Plan Review Details - Permit 12040280
Plan Review Stops For Permit 12040280
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2013-01-04 Cont ID  
Sent By jgomez Date 2013-01-04 Time 10:01 Rev Time 0.00
Received By jgomez Date 2013-01-04 Time 09:59 Sent To  
Notes
2013-01-04 10:16:46RESIDENTIAL (R3) ADDITION FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- SOIL IN THIS AREA IS QUESTIONABLE. PROVIDE SOIL TEST
 REPORT AS REQUIRED BY SEC. R401.4 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. OWNER SAID HE WILL
 HAVE THE TEST DONE ON JANUARY).
  
 2- ENGINEER REMOVED NOTE REGARDING THE SOIL BEARING
 CAPACITY USED FOR THE DESIGN. ENGINEER TO SPECIFY SOIL
 BEARING CAPACITY FOR WHICH STRUCTURE WAS DESIGNED FOR.
 ENGINEER TO READ SOIL TEST REPORT TO VERIFY IF PROPOSED
 FOOTING DESIGN IS ADEQUATE BASED ON THE TYPE AND
 BEARING CAPACITY OF THE SOIL. SEC. R301.1 OF 2010 FBC.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 3- REVISE INFORMATION SUBMITTED FOR ACCORDION SHUTTERS
 INSTALLATION. ON SHEET 7 OF 7 OWNER SPECIFIED USING
 1/4" TAPCONS AT 6"O.C. WITH CONNECTION TYPE C1. CLEARLY
 SPECIFY SHUTTERS MOUNTING TYPE. WALL TRACK MOUNTING ON
 SHEET 4 OF 7 SPECIFIES CONNECTION TYPE C3. AND, THIS
 CONNECTION TYPE IS NOT ALLOWED. SPECIFY WHICH MOUNTING
 CONDITION USING CONNECTION TYPE C1 IS GOING TO BE USED.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 4- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-11-13 Cont ID  
Sent By jgomez Date 2012-11-13 Time 14:31 Rev Time 0.00
Received By jgomez Date 2012-11-13 Time 14:31 Sent To  
Notes
2012-11-13 14:33:58RESIDENTIAL (R3) ADDITION THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- SOIL IN THIS AREA IS QUESTIONABLE. PROVIDE SOIL TEST
 REPORT AS REQUIRED BY SEC. R401.4 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 2- ENGINEER REMOVED NOTE REGARDING THE SOIL BEARING
 CAPACITY USED FOR THE DESIGN. ENGINEER TO SPECIFY SOIL
 BEARING CAPACITY FOR WHICH STRUCTURE WAS DESIGNED.
 ENGINEER TO READ SOIL TEST REPORT TO VERIFY IF PROPOSED
 FOOTING DESIGN IS ADEQUATE BASED ON THE TYPE AND
 BEARING CAPACITY OF THE SOIL. SEC. R301.1 OF 2010 FBC.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ACCORDION SHUTTERS. NOA 07-0828.12 SUBMITTED EXPIRED
 ON 10/29/12. NEED CURRENT NOA.
  
 B) THERE ARE DIFFERENT PRODUCT APPROVALS SUBMITTED FOR
 THE EXTERIOR DOORS. CLARIFY WHICH ONE IS GOING TO BE
 USED. CHECK THE DESIGN PRESSURES WITH DESIGN PRESSURES
 SPECIFIED BY THE ENGINEER.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 5- PROVIDE COMPLETE INSTALLATION FOR THE INSTALLATION
 OF ACCORDION SHUTTERS SUBMITTED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 6- PROVIDE DETAILS/SPECIFICATIONS FOR DOOR STRUCTURAL
 BUCK SIZE AS REQUIRED BY THE DOOR PRODUCT APPROVAL
 SUBMITTED. SPECIFY ALL FASTENERS (SIZE AND SPACING).
 STRUCTURAL BUCK TO COMPLY WITH SEC. R612.10.2.1 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. BUCK SIZE SPECIFIED
 DON'T COMPLY WITH PRODUCT APPROVAL SUBMITTED. AND,
 FASTENER SPACING WAS NOT SPECIFIED.
  
