Plan Review Details - Permit 12040400
Plan Review Stops For Permit 12040400
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-04-25 Cont ID  
Sent By jwitmer Date 2012-04-23 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2012-04-23 Time 08:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-04-24 Cont ID  
Sent By rlecky Date 2012-04-24 Time 17:29 Rev Time 0.00
Received By rlecky Date 2012-04-24 Time 17:11 Sent To  
Notes
2012-04-24 17:20:35A SEPARATE ELECTRICAL PERMIT AND ELECTRICAL PLAN WITH
 WIND LOAD ENGINEERING FOR THE LIGHT POLE, BASE AND
 FIXTURE IS REQUIRED. PLEASE USE THE 2010 FLORIDA
 BUILDING CODE FOR THE WIND LOAD DESIGN.
  
 ROBERT LECKY, CBO
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2012-05-03 Cont ID  
Sent By mgonzale Date 2012-05-03 Time   Rev Time 1.00
Received By mgonzale Date 2012-05-03 Time   Sent To  
Notes
2012-05-03 11:12:13PLAN IS ACCEPTABLE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-04-25 Cont ID  
Sent By wjolin Date 2012-04-25 Time 10:55 Rev Time 0.00
Received By wjolin Date 2012-04-25 Time 10:43 Sent To ENG
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-04 Cont ID  
Sent By rlecky Date 2012-05-04 Time 09:28 Rev Time 0.00
Received By rlecky Date 2012-04-16 Time 13:56 Sent To  
Notes
2012-04-17 13:56:57SENT TO C9 SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2012-04-20 Cont ID  
Sent By lfranco Date 2012-04-20 Time 16:42 Rev Time 2.25
Received By lfranco Date 2012-04-19 Time 17:45 Sent To  
Notes
2012-04-20 17:26:48PLANNING: ****** PASSED WITH PROVISO, ALL MINOR PD
 AMENDMENT COMMENTS BELOW SHALL BE ADDRESSED AND
 APPROVED, PRIOR TO FINAL PLANNING/ZONING SIGN-OFF OF
 CERTIFICATE OF COMPLETION FOR THIS PERMIT. *****
  
 PLANNING: **** FAILED - RESUBMITTAL 4: 4/12/12****
 RE-SUBMITTAL 3: 4/11/12
 RE-SUBMITTAL 2: 3/30/11
 RE-SUBMITTAL 1: 2/21/12
  
 PB970P - MCDONALD'S @ 45TH STREET & MILITARY
 4275 45TH STREET
 PROJECT NUMBER Z11090017
  
 1. RESPOND TO COMMENTS IN WRITING. RE-SUBMITTAL MAY
 GENERATE ADDITIONAL COMMENTS. ANY NEW RE-SUBMITTALS
 THAT ARE STILL OUTSTANDING AND HAVE NOT ADDRESSED THE
 SAME COMMENTS WILL REQUIRE A RE-SUBMITTAL FEE OF 20% OF
 THE ORIGINAL APPLICATION FEE REVIEW FROM THE PLANNING
 DIVISION.
 A RESUBMITTAL FEE MENTIONED ABOVE, WILL BE ACCESSED
 WHEN A RESUBMITTAL OF THESE COMMENTS IS SUBMITTED.
 PROVIDE REDUCED COPIES ( 8/12 " X 11" AND 11"X17") AND
 ELECTRONIC .PDF OR .JPG OF THE ALL PLANS.
  
 RE-SUBMITTAL 4: A RESPONSE IN WRITING WAS NOT PROVIDED
 ADDRESSING ALL COMMENTS NOTED.
  
 6. PURSUANT TO THE ZLDR, SECTION 94-485(G):
  
 C. PROVIDE DETAIL OF DUMPSTER ENCLOSURE PURSUANT TO THE
 ZLDR, SECTION 94-444 AND FIGURE XIV-3.
  
 RE-SUBMITTAL: THE MINIMUM DEPTH FOR A DUMPSTER
 ENCLOSURE IS 13'-8". PROVIDE A DETAIL ELEVATION OF THE
 ENCLOSURE AND REVISE DIMENSIONS ACCORDINGLY.
  
