TEL: (561)312-3600
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET 1 PLEASE SEE NEW 2010 ACCESSIBILITY CODE AND
 FIGURE 604.8.1.6 WHEELCHAIR ACCESSIBLE TOILET
 COMPARTMENT IN NEW CONSTRUCTION. THE MINIMUM DIMENSIONS
 ARE 84 1/2 " X 60" WITH THE WATERCLOSET AND LAV LOCATED
 ON THE 84 1/2" WALL. THE LAV CAN NOT OVER LAP INTO THE
 CLEAR FLOOR SPACE FOR THE WATER CLOSET.SEE FIGURE
 604.3.1.
  
 2) NEW TO THE 2010 ACCESSIBILITY CODE GRAB BARS ARE NO
 LONGER MEASURED TO THE CENTER LINE BUT TO THE TOP OF
 THE BAR PER SECTION 604.8.1.5/ 609.4 THE TOP OF THE
 GRIPPING SURFACE 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-05-30 Cont ID  
Sent By rlecky Date 2012-05-30 Time 11:31 Rev Time 0.00
Received By rlecky Date 2012-05-30 Time 11:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-02 Cont ID  
Sent By rlecky Date 2012-05-02 Time 14:47 Rev Time 0.00
Received By rlecky Date 2012-05-02 Time 14:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-05-15 Cont ID  
Sent By ddaniels Date 2012-05-15 Time 16:03 Rev Time 0.00
Received By ddaniels Date 2012-05-15 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-14 Cont ID  
Sent By lwagner Date 2012-06-14 Time 12:35 Rev Time 0.00
Received By lwagner Date 2012-05-29 Time 17:37 Sent To  
Notes
2012-05-29 17:43:55B8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-23 Cont ID  
Sent By hmoser Date 2012-05-23 Time 09:05 Rev Time 0.00
Received By hmoser Date 2012-04-25 Time 07:43 Sent To  
Notes
2012-04-26 07:51:45B14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-06-05 Cont ID  
Sent By jwitmer Date 2012-06-05 Time 17:06 Rev Time 0.00
Received By jwitmer Date 2012-06-05 Time 17:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-23 Cont ID  
Sent By hmoser Date 2012-05-23 Time 09:05 Rev Time 0.00
Received By hmoser Date 2012-05-23 Time 08:30 Sent To  
Notes
2012-05-23 09:05:11PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS WITH THE PLANS.
 PER TABLE 403.3 2010 FBC (M)
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPERS
 2010 FLORIDA ENERGY CODE
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-14 Cont ID  
Sent By lwagner Date 2012-06-14 Time 12:35 Rev Time 0.00
Received By lwagner Date 2012-06-14 Time 11:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-05-04 Cont ID  
Sent By lwagner Date 2012-05-04 Time 15:03 Rev Time 0.00
Received By lwagner Date 2012-05-04 Time 14:54 Sent To  
Notes
2012-05-04 15:03:27FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 PLEASE SEE BUILDING REVIEW NOTES BELOW:
  
 1) SHEET 1 PLEASE SEE NEW 2010 ACCESSIBILITY CODE AND
 FIGURE 604.8.1.6 WHEELCHAIR ACCESSIBLE TOILET
 COMPARTMENT IN NEW CONSTRUCTION. THE MINIMUM DIMENSIONS
 ARE 84 1/2 " X 60" WITH THE WATERCLOSET AND LAV LOCATED
 ON THE 84 1/2" WALL. THE LAV CAN NOT OVER LAP INTO THE
 CLEAR FLOOR SPACE FOR THE WATER CLOSET.SEE FIGURE
 604.3.1.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2012-05-01 Cont ID  
Sent By eschneid Date 2012-05-01 Time 12:17 Rev Time 0.50
Received By eschneid Date 2012-05-01 Time 12:17 Sent To  
Notes
2012-05-01 12:18:15INTERIOR WORK ONLY, LESS THAN 50% STRUCTURE VALUE PAST
 YEAR