Plan Review Details - Permit 12040446
Plan Review Stops For Permit 12040446
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-08-08 Cont ID  
Sent By jwitmer Date 2012-08-03 Time 11:40 Rev Time 0.00
Received By jwitmer Date 2012-08-02 Time 16:46 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-06-26 Cont ID  
Sent By jwitmer Date 2012-06-26 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2012-06-26 Time 15:12 Sent To  
Notes
2012-06-26 15:24:56BUILDING PLAN REVIEW
 PERMIT: 12040446
 ADD: 1590 FLORIDA MANGO RD
 CONT: ROUND HILL DEVELOPMENT GROUP
 TEL: (561)718-0831
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2)COMPLIED.
  
 3) SEMI COMPLIED. SHEET A-2 AND LS SHEETS NEED TO SHOW
 DOOR SWING IN THE SAME DIRECTION. SHEET A-2 DOES NOT
 INDICATE OCCUPANCY SEPERATION BETWEEN THE ASSEMBLY AND
 STORAGE OCCUPANCY, PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B TABLE 508.3.3 AND OPENING PROTECTIVES (DOORS) PER
 TABLE 715.4.
  
 4) SHEET A--2A INDICATES NEW A/C EQUIPMENT ON CONCRETE
 PADS AT A ELEVATION OF 13.5'. NOTE THIS IS THE MINIMUM
 BASE FLOOD ELEVATION FOR SLABS LOCATED IN A FLOOD ZONE.
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED
 BEFORE:
 1) PERMIT ISSUANCE.
 2) AFTER SLAB IS POURED
 3) BEFORE ISSUANCE OF CERTIFICATE OF OCCUPANCY.
 SUBMITTED ELEVATION CERTIFICATE INDICATES SEE SECTION
 "C" FINISHED CONSTRUCTION.
 THIS IS A NEW PROJECT AND THE DOCUMENT SHOULD BE
 CHECKED "CONSTRUCTION DOCUMENTS" NOT FINISHED
 CONSTRUCTION.
  
 FEMA ELEVATION CERTIFICATE SECTION C (E) MISSING
 COMMENT SECTION DESCRIBE TYPE OF EQUIPMENT AND LOCATION
 IN COMMENTS BACK OF SHEET, MISSING.
  
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 MARCH 31, 2012.
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS
 NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES
 MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED
 ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW
 FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 5) COMPLIED.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) SEE SHEET A-2 HARDWARE SCHEDULE AND USE OF MANUAL
 FLUSH BOLTS WITHIN THE HARDWARE SCHEDULE.
  
 1008.1.8.4 BOLT LOCKS. MANUALLY OPERATED FLUSH BOLTS OR
 SURFACE BOLTS ARE NOT PERMITTED. ALL HARDWARE MUST BE
 DIRECT ACTING REQUIRING NO MORE THAN ONE OPERATION.
 DOUBLE CYLINDER DEAD BOLTS, REQUIRING A KEY FOR
 OPERATION ON BOTH SIDES, ARE PROHIBITED ON REQUIRED
 MEANS OF EGRESS DOORS UNLESS THE LOCKING DEVICE IS
 PROVIDED WITH A KEY WHICH CANNOT BE REMOVED WHEN THE
 DOOR IS LOCKED FROM THE INSIDE. ONLY ONE LOCKING OR
 LATCHING DEVICE SHALL BE PERMITTED ON A DOOR OR ON ONE
 LEAF OF A PAIR OF DOORS.
 SEE EXECPTION #2 FOR STORAGE OR EQUIPMENT ROOMS.
  
 1008.1.8.3 LOCKS AND LATCHES (3). WHERE EGRESS DOORS
 ARE USED IN PAIRS, APPROVED AUTOMATIC FLUSH BOLTS SHALL
 BE PERMITTED TO BE USED, PROVIDED THAT THE DOOR LEAF
 HAVING THE AUTOMATIC FLUSH BOLTS HAS NO DOORKNOB OR
 SURFACE-MOUNTED HARDWARE.
  