 7- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
 (REPEAT COMMENT).
  
  
 ****NOTE: ONE SET OF PLANS WAS TAKEN OUT AND WAS NOT
 RETURNED. MISSING THE A/C, ELECTRICAL AND PLUMBING
 PLANS. WE HAVE ONLY ONE COPY. NEED TO COPIES.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-08-08 Cont ID  
Sent By jgomez Date 2012-08-07 Time 14:52 Rev Time 0.00
Received By jgomez Date 2012-08-07 Time 14:28 Sent To  
Notes
2012-08-07 15:21:25RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- SOIL IN THIS AREA IS QUESTIONABLE. PROVIDE SOIL TEST
 REPORT AS REQUIRED BY SEC. R401.4 OF 2010
 FBC-RESIDENTIAL.
 NOTE: ENGINEER REMOVED NOTE REGARDING THE SOIL BEARING
 CAPACITY USED FOR THE DESIGN. ENGINEER TO SPECIFY SOIL
 BEARING CAPACITY FOR WHICH STRUCTURE WAS DESIGNED.
 ENGINEER TO READ SOIL TEST REPORT TO VERIFY IF PROPOSED
 FOOTING DESIGN IS ADEQUATE BASED ON THE TYPE AND
 BEARING CAPACITY OF THE SOIL.
  
 2- REVISE THE ENERGY CALCULATIONS TO MATCH PLANS.
 A) PLANS SHOW VENTED ATTIC.
 B) ROOF MATERIAL IS SHINGLES NOT CONCRETE TILE.
 C) CEILING TYPE IS NOT CATHEDRAL/SINGLE ASSEMBLY. SEE
 PLANS AND REVISE.
 D) KITCHEN IS NOT INCLUDED IN THE ADDITION. SEE PLANS.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS. NOA 06-0407.02 SUBMITTED
 EXPIRED ON AUGUST 10, 2011. PROVIDE TWO NEW COPIES.
  
 B) SHUTTERS IF NOT USING IMPACT WINDOWS. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE. PROVIDE 2 COPIES.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS. VALUATION WAS UPDATED,
 OWES $1432.91.
  
 6- PROVIDE DETAILS/SPECIFICATIONS FOR DOOR STRUCTURAL
 BUCK SIZE AS REQUIRED BY THE DOOR PRODUCT APPROVAL
 SUBMITTED. SPECIFY ALL FASTENERS. STRUCTURAL BUCK TO
 COMPLY WITH SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL.
  
 7- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-15 Cont ID  
Sent By jgomez Date 2012-05-15 Time 08:49 Rev Time 0.00
Received By jgomez Date 2012-05-14 Time 11:57 Sent To  
Notes
2012-05-15 10:06:58RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
  
 1- AFTER PLANS ARE REVISED, PLEASE BRING THEM TO PALM
 BEACH COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES
 ARE DUE. THEN, BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE.
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 401 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- ENGINEER NEEDS TO UPDATE ALL THE PLANS. CURRENT CODE
 IN EFFECT IS THE 2010 FLORIDA RESIDENTIAL CODE AND THE
 2010 FBC. REVISE ALL THE DESIGN INFORMATION
 ACCORDINGLY. UPDATE IN ALL PLANS ALL THE INFORMATION
 THAT REFERENCES THE 2007 FBC AND THE ASCE 7-05 AND
 REFERENCE CORRECT CURRENT SECTION.
  
 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS SPECIFIED ON PLANS. NOA
 09-0316.10 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE.
 PLEASE VISIT THE MIAMI-DADE WEBSITE AND DOWNLOAD
 CURRENT NOA.
  
 B) ROOF SHINGLES. PROVIDE 2 COPIES. ONLY ONE WAS
 SUBMITTED.
  
 C) EXTERIOR DOOR. PROVIDE 2 COPIES. ONLY ONE WAS
 SUBMITTED.
  
 D) HURRICANE SHUTTERS FOR SINGLE HUNG WINDOWS SINCE
 WINDOWS HAVE NO IMPACT GLASS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE SHOWING SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED.
  
 E) ALL USP STRUCTURAL CONNECTORS SPECIFIED BY THE
 ENGINEER ON PLANS AND DETAILS. PROVIDE ONLY THE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE STRUCTURAL
 CONNECTOR ONLY. THIS APPLIES TO STRUCTURAL CONNECTORS
 ONLY.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 6- ENGINEER SPECIFIED ON WALL SECTION ON SHEET A-1 AND
 ON SHEET A-3 THAT THE SOIL WAS OBSERVED TO BE SAND AND
 ROCK. THIS IS NOT THE TYPE OF SOIL ON THIS AREA.
 PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4 AND
 ENGINEER TO REVISE SPECS AS REQUIRED BASED ON THE SOIL
 TEST REPORT FINDINGS.
  
 7- WALL SECTIONS SPECIFY ROOF PITCH OF 3/12. ENGINEER
 NEEDS TO SPECIFY 2 LAYERS OF UNDERLAYMENT AS REQUIRED
 BY SEC. R905.2.2.
  
 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 DESIGN PROFESSIONAL FEES. SEC. 109.3 OF CITY AMENDMENTS
 TO FBC. VALUATION WAS UPDATED. OWES $1432.91.
  
 9- WALL SECTION ON SHEET A-3 SHOWS THAT EXISTING
 TRUSSES ARE TO BE CUT TO RECEIVE NEW WALL. ENGINEER TO
 PROVIDE SPECIFICATIONS SHOWING HOW THE EXISTING TRUSSES
 ARE TO BE REINFORCED SO THE STRUCTURAL STABILITY IS NOT
 AFFECTED. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC.
  
 10- PROVIDE DETAILS/SPECIFICATIONS FOR DOORS AND
 WINDOWS BUCKS AS REQUIRED BY SEC. R612.10.2.1.
  
 11-WALL SECTION ON SHEET A-1:
 A) FOOTING NEEDS TO BE MIN. 12" BELOW GRADE. SEC.
 R403.1.4. REVISE AS REQUIRED.
  
 B) SPECIFY ROOF EDGE WIDTH. 4'-0" WIDE MIN. AS REQUIRED
 BY FIGURE R301.2(7).
  
 12- DOOR SCHEDULE ON SHEET A-1 IS MISSING DOOR #3 FOR
 NEW BEDROOM. REVISE AS REQUIRED.
  
 13- SHEET A-2:
 A) FOUNDATION PLAN IS MISSING THE SPECIFICATION FOR THE
 WATER VAPOR BARRIER AS REQUIRED BY SEC. R506.2.3.
  
 B) ROOFING LOADS. SPECIFY ALL THE LIVE, DEAD AND WIND
 LOADS AS REQUIRED BY SEC. R301.1, TABLE R301.2(2) AND
 TABLE R301.5. AND CLEARLY IDENTIFY ALL ROOF ZONES AND
 WALL ZONES.
  
 C) UPDATE THE WIND CODE EDITION AND THE SECTIONS
 REFERENCED ON ON THE FOOTING AND TIE BEAM DETAIL.
 CURRENT CODE IW THE 2010 FLORIDA RESIDENTIAL CODE AND
 2010 FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-04-30 Cont ID  
Sent By rlecky Date 2012-04-30 Time 15:53 Rev Time 0.00
Received By rlecky Date 2012-04-30 Time 15:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2013-02-14 Cont ID  
Sent By jgomez Date 2013-02-14 Time 14:00 Rev Time 0.00
Received By jgomez Date 2013-02-14 Time 14:00 Sent To  
Notes
2013-02-14 14:04:50TALKED TO MR. HARRIS. HE SAID HE CAN'T GET THE
 GEOTECHNICAL ENGINEER TO DO THE SOIL TEST REPORT. HE
 SAID THEY DIDN'T SHOW UP. I TOLD HIM THIS AREA IS KNOWN
 TO HAVE MUCK AND THE SOIL TEST REPORT IS REQUIRED TO
 PROPERLY DESIGN THE FOUNDATION AND PROPERLY PREPARE THE
 SOIL TO RESIST THE NEW BUILDING LOADS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-01-04 Cont ID  
Sent By jgomez Date 2013-01-04 Time 14:09 Rev Time 0.00
Received By jgomez Date 2012-12-27 Time 09:47 Sent To  
Notes
2013-01-04 09:49:56MET WITH MR. HARRIS. PRODUCT APPROVALS AND REVISED
 DRAWINGS SUBMITTED. HE SAID SOIL TEST REPORT WILL BE
 DONE IN JANUARY. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-11-13 Cont ID  
Sent By jgomez Date 2012-11-13 Time 16:53 Rev Time 0.00
Received By jgomez Date 2012-11-06 Time 09:10 Sent To  
Notes
2012-11-07 09:11:16SENT TO ZONING SHELF FOR JOHN'S REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-08 Cont ID  
Sent By jgomez Date 2012-08-08 Time 13:18 Rev Time 0.00
Received By jgomez Date 2012-07-03 Time 16:14 Sent To  
Notes
2012-07-03 16:15:50R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-15 Cont ID  
Sent By jgomez Date 2012-05-15 Time 14:31 Rev Time 0.00
Received By jgomez Date 2012-04-11 Time 15:03 Sent To  
Notes
2012-04-11 15:04:01R--7

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2013-01-04 Cont ID  
Sent By jgomez Date 2013-01-04 Time 10:00 Rev Time 0.00
Received By jgomez Date 2013-01-04 Time 09:59 Sent To  
Notes
2013-01-04 10:00:31NEED PALM BEACH COUNTY IMPACT FEES STAMP ON PLANS AND
 COPY OF PAID RECEIPT IF FEES ARE DUE AS REQUIRED BY THE
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2012-11-13 Cont ID  
Sent By jgomez Date 2012-11-13 Time 16:50 Rev Time 0.00
Received By jgomez Date 2012-11-13 Time 16:50 Sent To  
Notes
2012-11-13 16:50:47NEED PALM BEACH COUNTY IMPACT FEES STAMP ON PLANS AND
 COPY OF PAID RECEIPT IF FEES ARE DUE AS REQUIRED BY THE
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-08-07 Cont ID  
Sent By jgomez Date 2012-08-07 Time 14:48 Rev Time 0.00
Received By jgomez Date 2012-08-07 Time 14:48 Sent To  
Notes
2012-08-07 14:50:25NEED PALM BEACH COUNTY IMPACT FEES STAMP ON PLANS AND
 COPY OF PAID RECEIPT IF FEES ARE DUE AS REQUIRED BY THE
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-05-15 Cont ID  
Sent By jgomez Date 2012-05-15 Time 08:46 Rev Time 0.00
Received By jgomez Date 2012-05-15 Time 08:46 Sent To  
Notes
2012-05-15 08:48:37AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY TO CHECK IF IMPACT FEES ARE DUE. BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-08-07 Cont ID  
Sent By hmoser Date 2012-08-07 Time 13:49 Rev Time 0.00
Received By hmoser Date 2012-08-07 Time 13:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-15 Cont ID  
Sent By jgomez Date 2012-05-15 Time 14:14 Rev Time 0.00
Received By jgomez Date 2012-05-15 Time 14:14 Sent To  
Notes
2012-05-15 14:22:10RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE & 2010 FBC.
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS (2 COPIES) AS
 REQUIRED BY SEC. 403.6 OF 2010 FBC- ENERGY
 CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-11-14 Cont ID  
Sent By jgomez Date 2012-11-13 Time 16:53 Rev Time 0.00
Received By jgomez Date 2012-11-13 Time 16:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-08-08 Cont ID  
Sent By jgomez Date 2012-08-08 Time 13:14 Rev Time 0.00
Received By jgomez Date 2012-08-08 Time 13:10 Sent To  
Notes
2012-08-08 13:15:59RESIDENTIAL (R3) ADDITION SECOND PLUMBING REVIEW
 COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE.
  
 1- PROVIDE PLUMBING RISER DIAGRAM AS REQUIRED BY SEC.
 107.3.5.3(11) OF CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-05-15 Cont ID  
Sent By jgomez Date 2012-05-15 Time 14:26 Rev Time 0.00
Received By jgomez Date 2012-05-15 Time 14:22 Sent To  
Notes
2012-05-15 14:31:36RESIDENTIAL (R3) ADDITION PLUMBING REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE.
  
 1- PROVIDE PLUMBING RISER DIAGRAM AS REQUIRED BY SEC.
 107.3.5.3(11) OF CITY AMENDMENTS TO FBC.
  
 2- SPECIFY LOCATION OF WATER HEATER TO VERIFY
 COMPLIANCE WITH SEC. M2005.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 4 Status P Date 2013-01-03 Cont ID  
Sent By jroach Date 2013-01-03 Time 09:42 Rev Time 0.00
Received By jroach Date 2013-01-03 Time 09:42 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2012-11-07 Cont ID  
Sent By jroach Date 2012-11-07 Time 16:23 Rev Time 0.00
Received By jroach Date 2012-11-07 Time   Sent To B
Notes
2012-11-07 16:25:02ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 11.07.2012
 PERMIT NO.: 12040280
 ADDRESS: 1371 9TH COURT
 CONTRACTOR/CONTACT: LAWRENCE HARRIS
 TELEPHONE NO.: 561.213.2668
 SCOPE OF REVIEW: ADDITION OF 2 BEDROOMS AND 1 BATH TO
 EXISTING RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. REPEAT COMMENT: PLEASE NOTE THE HEIGHT OF THE
 PROPOSED ADDITION. BUILDING HEIGHT SHALL BE MEASURED
 FROM GRADE TO THE MEAN POINT OF THE PITCHED ROOF.
  
 2. IT APPEARS THAT THE VALUE OF WORK WAS INCREASED FROM
 $20,000 TO $51,520. PURSUANT TO SECTION 94-441 OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS),
 ANY WORK PROPOSED TO EXCEED 50% OF THE VALUE OF THE
 STRUCTURE SHALL REQUIRE THAT THE PROPERTY BE BROUGHT
 INTO COMPLIANCE WITH ARTICLE XIV (LANDSCAPING) OF THE
 ZLDRS. PLEASE PROVIDE A LANDSCAPE INDICATING COMPLIANCE
 WITH THE FOLLOWING:
  
 A. 1 SHADE/FLOWERING/FRUIT TREE SHALL BE PLANTED FOR
 EACH 1,200 SQUARE FEET OF OPEN SPACE.
  
 B. 1 SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF
 OPEN SPACE.
  
 IF THE EXISTING LANDSCAPING CONFORMS TO THESE
 PROVISIONS, THEN ONLY A PLAN SHOWING THE EXISTING
 PLANTING, ALONG WITH A DATA TABLE INDICATING COMPLIANCE
 WITH ARTICLE XIV SHALL BE PROVIDED. PLEASE NOTE THAT
 THE DATA TABLE SHOULD NOTE THE SIZE AND SPECIES OF THE
 EXISTING TREES/SHRUBS. IF ADDITIONAL MATERIAL NEEDS TO
 BE INSTALLED IN ORDER TO COMPLY WITH THE PROVISIONS OF
 ARTICLE XIV, THEN A SEPARATE LANDSCAPE PERMIT
 APPLICATION SHALL BE SUBMITTED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  
2012-11-07 11:45:21GAVE TO J.R. - MD

Review Stop Z ZONING
Rev No 2 Status F Date 2012-07-12 Cont ID  
Sent By jroach Date 2012-07-12 Time 14:34 Rev Time 0.00
Received By jroach Date 2012-07-12 Time 14:34 Sent To  
Notes
2012-07-12 14:45:10ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.12.2012
 PERMIT NO.: 12040280
 ADDRESS: 1371 9TH COURT
 CONTRACTOR/CONTACT: LAWRENCE HARRIS
 TELEPHONE NO.: 561.213.2668
 SCOPE OF REVIEW: ADDITION OF 2 BEDROOMS AND 1 BATH TO
 EXISTING RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. REPEAT COMMENT: TWO (2) COPIES OF A CURRENT AND
 ACCURATE SURVEY SHALL BE PROVIDED.
  
 2. REPEAT COMMENT: PLEASE NOTE THE HEIGHT OF THE
 PROPOSED ADDITION. BUILDING HEIGHT SHALL BE MEASURED
 FROM GRADE TO THE MEAN POINT OF THE PITCHED ROOF.
  
 3. IT APPEARS THAT THE VALUE OF WORK WAS INCREASED FROM
 $20,000 TO $51,520. PURSUANT TO SECTION 94-441 OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS),
 ANY WORK PROPOSED TO EXCEED 50% OF THE VALUE OF THE
 STRUCTURE SHALL REQUIRE THAT THE PROPERTY BE BROUGHT
 INTO COMPLIANCE WITH ARTICLE XIV (LANDSCAPING) OF THE
 ZLDRS. PLEASE PROVIDE A LANDSCAPE INDICATING COMPLIANCE
 WITH THE FOLLOWING:
  
 A. 1 SHADE/FLOWERING/FRUIT TREE SHALL BE PLANTED FOR
 EACH 1,200 SQUARE FEET OF OPEN SPACE.
  
 B. 1 SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF
 OPEN SPACE.
  
 IF THE EXISTING LANDSCAPING CONFORMS TO THESE
 PROVISIONS, THEN ONLY A PLAN SHOWING THE EXISTING
 PLANTING, ALONG WITH A DATA TABLE INDICATING COMPLIANCE
 WITH ARTICLE XIV SHALL BE PROVIDED. PLEASE NOTE THAT
 THE DATA TABLE SHOULD NOTE THE SIZE AND SPECIES OF THE
 EXISTING TREES/SHRUBS. IF ADDITIONAL MATERIAL NEEDS TO
 BE INSTALLED IN ORDER TO COMPLY WITH THE PROVISIONS OF
 ARTICLE XIV, THEN A SEPARATE LANDSCAPE PERMIT
 APPLICATION SHALL BE SUBMITTED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-04-25 Cont ID  
Sent By jroach Date 2012-04-25 Time 10:30 Rev Time 0.00
Received By jroach Date 2012-04-25 Time 10:11 Sent To  
Notes
2012-04-25 10:30:14ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.25.2012
 PERMIT NO.: 12040280
 ADDRESS: 1371 9TH COURT
 CONTRACTOR/CONTACT: LAWRENCE HARRIS
 TELEPHONE NO.: 561.213.2668
 SCOPE OF REVIEW: ADDITION OF 2 BEDROOMS AND 1 BATH TO
 EXISTING RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
 2. PLEASE NOTE THE HEIGHT OF THE PROPOSED ADDITION.
 BUILDING HEIGHT SHALL BE MEASURED FROM GRADE TO THE
 MEAN POINT OF THE PITCHED ROOF.
 3. PLANS INDICATE THE ADDITION OF A CONDENSING UNIT AT
 THE REAR OF THE PROPOSED ADDITION. PLEASE NOTE THE
 SETBACKS FROM THE CONDENSING UNIT TO ALL ADJACENT
 PROPERTY LINES (SIDES AND REAR). MECHANICAL EQUIPMENT
 SHALL NOT ENCROACH MORE THAN FOUR (4) FEET INTO ANY
 REQUIRED SETBACK.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  