Plan Review Details - Permit 12040421
Plan Review Stops For Permit 12040421
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-05-04 Cont ID  
Sent By jwitmer Date 2012-05-04 Time 13:21 Rev Time 0.00
Received By jwitmer Date 2012-05-04 Time 13:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-24 Cont ID  
Sent By jwitmer Date 2012-04-24 Time 10:09 Rev Time 0.00
Received By jwitmer Date 2012-04-23 Time 16:24 Sent To  
Notes
2012-04-24 10:22:56BUILDING PLAN REVIEW
 PERMIT: 12040421- UNIT 910
 12040586- UNIT 912
 ADD:319 CLEMATIS ST
 CONT: RIELLY CONSTRCUCTION
 TEL: (561)262-6876
  
 2010 FLORIDA BUILDING CODE W/
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE: PLANS INDICATE A NEW TENANT SEPERATION WALL, 2
 PERMITS WERE CREATED FOR UNITS ON EACH SIDE OF THE WALL
 FOR HISTORY OF THE UNIT (INDICATION OF WHEN THIS UNIT
 WAS CREATED) AND LOGGING IN OF INSPECTION RESULTS.
  
 1) NEITHER THE LS NOR A-1.0 SHEET PROVIDE WALL
 IDENTIFICATION TAGS IDENTIFYING THE WALL TYPE TO BE
 INSTALLED. SHEET A-3.0 DETAIL-A PARTITION DETAILS DO
 NOT INDENTIFY WHERE THESE WALLS TYPES WILL BE
 INSTALLED? 106.3.5.1.1(4) FIRE SEPERATION WALLS,
 709.6(1) ALSO SEE EXCEEPTION #1?
  
 2) PROVIDE COMPLIANCE WITH: 2010 FBC-B 712.6 FIRE
 WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS
 AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE
 PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH
 IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING
 AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND
 SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL
 OPENINGS."
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-01 Cont ID  
Sent By rlecky Date 2012-05-01 Time 09:42 Rev Time 0.00
Received By rlecky Date 2012-05-01 Time 09:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-05-04 Cont ID  
Sent By ddaniels Date 2012-05-04 Time 15:06 Rev Time 0.00
Received By ddaniels Date 2012-05-04 Time 15:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-25 Cont ID  
Sent By wjolin Date 2012-04-25 Time 11:21 Rev Time 0.00
Received By wjolin Date 2012-04-25 Time 10:56 Sent To  
Notes
2012-04-25 11:21:17319 CLEMATIS STREET - #910
 PERMIT #12040421
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 NO FIRE ALARM NOTIFICATION APPLIANCES SHOWN.
  
 SHEET M-2 DOES NOT INDICATE ANY FIRE DAMPERS WHERE
 DUCTWORK IS PENETRATING FIRE RATED ASSEMBLIES. ALSO
 SHOWS EXISTING DUCTWORK ROUTED THROUGH A FIRE RATED
 STAIR ENCLOSURE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rlecky Date 2012-05-04 Time 11:29 Sent To  
Notes
2012-05-04 11:35:22TO JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-03 Cont ID  
Sent By hmoser Date 2012-05-03 Time 10:23 Rev Time 0.00
Received By hmoser Date 2012-04-16 Time 13:40 Sent To  
Notes
2012-04-18 13:40:36SENT TO B3 FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-05-03 Cont ID  
Sent By hmoser Date 2012-05-03 Time 10:22 Rev Time 0.00
Received By hmoser Date 2012-05-03 Time 10:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-04-27 Cont ID  
Sent By aaponte Date 2012-04-27 Time 16:02 Rev Time 0.00
Received By aaponte Date 2012-04-24 Time 10:24 Sent To  
Notes
***NONE***