Plan Review Details - Permit 12040429
Plan Review Stops For Permit 12040429
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-06-22 Cont ID  
Sent By lmartine Date 2012-06-22 Time 16:28 Rev Time 0.00
Received By lmartine Date 2012-06-22 Time 16:28 Sent To  
Notes
2012-06-22 16:30:04SEE PERMIT #12060352 FOR FIRE SPRINKLER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-05-31 Cont ID  
Sent By jwitmer Date 2012-05-31 Time 14:55 Rev Time 0.00
Received By jwitmer Date 2012-05-31 Time 14:45 Sent To  
Notes
2012-05-31 15:05:16BUILDING PLAN REVIEW
 PERMIT: 12040429
 ADD: 7587-7599 S DIXIE HWY
 CONT: CANDAS CONSTRUCTION
 TEL: (954)321-3442
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
 1-4 COMPLIED.
 NEW COMMENT:
  
 5) THE PLANS INDICATE THE BUILDING IS FIRE SPRINKLERED,
 THE BUILDING ORIGINALLY TOOK AREA INCREASES WITH
 SPRINKLERS, FIRE SPRINKLER LAY OUT SHEETS ARE REQUIRED
 AS PART OF THE
 BUILDING PERMIT. ONCE THE BUILDING PERMIT IS ISSUED THE
 FIRE SPRINKLER PERMIT MAY BE APPLIED FOR WITH THE
 HYDROLIC CALCULATIONS ANAD SHOP DRAWING 2010 FBC-B 903.
 SEE FIRE COMMENTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-04 Cont ID  
Sent By jwitmer Date 2012-05-04 Time 15:01 Rev Time 0.00
Received By jwitmer Date 2012-05-04 Time 11:08 Sent To  
Notes
2012-05-04 15:25:12BUILDING PLAN REVIEW
 PERMIT: 12040429
 ADD: 7587-7599 S DIXIE HWY
 CONT: CANDAS CONSTRUCTION
 TEL: (954)321-3442
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET LSP-1 INDICATE TWO AREAS THAT ARE CONSIDERED
 ASSMEBLY OCCUPANCIES THE SALON AREA AND CLASSROOMS 134
 & 135. THE DESIGNER OF RECORD HAS NOT DECLARED IF THE
 INTENT IS SEPERATED OCCUPNCIES OR NON-SEPERATED
 OCCUPANCIES PER 2010 FBC-B:
 508.2.5.1 FIRE-RESISTANCE-RATED SEPERATION.
 508.2.5.2 NONFIRE-RESISTANCE-RATED SEPERATION AND
 PROTECTION.
 DEPENDING ON THE OUTCOME OF THIS SITUATION MORE
 COMMENTS MAY OCCUR WITH OPENING PROTECTION REQUIREMENTS
 TABLE 715.4.
  
 2) LSP-1 ROOM # 133 LABELED A UTILITY ROOM THE USAGE
 WITH A WASHER AND DRYER IS MORE IN LINE WITH LAUNDRY
 PLEASE SEE THE REQUIREMENTS 1 HOUR PROTECTED OR FIRE
 SPRINKLERED, PLANS INDICATE THE BUILDING BEING FIRE
 SPRINKLERED. MAY OR MAYNOT REQUIRE SEPERATION PLEASE
 REVIEW 508.2.5.2 , 508.2.5.3 AND 508.3 NONSEPERATED
 OCCUPANCIES.
  
 3) RESTROOMS AND VICHY ROOM INDICATE THE USE OF TILE
 WALLS BUT THE PLANS LACK THE TYPE OF BACKING TO BE USED
 IN THE INSTALATION. PLEASE REVIEW SECTION :
 2010 FBC-B 2509.2 BASE FOR TILE. CEMENT, FIBER-CEMENT
 OR GLASS MAT GYPSUM BACKERS IN COMPLIANCE WITH ASTM C
 1178, C 1288 OR C 1325 AND INSTALLED IN ACCORDANCE WITH
 MANUFACTURER RECOMMENDATIONS SHALL BE USED AS A BASE
 FOR WALL TILE IN TUB AND SHOWER AREAS AND WALL AND
 CEILING PANELS IN SHOWER AREAS. WATER-RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C 840 AND MANUFACTURER
 RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED
 UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING
 AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C 840.
  
 4) SHEET A-3 PLEASE PROVIDE COMPLIANCE WITH SECTION
 2010 ACCESSIBILITY CODE 803.1-5.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-05-22 Cont ID  
Sent By rlecky Date 2012-05-22 Time 15:59 Rev Time 0.00
Received By rlecky Date 2012-05-22 Time 10:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-05-01 Cont ID  
Sent By rlecky Date 2012-05-01 Time 14:50 Rev Time 0.00
Received By rlecky Date 2012-05-01 Time 10:12 Sent To  
Notes
2012-05-01 14:52:5312040429
 7587 S. DIXIE HWY
 INTERIOR IMPROVEMENTS
  
  
 PROVIDE A LIGHTING DENSITY CALCULATION VERIFYING
 COMPLIANCE WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 505.5.3
 ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST
 BE GFCI PROTECTED. NEC 210.8
 VERIFY COMPLIANCE WITH LIGHTING REQUIREMENTS FOR CLASS
 ROOMS. 2010 FBC 443.3.7
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, VOICE AND DATA.
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-06-22 Cont ID  
Sent By lmartine Date 2012-06-22 Time 16:33 Rev Time 0.00
Received By lmartine Date 2012-06-22 Time 16:32 Sent To  
Notes
2012-06-22 16:33:40SEE PERMIT #12060352 FOR FIRE SPRINKLER

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-05-30 Cont ID  
Sent By wjolin Date 2012-05-30 Time 13:30 Rev Time 0.00
Received By wjolin Date 2012-05-30 Time 13:30 Sent To  
Notes
2012-05-30 13:23:527587 SOUTH DIXIE HIGHWAY
 PERMIT #12040429
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ENGINEERED FIRE SPRINKLER DRAWINGS WERE NOT SUBMITTED.
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-30 Cont ID  
Sent By wjolin Date 2012-04-30 Time 11:47 Rev Time 0.00
Received By wjolin Date 2012-04-30 Time 10:08 Sent To  
Notes
2012-04-30 11:47:157587 SOUTH DIXIE HIGHWAY
 PERMIT #12040429
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 EXISTING EXTERIOR GLASS DOORS NOT INTENDED FOR EXITING
 SHALL BE PERMANENTLY IDENTIFIED WITH SIGNAGE STATING
 "NOT AN EXIT."
  
 INACTIVE DOOR LEAFS SHALL NOT BE EQUIPPED WITH DOOR
 HARDWARE.
  
 WHILE THE OVERALL OCCUPANCY CLASSIFICATION IS
 CONSIDERED TO BE A BUSINESS OCCUPANCY, THE OCCUPANT
 LOAD CAPACITY OF THE CLASSROOMS AND BREAKROOM (ASSEMBLY
 USE) NEED TO BE ESTABLISHED USING AN OCCUPANT LOAD
 FACTOR OF 15 SQ.FT. PER PERSON.
  
 CLASSROOM #134/#135 HAS AN OCCUPANT LOAD EXCEEDING 50
 PERSONS (ASSEMBLY OCCUPANCY) AND WILL NEED TO BE
 SEPARATED FROM THE BUSINESS OCCUPANCY WITH A 1-HOUR
 FIRE BARRIER.
  
 EACH SMOKE OR FIRE-RATED WALL SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 NO EXIT SIGN HAS BEEN PROVIDED FOR THE EXIT NEAR DRYERS
 #107.
  
 PER THE FLORIDA FIRE PREVENTION (CHAPTER 38 - BUSINESS
 OCCUPANCY), A MONITORED FIRE ALARM SYSTEM IS REQUIRED.
  