 8) THE NEW BACK EXIT DOOR MISSING THE MANEUVERING
 CLEARANCES REQUIRED BY THE NEW STORAGE ROOM 2010 FBC
 ACCESSIBILITY 404.2.4 & FIGURE 404.2.4.1 (C).
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-03 Cont ID  
Sent By jwitmer Date 2012-05-03 Time 12:05 Rev Time 0.00
Received By jwitmer Date 2012-05-01 Time 15:45 Sent To  
Notes
2012-05-01 15:48:31BUILDING PLAN REVIEW
 PERMIT: 12040446
 ADD: 1590 FLORIDA MANGO RD
 CONT: ROUND HILL DEVELOPMENT GROUP
 TEL: (561)718-0831
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE A LIFE SAFETY SHEET FROM THE MAIN ICE
 SCATING FACILITY INDICATING THE TOTAL OCCUPANT LOAD,
 AMOUNT OF OCCUPANTS THAT WILL BE EXITING EACH OF THE
 EXITS. THE SHARED EXIT BETWEEN THE EXISTING FACILITY
 AND NEW GYM FACILITY WILL NEED TO BE REVIEWED FOR CODE
 COMPLIANCE FOR EXITING. 2010 FBC-B 106.3.5.1.1(7) * &
 TABLE 1016.1. PLEASE PROVIDE DISTANCES FROM BOTH THE
 SKATING RINK AND THE NEW GYM FOR EXIT ACCESS TRAVEL
 DISTANCES SINCE THE EXIT PASSAGEWAY IS BEING REMOVED,
 THIS TENANT SPACE BEFORE WAS CLASSIFIED AS A WARE HOUSE
 WHICH WOULD REQUIRE THE EXIT PASSAGE WAY TO THE EXIT
 DISCHARGE. NOW WE WILL NEED TO REVIEW THE PLANS FOR THE
 EXIT ACCESS FOR ASSEMBLY OCCUPANCY AND TRAVEL DISTANCES
 ALLOWED.
  
 2) THE PLANS SHEET A-2 INDICATE ONE LEAF OF THE DOUBLE
 DOORS IS TO BE WELDED SHUT. DOORS CAN NOT BE WELDED
 SHUT AND LOOK LIKE A ACTIVE DOOR, OCCUPANTS WILL STILL
 TRY GOING THROUGH THAT WELDED SHUT OPENING. THE DOUBLE
 DOORS SHOULD BE REMOVED AND REPLACED WITH A SINGLE
 DOOR.
 2010 FBC-B 1008.1 MEANS OF EGRESS DOORS SHALL BE
 READILY DISTINGUISHABLE FROM THE ADJACENT CONSTRUCTION
 AND FINISHES SUCH THAT THE DOORS ARE EASILY
 RECOGNIZABLE AS DOORS. MIRRORS OR SIMILAR REFLECTING
 MATERIALS SHALL NOT BE USED ON MEANS OF EGRESS DOORS.
 MEANS OF EGRESS DOORS SHALL NOT BE CONCEALED BY
 CURTAINS, DRAPES, DECORATIONS OR SIMILAR MATERIALS.
 2010 EXIST BUILDING CODE 912.4.3. EGRESS CAPACITY.
  
 3) SHEET A-2 DOES NOT INDICATE OCCUPANCY SEPERATION
 BETWEEN TTHE ASSEMBLY AND STORAGE OCCUPANCY, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B TABLE 508.3.3 AND
 OPENING PROTECTIVES (DOORS) PER TABLE 715.4.
  
 4) SHEET A--2A INDICATES NEW A/C EQUIPMENT ON CONCRETE
 PADS AT A ELEVATION OF 13.5'. NOTE THIS IS THE MINIMUM
 BASE FLOOD ELEVATION FOR SLABS LOCATED IN A FLOOD ZONE.
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 MARCH 31, 2012.
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS
 NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES
 MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED
 ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW
 FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 5) PLEASE PROVIDE THE TOTAL SQUARE FOOTAGE FOR THIS
 BUILDING, HOW MANY SQ FT ARE ASSEMBLY AND HOW MANY SQ
 FT ARE OF OTHER OCCUPANCIES, CONCERNS ARE THTE BUILDING
 WAS NOT BUILT ORIGINALLY AS AN A-4 ASSEMBLY OCCUPANCY
 IF THE BUILDING STILL MEETS THE MINIMUM BUILDING TYPE
 FOR THE A-4 ASSEMBY OCCUPANCY PLEASE PROVIDE ANY AREA
 FRONTAGE INCREASES TAKEN AND IF THE TOTAL BUILDING IS
 FIRE SPRINKLERED FOR AREA INCREASES. 2010 FBC-B TABLE
 503, 2010 EXISTING BUILDING CODE 901.3.1.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-07 Cont ID  
Sent By rlecky Date 2012-05-07 Time 10:46 Rev Time 0.00
Received By rlecky Date 2012-05-07 Time 10:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-07-30 Cont ID  
Sent By rferguso Date 2012-07-30 Time 13:53 Rev Time 0.00
Received By rferguso Date 2012-07-30 Time 13:53 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-06-15 Cont ID  
Sent By wjolin Date 2012-06-15 Time 14:17 Rev Time 0.00
Received By wjolin Date 2012-06-15 Time 13:29 Sent To  
Notes
2012-06-15 14:17:561590 NORTH FLORIDA MANGO ROAD
 PERMIT #12040446
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****ORIGINAL COMMENTS HAVE NOT BEEN ADDRESSED*****
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 MANUAL FLUSH BOLTS ARE NOT PERMITTED ON EGRESS DOORS.
  
