Plan Review Details - Permit 12040590
Plan Review Stops For Permit 12040590
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-04-28 Cont ID  
Sent By ddaniels Date 2012-04-28 Time 22:19 Rev Time 0.00
Received By ddaniels Date 2012-04-28 Time 21:02 Sent To  
Notes
2012-04-28 22:18:40FIRE PLAN REVIEW
 PERMIT #12040590
 ADDRESS: 100 CLEMATIS STREET
  
 PLANS REVIEWED BY FIRE ***APPROVED***
  
  
 1.) TENT SHALL BE OF THE OPEN AREA/NO SIDES TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
 2.) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 3.) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6733
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-28 Cont ID  
Sent By ddaniels Date 2012-04-28 Time 22:23 Rev Time 0.00
Received By ddaniels Date 2012-04-28 Time 22:23 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved