Plan Review Details - Permit 12040363
Plan Review Stops For Permit 12040363
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-05-31 Cont ID  
Sent By rmcdouga Date 2012-05-31 Time 15:30 Rev Time 0.00
Received By rmcdouga Date 2012-05-31 Time 15:30 Sent To  
Notes
2012-05-31 15:31:42THE PLAN REVIEW COMMENTS FROM THE FIRST REVIEW WERE NOT
 ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-15 Cont ID  
Sent By rmcdouga Date 2012-05-15 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2012-05-14 Time 13:44 Sent To  
Notes
2012-05-14 14:53:552010 FBC
  
 DENIED BY BUILDING
  
 1) THE 2010 FLORIDA BUILDING CODE BECAME EFFECTIVE ON
 MARCH 15, 2012 AND THE PERMIT WAS APPLIED FOR ON APRIL
 13, 2012. THEREFORE, THE PLANS ARE REQUIRED TO BE
 DESIGNED TO COMPLY WITH THE 2010 FBC. PLEASE REVISE THE
 PLANS TO REFERENCE THE 2010 FBC. FS
  
 2) UNDER THE 2010 FBC, THE WIND SPEED IS 170 MPH.
 PLEASE REVISE. FBC R301.2.1
  
 3) THE LOCATION OF THE ADDITION THAT WAS DRAWN ON THE
 SURVEY DOES NOT MATCH THE LOCATION SHOWN ON THE PLANS.
 PLEASE PROVIDE TWO COPIES OF AN ACCURATE SITE PLAN
 INDICATING THE DISTANCES FROM THE NEW ADDITION TO THE
 PROPERTY LINES. FBC 302.1
  
 4) SUBMIT TWO COPIES OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3.
  
 5) SHOW COMPLIANCE WITH FBC R318.1 FOR TERMITE
 PROTECTION.
  
 6) PROVIDE TWO SETS OF FLOOR PLANS SHOWING ALL ROOM
 DIMENSIONS, WINDOW AND DOOR SIZES, ETC. DRAWN TO SCALE
 (MINIMUM 1/8" SCALE) WITH THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. CITY AMENDMENTS
 107.2.1 AND 107.2.1.4
  
 7) SUBMIT ENERGY CALCULATIONS SHOWING COMPLIANCE WITH
 FBC ENERGY CONSERVATION SECTION 401.2.
  
 8) SPECIFY THE CEILING INSULATION ON THE PLANS. FBC
 ENERGY CONSERVATION SECTION 401
  
 9) SHEET S-2 SPECIFIES A 12" DEEP MONOLITHIC
 FOUNDATION. FBC R403.1.4 REQUIRES FOOTINGS TO BE A
 MINIMUM OF 12" BELOW GRADE AND R404.1.6 REQUIRES
 CONCRETE FOUNDATIONS TO EXTEND 6" ABOVE FINISHED GRADE.
 THEREFORE, AN 18" THICKENED EDGE IS REQUIRED.
  
 10) SHOW COMPLIANCE WITH ASTM C 1063 WHICH REQUIRES A
 FOUNDATION WEEP SCREED FOR EXTERIOR STUCCO WALLS AT THE
 BOTTOM OF ALL FRAMED EXTERIOR WALLS, BELOW THE FLOOR
 LINE.
  
 11) PROVIDE FINISHED EXTERIOR ELEVATIONS ON THE PLANS
 SHOWING DIMENSIONS AND DRAWN TO SCALE. CITY AMENDMENTS
 107.2..1 AND 107.2.1.4
  
 12) CLARIFY HOW THE EXTERIOR WALL WILL BE FINISHED TO
 PREVENT WATER INTRUSION WHERE THE PATIO RAFTERS
 PENETRATE INTO THE NORTH WALL. FBC R703.1
  
 13) SPECIFY THE ROOF PITCH ON THE PLANS. FBC R905.2.2
  
 14) SPECIFY THE SOFFIT COVERING MATERIAL ON THE PLANS.
 FBC R703.1.2
  
 15) SPECIFY THE INTERIOR CEILING FINISH MATERIAL ON THE
 PLANS. FBC R805
  
 16) SPECIFY THE LOCATION AND SIZE OF THE ATTIC ACCESS
 FOR THE NEW A/C AIR HANDLER THAT IS LOCATED IN THE
 ATTIC. FBC R807.1
  
 17) CLARIFY THE NOTE ON SHEET S-3 THAT STATES 1 X 6
 COLLAR TIES WHERE FEASIBLE.
  
 18) SHOW COMPLIANCE WITH FBC R806 FOR ROOF VENTILATION.
  
 19) SHOW COMPLIANCE WITH FBC R803.2.3.1 FOR ROOF
 SHEATHING FASTENING REQUIREMENTS.
  
 20) THE PLANS APPEAR TO INDICATE THAT THE ADDITION HAS
 A CATHEDRAL CEILING. PLEASE SHOW HOW THE LATERAL WIND
 LOADS WILL BE ADDRESSED WITHOUT A CEILING DIAPHRAGM.
 PROVIDE CALCULATIONS. CITY AMENDMENTS 107.107.2.1.3
  
 21) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS, WINDOWS AND ROOFING COVERING MATERIAL
 AS REQUIRED BY DCA RULE 9N-3.
  
 22) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PER
 CITY AMENDMENTS 107.3.4.1.
  
 24) SHOW COMPLIANCE WITH FBC R301.2.1.2 FOR PROTECTION
 OF OPENINGS FROM WINDBORNE DEBRIS.
  
 25) NOTE: IN ORDER TO SPEED PLAN REVIEW TIME, PLEASE
 SUBMIT A RESPONSE LETTER INDICATING HOW EACH OF THE
 REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-01 Cont ID  
Sent By jleahy Date 2012-05-01 Time 08:22 Rev Time 0.00
Received By jleahy Date 2012-05-01 Time 07:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-31 Cont ID  
Sent By rmcdouga Date 2012-05-31 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2012-05-29 Time 09:31 Sent To  
Notes
2012-05-29 09:32:57TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-15 Cont ID  
Sent By rmcdouga Date 2012-05-15 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2012-04-13 Time 10:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-05-14 Cont ID  
Sent By rmcdouga Date 2012-05-14 Time 14:05 Rev Time 0.00
Received By rmcdouga Date 2012-05-14 Time 14:05 Sent To  
Notes
2012-05-14 14:17:56AN IMPACT FEE REVIEW BY PALM BEACH COUNTY WILL BE
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-05-31 Cont ID  
Sent By rmcdouga Date 2012-05-31 Time 15:33 Rev Time 0.00
Received By rmcdouga Date 2012-05-31 Time 15:33 Sent To  
Notes
2012-05-31 15:34:10THE PLAN REVIEW COMMENTS FROM THE FIRST REVIEW WERE NOT
 ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-14 Cont ID  
Sent By rmcdouga Date 2012-05-14 Time 14:19 Rev Time 0.00
Received By rmcdouga Date 2012-05-14 Time 14:19 Sent To  
Notes
2012-05-14 14:31:122010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF MECHANICAL PLANS WITH THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 SPECIFY THE SIZE AND LOCATION OF SUPPLY AND RETURN
 DUCTS. SPECIFY THE GRILL SIZES AND THE CFMS AT EACH
 DROP. CITY AMENDMENTS 107.3.5.3
  
 2) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE NEW
 ADDITION AS REQUIRED BY 2010 FBC ENERGY CONSERVATION
 SECTION 401.2.
  
 3) IF NEW EQUIPMENT IS BEING INSTALLED, SUBMIT TWO
 COPIES OF THE EQUIPMENT SIZING CALCULATIONS AND PROVIDE
 AN EQUIPMENT SCHEDULE ON THE PLANS. FBC 1401.3
  
 4) PLANS SHOWN NEW A/C EQUIPMENT LOCATED IN THE ATTIC.
 SPECIFY THE SIZE AND LOCATION OF ATTIC ACCESS AND SHOW
 COMPLIANCE WITH FBCR M1305.1.3.
  
 5) SHOW THE LOCATION OF THE NEW A/C CONDENSING UNIT ON
 THE PLANS.
  
 6) SHOW COMPLIANCE WITH FBC M 1507.1 FOR MECHANICAL
 BATHROOM VENTILATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-05-31 Cont ID  
Sent By rmcdouga Date 2012-05-31 Time 15:32 Rev Time 0.00
Received By rmcdouga Date 2012-05-31 Time 15:32 Sent To  
Notes
2012-05-31 15:33:12THE PLAN REVIEW COMMENTS FROM THE FIRST REVIEW WERE NOT
 ADDRESSED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-05-14 Cont ID  
Sent By rmcdouga Date 2012-05-14 Time 14:08 Rev Time 0.00
Received By rmcdouga Date 2012-05-14 Time 14:08 Sent To  
Notes
2012-05-14 14:16:542010 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO SETS OF AN ISOMETRIC SANITARY RISER
 DIAGRAM FOR THE NEW BATHROOM WITH THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 107.2.1 AND 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2012-05-30 Cont ID  
Sent By eschneid Date 2012-05-30 Time 09:52 Rev Time 0.50
Received By eschneid Date 2012-05-29 Time 17:55 Sent To B
Notes
2012-05-30 09:50:52FAILED
  
 1) REPEAT COMMENT: PROVIDE ACCURATE INFORMATION, TO
 INCLUDE ACCURATE SETBACK DIMENSIONS, AS TO THE LOCATION
 AND SIZE OF THE ADDITION ON A SITE PLAN OR A MARKED UP
 SURVEY.
  
 2) REPEAT COMMENT: THE PROPOSED ROOF AND SUPPORT POSTS
 OVER THE PATIO ON THE NORTH SIDE OF THE HOUSE APPEAR TO
 ENCROACH INTO THE REQUIRED 10 FOOT REAR SETBACK.
 ACCURATE DIMENSIONS FOR THE PATIO ROOF SHALL BE
 PROVIDED TO THE PROPERTY LINE TO CLEARLY SHOW NO
 ENCROACHMENT.
  
 3) REPEAT COMMENT: SHOW THE LOCATION, WITH SETBACK
 DIMENSIONS, OF NEW OR RELOCATED A/C EQUIPMENT ON THE
 SITE PLAN. THE RESUBMITTED PLANS SEEM TO INDICATE THAT
 THE A/C WILL BE LOCATED WITHIN THE CURRENT HOUSE, ON
 THE EAST SIDE OF THE ADDITION.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED BASED ON THE
 PROVISION OF ACCURATE INFORMATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2012-05-29 17:56:02GIVEN TO ES

Review Stop Z ZONING
Rev No 1 Status F Date 2012-04-19 Cont ID  
Sent By eschneid Date 2012-04-19 Time 16:12 Rev Time 0.50
Received By eschneid Date 2012-04-19 Time 11:15 Sent To  
Notes
2012-04-19 16:23:25FAILED
  
 1) PROVIDE 2 COPIES OF A RECENT SURVEY, LESS THAN ONE
 YEAR OLD, SHOWING ALL THE FEATURES ON THE PROPERTY.
  
 2) THE STRUCTURAL/FLOOR PLANS SHOW ONE ADDITION ON THE
 WEST SIDE OF THE EXISTING HOUSE, WHILE THE MARKED UP
 OLD SURVEY SHOWS TWO ADDITIONS ON THE EAST SIDE OF THE
 EXISTING HOUSE. PROVIDE ACCURATE INFORMATION, TO
 INCLUDE ACCURATE SETBACK DIMENSIONS, AS TO THE LOCATION
 AND SIZE OF THE ADDITION ON THE SITE PLAN.
  
 3) THE PROPOSED ROOF AND SUPPORT POSTS OVER THE PATIO
 ON THE NORTH SIDE OF THE HOUSE ENCROACH INTO THE
 REQUIRED 10 FOOT REAR SETBACK. THE PLANS SHALL CLEARLY
 SHOW NO ENCROACHMENT.
  
 4) SHOW THE LOCATION, WITH SETBACK DIMENSIONS, OF NEW
 OR RELOCATED A/C EQUIPMENT ON THE SITE PLAN.
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED BASED ON THE
 PROVISION OF ACCURATE INFORMATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.