 FOR DOORS EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE, NO
 OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC/FIRE HARDWARE.
  
 SEVERAL SHEETS INCORRECTLY MAKE CODE REFERENCES TO AN
 "M" (MERCANTILE) OCCUPANCY.
  
 COORDINATE THE DOUBLE DOOR SWING DIRECTION OF THE
 STORAGE ROOM BETWEEN DRAWINGS. THE LIFE SAFETY DRAWING
 SHOWS A SWING DIRECTION OPPOSITE FROM THE OTHER PLANS.
  
 THE MEPF PLANS ARE NOT SIGNED OR SEALED BY THE
 PROFESSIONAL ENGINEER.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-27 Cont ID  
Sent By wjolin Date 2012-04-27 Time 13:53 Rev Time 0.00
Received By wjolin Date 2012-04-27 Time 12:55 Sent To  
Notes
2012-04-27 13:53:481590 NORTH FLORIDA MANGO ROAD
 PERMIT #12040446
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 MANUAL FLUSH BOLTS ARE NOT PERMITTED ON EGRESS DOORS.
  
 FOR DOORS EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE, NO
 OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC/FIRE HARDWARE.
  
 SEVERAL SHEETS INCORRECTLY MAKE CODE REFERENCES TO AN
 "M" (MERCANTILE) OCCUPANCY.
  
 COORDINATE THE DOUBLE DOOR SWING DIRECTION OF THE
 STORAGE ROOM BETWEEN DRAWINGS. THE LIFE SAFETY DRAWING
 SHOWS A SWING DIRECTION OPPOSITE FROM THE OTHER PLANS.
  
 THE MEPF PLANS ARE NOT SIGNED OR SEALED BY THE
 PROFESSIONAL ENGINEER.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-08-08 Cont ID  
Sent By jwitmer Date 2012-08-08 Time 13:33 Rev Time 0.00
Received By jwitmer Date 2012-07-19 Time 13:52 Sent To  
Notes
2012-07-19 13:54:49TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-26 Cont ID  
Sent By jwitmer Date 2012-06-26 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2012-06-05 Time 08:23 Sent To  
Notes
2012-06-05 08:23:07INCOMING SENT TO C-6 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-07 Cont ID  
Sent By hmoser Date 2012-05-07 Time 14:14 Rev Time 0.00
Received By hmoser Date 2012-04-17 Time 17:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2012-08-08 Cont ID  
Sent By jwitmer Date 2012-08-08 Time 13:32 Rev Time 0.00
Received By jwitmer Date 2012-08-08 Time 13:32 Sent To  
Notes
2012-08-08 13:33:29IMPACT FEES:
 RECEIPT NO: 2012-0808-183
 $11,134.08

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-05-07 Cont ID  
Sent By hmoser Date 2012-05-07 Time 14:12 Rev Time 0.00
Received By hmoser Date 2012-05-07 Time 13:47 Sent To  
Notes
2012-05-07 14:12:39PROVISO
 REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS.
 2010 FLORIDA ENERGY CODE
 ( FOR OUT DOOR AIR )
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2012-05-04 Cont ID  
Sent By lwagner Date 2012-05-04 Time 14:16 Rev Time 0.00
Received By lwagner Date 2012-05-03 Time 13:35 Sent To  
Notes
2012-05-04 14:17:47NEW AREA IS USING PLUMBING FACILITIES WITHIN 500 FEET.
 NO NEW PLUMBING AT THIS TIME.