 ENGINEERED FIRE SPRINKLER DRAWINGS WERE NOT SUBMITTED.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-06-22 Cont ID  
Sent By lmartine Date 2012-06-15 Time 16:28 Rev Time 0.00
Received By lmartine Date 2012-06-13 Time 13:21 Sent To  
Notes
2012-06-14 13:36:01EXPEDITED
 GAVE TO HAROLD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-05 Cont ID  
Sent By hmoser Date 2012-06-05 Time 15:37 Rev Time 0.00
Received By hmoser Date 2012-05-18 Time 09:30 Sent To  
Notes
2012-05-21 09:32:10C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-21 Cont ID  
Sent By rlecky Date 2012-05-10 Time 09:26 Rev Time 0.00
Received By rlecky Date 2012-04-17 Time 16:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-06-15 Cont ID  
Sent By hmoser Date 2012-06-15 Time 15:56 Rev Time 0.00
Received By hmoser Date 2012-06-15 Time 15:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-06-05 Cont ID  
Sent By hmoser Date 2012-06-05 Time 15:37 Rev Time 0.00
Received By hmoser Date 2012-06-05 Time 14:19 Sent To  
Notes
2012-06-05 15:37:28PLANS DENIED
 1) PROVIDE A DETAIL ON THE PLANS SHOWING REQUIRED
 EXHAUST AT THE SOURCE FOR THE NAIL STATIONS. REFER
 TO NOTE H TABLE 403.3 2010 FBC (M)
 2) REFER TO SECTION 510.4 INDEPENDENT SYSTEMS.
 2010 FBC (M)
 3) REFER TO SECTION 510.5.4 CONTAMINANT CAPTURE AND
 DILUTION.
 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-08 Cont ID  
Sent By hmoser Date 2012-05-08 Time 10:41 Rev Time 0.00
Received By hmoser Date 2012-05-07 Time 14:32 Sent To  
Notes
2012-05-08 10:41:47PLANS DENIED
 1) REFER TO SECTION 304.11 GUARDS 2010 FBC (M)
 2) REFER TO TABLE 403.3 BEAUTY ANS NAIL SALONS .
 REFER TO NOTES B & H 2010 FBC (M)
 3) REFER TO SECTION 13-503.2.4.4 SHUTOFF DAMPER
 CONTROLS
 2010 FLORIDA ENERGY CODE
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-04 Cont ID  
Sent By lwagner Date 2012-06-04 Time 14:57 Rev Time 0.00
Received By lwagner Date 2012-06-04 Time 14:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-05-07 Cont ID  
Sent By lwagner Date 2012-05-07 Time 13:07 Rev Time 0.00
Received By lwagner Date 2012-05-07 Time 11:07 Sent To  
Notes
2012-05-07 11:37:32 
 PLUMBING IS OK BASED UPON 177 OCCUPANTS - BUSINESS.
  
 *NOTE*
 PLUMBING 1003.6 LAUNDRIES. LAUNDRY FACILITIES NOT
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT OR
 INTENDED FOR INDIVIDUAL FAMILY USE SHALL BE EQUIPPED
 WITH AN INTERCEPTOR WITH A WIRE BASKET OR SIMILAR
 DEVICE, REMOVABLE FOR CLEANING, THAT PREVENTS PASSAGE
 INTO THE DRAINAGE SYSTEM OF SOLIDS 0.5 INCH (12.7 MM)
 OR LARGER IN SIZE, STRING, RAGS, BUTTONS OR OTHER
 MATERIALS DETRIMENTAL TO THE PUBLIC SEWAGE SYSTEM.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-05-10 Cont ID  
Sent By lfranco Date 2012-05-10 Time 11:50 Rev Time 0.50
Received By lfranco Date 2012-05-10 Time 10:06 Sent To  
Notes
2012-05-10 11:51:47PLANNING: **** ZONING REVIEW NOT REQUIRED: INTERIOR
 WORK ONLY AND THE VALUE OF PROPOSED WORK DOES NOT
 EXCEED 50% OF THE IMPROVEMENT VALUE. ****