 RE-SUBMITTAL 4 (4-12-12) REPEAT COMMENT NOT ADDRESSED,
 ONLY SHEET C-100 WAS RESUBMITTED.
  
 COMMENT 6 C : THE SITE PLAN (SHEET C100) SHOWS 14'-1"
 WIDE BY 13'-4" DEEP VS. ARCH SHEET A0 - SHOWS 15'-4"
 WIDE BY 14'-0" DEEP. WHAT IS THE ACTUAL DIMENSION?
 PLEASE REVISE ALL PLANS TO CORRELATE ACCORDINGLY.
  
 11. SUBMIT TWO (2) COPIES OF SIGNED AND SEALED COPIES
 OF THE LANDSCAPE PLANS SHOWING REVISED SITE PLAN
 IMPROVEMENTS AND EXISTING/PROPOSED LANDSCAPING TO MAKE
 SURE THERE ARE NO CONFLICTS WITH LANDSCAPING. ARE THERE
 ANY TREES TO BE RELOCATED/REMOVED? IF SO, SUBMIT FOR A
 TREE ALTERATION PERMIT ALONG WITH THE ASSOCIATED FEE,
 APPLICATION AND PLANS.
  
 RE-SUBMITTAL 4 (4-12-12): REPEAT COMMENT, LANDSCAPE
 PLANS WERE NOT SUBMITTED.
  
  
 14. ELEVATIONS - PROVIDE SIGNAGE BREAKDOWN OF FACADE
 VS. SQUARE FOOTAGE OF EACH SIGN. A MAXIMUM OF THREE (3)
 WALL MOUNTED SIGNS ARE ALLOWED ON THE ENTIRE BUILDING.
  
 RE-SUBMITTAL 4 (4-12-12) REPEAT COMMENT WAS NOT
 ADDRESSED, NO SIGNAGE PACKET WAS SUBMITTED. ONLY SHEET
 C-100 WAS SUBMITTED IN RESUBMITTAL
  
 COMMENT 14 - THE ENCLOSED SIGNAGE PLAN AND ELEVATIONS
 DO NOT MATCH WHAT IS CURRENTLY IN THE BUILDING
 PERMITTING DIVISION'S BUILDING PERMIT. THE LATEST SIGN
 PLANS SHOW THREE (3) "M" FOR WALL SIGNAGE. THERE ARE NO
 SIGNS THAT SHOW "MCDONALD'S". REVISE PLANS ACCORDINGLY.
 ADDITIONALLY, PROVIDE SIGNAGE COMPANY WITH LATEST
 BUILDING/SITE PLAN FOOT PRINT SHOWN ON SHEET C100,
 WHERE DUMPSTER LOCATION AND DRIVE-THRU AREA HAS BEEN
 REVISED, SO THAT ALL PLANS CORRELATE.
  
 RE-SUBMITTAL 1: PROVIDE ELEVATIONS OF BUILDING WITH
 COMPLETE SIGNAGE PACKAGE PROPOSED AS PART OF THE
 APPLICATION. OTHERWISE, A SEPARATE MINOR PD AMENDMENT
 WILL BE REQUIRED FOR ALL SIGNAGE ON SITE, WALL SIGNAGE,
 MENU BOARDS, ETC. THERE IS AN EXISTING SIGNAGE PERMIT
 FOR THIS PROPERTY, THE PERMIT WILL NOT BE APPROVED,
 UNTIL THIS INFORMATION IS SUBMITTED THROUGH THIS
 PLANNING BOARD 970P MINOR AMENDMENT OR A SEPARATE
 AMENDMENT IS SUBMITTED. PLEASE ADVISE SO THAT WE CAN
 PROCESS THE SIGNAGE PERMIT ACCORDINGLY. PURSUANT TO THE
 ZLDR, SECTION 94-408(D):
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  