Review Stop Z ZONING
Rev No 3 Status P Date 2012-08-03 Cont ID  
Sent By jwitmer Date 2012-08-08 Time 13:34 Rev Time 0.00
Received By jroach Date 2012-08-03 Time 13:51 Sent To  
Notes
2012-08-03 13:52:21ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.03.2012
 PERMIT NO.: 12040446
 ADDRESS: 1590 NORTH FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: BERNARD JONES
 TELEPHONE NO.: 561.718.0831
 SCOPE OF REVIEW: RENOVATION FOR NEW PRACTICE RINK/GYM
 FACILITY.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT APPLICATION AND SHALL BE ACCOMPANIED BY A
 CERTIFIED COST ESTIMATE.
  
 2. ALL LANDSCAPE AREAS SHALL BE IRRIGATED. IRRIGATION
 PLANS SHALL BE SUBMITTED UNDER A SEPARATE PERMIT
 APPLICATION AND SHALL CONFORM TO THE REQUIREMENTS OF
 ARTICLE XIV OF THE CITY'S ZLDRS.
  
 3. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 ALL LANDSCAPING SHALL BE INSTALLED AND PASS INSPECTION
 IN ACCORDANCE WITH THE LANDSCAPE PERMIT TO BE ISSUED
 PURSUANT TO COMMENT #1.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 2 Status P Date 2012-06-06 Cont ID  
Sent By jroach Date 2012-06-06 Time 23:38 Rev Time 0.00
Received By jroach Date 2012-06-06 Time 23:38 Sent To  
Notes
2012-06-06 23:42:06ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.06.2012
 PERMIT NO.: 12040446
 ADDRESS: 1590 NORTH FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: BERNARD JONES
 TELEPHONE NO.: 561.718.0831
 SCOPE OF REVIEW: RENOVATION FOR NEW PRACTICE RINK/GYM
 FACILITY.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT APPLICATION AND SHALL BE ACCOMPANIED BY A
 CERTIFIED COST ESTIMATE.
  
 2. ALL LANDSCAPE AREAS SHALL BE IRRIGATED. IRRIGATION
 PLANS SHALL BE SUBMITTED UNDER A SEPARATE PERMIT
 APPLICATION AND SHALL CONFORM TO THE REQUIREMENTS OF
 ARTICLE XIV OF THE CITY'S ZLDRS.
  
 3. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 ALL LANDSCAPING SHALL BE INSTALLED AND PASS INSPECTION
 IN ACCORDANCE WITH THE LANDSCAPE PERMIT TO BE ISSUED
 PURSUANT TO COMMENT #1.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 1 Status F Date 2012-04-25 Cont ID  
Sent By jroach Date 2012-04-25 Time 11:53 Rev Time 0.00
Received By jroach Date 2012-04-25 Time 10:10 Sent To  
Notes
2012-04-25 11:53:34ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.25.2012
 PERMIT NO.: 12040446
 ADDRESS: 1590 NORTH FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: BERNARD JONES
 TELEPHONE NO.: 561.718.0831
 SCOPE OF REVIEW: BUILD-OUT OF EXISTING WAREHOUSE SPACE
 INTO A GYM/PRACTICE RINK FACILITY.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A MINOR
 AMENDMENT TO THE PALM BEACH ICE WORKS DEVELOPMENT OF
 SIGNIFICANT IMPACT (DSI) SHALL BE APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING & ZONING
 DIVISION. ALL COMMENTS REGARDING THE EXTERIOR
 IMPROVEMENTS WILL BE MADE DURING REVIEW OF THE
 AMENDMENT; HOWEVER, SOME PRELIMINARY COMMENTS INCLUDE:
  
 A. PURSUANT TO SECTION 94-444 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), ALL MECHANICAL
 EQUIPMENT SHALL BE SCREENED FROM VIEW. SCREENING SHALL
 CONSIST OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL.
 SHRUBS/HEDGES SHALL ALSO BE PLANTED AT 2 FOOT
 INTERVALS.
  
 B. IT APPEARS THAT THE PROPOSED ACCESSIBLE RAMP ON THE
 WEST SIDE OF THE BUILDING ENCROACHES INTO THE PARKING
 AREA, SPECIFICALLY THAT AREA WHERE CARS MANEUVER TO
 EXIT THE NEARBY PARKING SPACE. ADJUSTMENTS TO THE
 PARKING AREA MAY NEED TO BE MADE TO ACCOMMODATE THE
 RAMP. ADDITIONALLY, WILL A ACCESSIBLE PARKING SPACE BE
 REQUIRED NEAR THE NEW ENTRANCE? PLEASE VERIFY.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved