| Plan Review Stops For Permit 12040569 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2012-09-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-09-13 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-09-13 |
Time |
09:12 |
Sent To |
FIRE |
|
| Notes |
| 2012-09-13 09:13:39 | ****PROVISO**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PROVIDE ORIGINAL SIGNED AND SEALED A1.0, LIFE SAFETY | | | PLAN, AT INSPECTION. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2012-09-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-09-12 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-09-12 |
Time |
13:25 |
Sent To |
FIRE |
|
| Notes |
| 2012-09-12 13:28:11 | ****PROVISO**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | ****REVISION REQUIRED**** | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. SEE PREVIOUS LIST, OCCUPANCY CLASSIFICATION AND | | | DESIGNATION AS CHANGE OF OCCUPANCY (WHICH APPEARS TO BE | | | APPLICABLE) IS TO BE INCLUDED ON THE PLAN. | | | | | | 2. THE ADDRESS ON THE PLAN IS SYNNEX RACKING, AND THE | | | PLAN IS LABELED A "LIFE SAFETY/RACKING PLAN." PLEASE | | | REVISE; REMOVE THE JOB WHICH IS LOCATED IN MIAMI AND | | | INCLUDE THE ADDRESS, JOB NAME FOR THIS PROJECT. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2012-08-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-08-17 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-08-13 |
Time |
17:19 |
Sent To |
|
|
| Notes |
| 2012-08-17 09:00:55 | ****CORRECTIONS**** | | | ****REVISED PER EMAIL FROM ENGINEER 8/22/12**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PLEASE INCLUDE OCCUPANCY CLASSIFICATION. CLASSROOMS | | | ARE EDUCATIONAL, FBC 305. CURRENT PLAN SHOWS | | | CLASSROOMS. PER ENGINEER, THIS IS DAY CARE ONLY. | | | | | | IF THIS IS EDUCATIONAL, THIS IS A CHANGE OF OCCUPANCY. | | | REVISE PLAN TO INCLUDE THIS INFORMATION, SEE ALSO FBC | | | 443 REGARDING ADDITIONAL REQUIREMENTS FOR EDUCATIONAL | | | OCCUPANCY. | | | | | | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | | FAC9N-3. THE NOA REFERENCED ON THE PLAN (10-1203.03) IS | | | SUPERSEDED BY ANOTHER NOA; PROVIDE CURRENT PRODUCT | | | APPROVAL. PLEASE MARK OPTIONS PROPOSED ON THE PRODUCT | | | APPROVAL. | | | | | | 3. PROVIDE A REASONABLE VALUE FOR THE PROPOSED WORK AND | | | FOR WORK DONE PREVIOUSLY WITHOUT PERMIT WHICH WILL BE | | | INCLUDED UNDER THE SCOPE OF THIS PERMIT, FBC 109.3. | | | | | | 4. FBC ACCESSIBILITY 202.3, 202.4, PROVIDE INFORMATION | | | REGARDING COMPLIANCE OF THE ACCESSIBLE PATH OF TRAVEL | | | AND THE ELEMENTS LISTED. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2012-06-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-06-28 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-06-28 |
Time |
18:52 |
Sent To |
|
|
| Notes |
| 2012-06-28 18:53:18 | ****CORRECTIONS**** | | | ****PLAN REVIEW IN PROGRESS*** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. CONFIRM THAT THIS FACILITY HAS A FIRE ALARM SYSTEM | | | AS THIS NO LONGER FALLS UNDER THE EXCEPTION, FBC 436.7. | | | | | | 2. ENGINEER WHO SIGNED AND SEALED THE PLAN NO LONGER | | | HAS A LICENSE TO PRACTICE ENGINEERING IN FLORIDA, SEE | | | WWW.MYFLORIDALICENSE.COM. PLEASE SUBMIT PLANS DESIGNED | | | BY A LICENSED DESIGN PROFESSIONAL. | | | | | | 3. PROVIDE A SITE PLAN SHOWING LOCATION OF AFFECTED | | | WALL AND DISTANCE TO PROPERTY LINE OR OTHER STRUCTURES, | | | FBC 602, 705. MORE INFORMATION MAY BE REQUIRED. | | | | | | 4. PROVIDE OCCUPANT LOAD AND SQUARE FOOT AREA FOR EACH | | | ROOM, FBC 1037.2. | | | | | | 5. SEE FBC 709.1, RECONFIGURED SPACES, NO MECHANICAL | | | INFORMATION PROVIDED, PLEASE ADDRESS. MECHANICAL REVIEW | | | WILL BE REQUIRED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-05-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-05-04 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-05-04 |
Time |
15:44 |
Sent To |
FIRE |
|
| Notes |
| 2012-05-07 10:06:14 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. OUR RECORDS DO NOT SHOW INTERIOR PARTITION WALLS AS | | | SHOWN ON THE PLAN. ORIGINAL BUILDING PLANS SHOW A LARGE | | | OPEN SPACE, AND OUR RECORD DEPARTMENT WAS UNABLE TO | | | LOCATE A RENOVATION PERMIT FOR THIS ADDRESS. | | | | | | PLEASE SEE FBC 1037 REGARDING MEANS OF EGRESS | | | REQUIREMENTS, AND ALSO PLEASE SEE FBC 1037.6 REGARDING | | | MEANS OF EGRESS FROM EACH SPACE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-08-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-08-20 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-08-20 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2012-09-13 |
|
|
Cont ID |
|
| Sent By |
ddaniels |
Date |
2012-09-13 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
ddaniels |
Date |
2012-09-13 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2012-08-25 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-08-25 |
Time |
20:56 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-08-25 |
Time |
20:43 |
Sent To |
B |
|
| Notes |
| 2012-08-25 20:57:14 | SEE BUILDING DEPT COMMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2012-06-21 |
|
|
Cont ID |
|
| Sent By |
rferguso |
Date |
2012-06-21 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
rferguso |
Date |
2012-06-21 |
Time |
14:02 |
Sent To |
B |
|
| Notes |
| 2012-06-21 14:04:41 | DELIVERED TO SAMANTHA |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2012-05-07 |
|
|
Cont ID |
|
| Sent By |
ddaniels |
Date |
2012-05-07 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
ddaniels |
Date |
2012-05-07 |
Time |
10:08 |
Sent To |
Z |
|
| Notes |
| 2012-05-07 10:16:19 | FIRE DEPARTMENT REVIEW ****DENIED*** | | | ADDRESS: 391 VALLEY FORGE ROAD | | | PERMIT # 12040569 | | | CONTRACTOR: ALLCRETE CONSTRUCTION | | | PHONE: (305) 592-6255 | | | | | | | | | | | | 1.) SPECIAL MEANS OF EGRESS FEATURES | | | | | | WHERE THE ROOM OR SPACE COMPLIES WITH THE FOLLOWING: | | | | | | (A) DOORS SHALL EXIST THAT ALLOW TRAVEL BETWEEN | | | ADJACENT ROOMS. | | | | | | (B) DOORS USED TO TRAVEL FROM ROOM TO ROOM SHALL | | | PROVIDE ON OF THE FOLLOWING: | | | I. DIRECT ACCESS TO EXIS IN BOTH DIRECTIONS | | | II. DIRECT ACCESS TO AN EXIT IN ONE DIRECTION AND TO A | | | SEPARATE SMOKE COMPARTMENT THAT PROVIDES ACCESS TO | | | ANOTHER EXIT IN THE OTHER DIRECTION | | | | | | (C) THE CORRIDOR SHALL BE SEPARATED FROM THE ROOMS BY A | | | WALL THAT RESISTS THE PASSAGE OF SMOKE, AND ALL DOORS | | | BETWEEN THE ROOMS AND THE CORRIDOR SHALL BE SELFCLOSING | | | IN ACCORDANCE WITH 7.2.1.8 OF NFPA 101 CHAPTER 7 | | | SECTION 5 A-F. | | | | | | (D) THE LENGTH OF TRAVEL TO EXITS ALONG SUCH PATHS | | | SHALL NOT EXCEED 150FT. | | | | | | (E) EACH COMMUNICATING DOOR SHALL BE MARKDED IN | | | ACCORDANCE WTIH SECTION 7.10. | | | | | | (F) NO LOCKING DEVICE SHALL BE PERMITTED ON THE | | | COMMUNICATING DOORS. | | | | | | | | | | | | DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | OFFICE OF THE FIRE MARSHAL | | | (561) 805-6722 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-09-12 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2012-09-12 15:39:17 | ROUTED TO FIRE DESK FOR DD REVIEW | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2012-08-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-08-28 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-07-26 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2012-07-26 14:58:23 | SENT TO SAMANTHA'S DESK FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-06-29 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-06-20 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2012-06-20 13:42:39 | TO FIRE | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-05-09 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2012-05-09 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2012-04-23 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2012-05-09 16:17:54 | FILED UNDER SMALL BIN "A" | | 2012-05-04 16:07:44 | 5/4 TO FIRE | | | | | 2012-04-24 10:49:48 | SENT TO BUILDING UNDER $5000 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2012-08-21 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2012-08-21 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2012-08-21 |
Time |
12:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2012-09-12 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-09-12 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-09-11 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2012-09-11 13:26:19 | FACILITY HAS EXISTING DRINKING FOUNTAIN AND LAUNDRY TUB | | | LISTED IN REVIEW #1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2012-09-12 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-08-20 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-08-20 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2012-08-20 13:50:25 | UPDATED IN REVIEW # 2 | | | | | | FBC EXISTING BUILDING CODE 2010 | | | FBC ACCESSIBILITY CODE 2010 | | | FBC PLUMBING CODE 2010 REVIEW #1 | | | DENIED: | | | | | | FBC PLUMBING TABLE 403.1 | | | DAY CARE AND EDUCATIONAL OCCUPANCIES REQUIRE DRINKING | | | FOUNTAINS AND A SERVICE SINK. THE SUBMITTED PLAN DOES | | | NOT SHOW THESE FIXTURES (HEALTH DEPT. REGULATIONS ALSO | | | REQUIRE THESE FIXTURES - ARTICLE X #46 & #48). | | | | | | 2. FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO | | | FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH | | | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH | | | 602.7. | | | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES | | | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE | | | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING | | | FOUNTAINS. | | | 602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR FLOOR | | | OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A | | | FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE | | | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. | | | EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305 SHALL | | | BE PERMITTED AT UNITS FOR CHILDREN'S USE WHERE THE | | | SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND AND IS 3 1/2 INCHES (90 MM) MAXIMUM | | | FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS. | | | | | | | | | ****INFORMATIONAL**** | | | 3. FBC 2012 TABLE 1004.1.1 | | | FROM THE BUILDING REVIEW COMMENTS A CHANGE OF OCCUPANCY | | | - EDUCATIONAL OCCUPANCIES ARE 20 S.F. PER OCCUPANT. THE | | | TOILET FACILITIES SHOWN WOULD BE SUFFICIENT. | | | | | | PLEASE SEE THE HEALTH DEPT. WEB SITE FOR REQUIREMENTS: | | | HTTP://WWW.PBCHD.COM/PDFS/ENVIRONMENTAL/CHILDCARE/PBCHD | | | _RULES_AND_REGULATIONS_GOVERNING_CHILD_CARE_FACILITIES. | | | PDF | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2012-05-09 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2012-05-09 |
Time |
16:08 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2012-05-08 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2012-05-09 16:09:29 | VALUE LESS THAN 50% OF STRUCTURE, INTERIOR WORK ONLY. | | 2012-05-08 10:28:22 | GIVEN TO ES |
|
|