Plan Review Details - Permit 12040231
Plan Review Stops For Permit 12040231
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-10-09 Cont ID  
Sent By jgomez Date 2012-10-09 Time 11:07 Rev Time 0.00
Received By jgomez Date 2012-10-09 Time 11:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-09-14 Cont ID  
Sent By jgomez Date 2012-09-14 Time 11:58 Rev Time 0.00
Received By jgomez Date 2012-09-14 Time 11:58 Sent To  
Notes
2012-09-14 11:59:37RESIDENTIAL (R3) ADDITION THIRD BUILDING REVIEW
 CHECKLIST.
 2010 FBC.
  
 1- WALL SECTION:
 A) REVISE R-VALUE INSULATION SHOWN ON THE WALL SECTION
 TO MATCH INFORMATION GIVEN ON THE ENERGY CALCULATIONS.
 SEE TABLE 402A OF ENERGY CALCULATIONS SUBMITTED. REVISE
 AS REQUIRED.
 NOTE: CHECK VALUES GIVEN FOR INTERIOR OF WALL AND
 EXTERIOR OF WALL AND REVISE/COORDINATE WITH PLANS AS
 REQUIRED.
  
 B) R-30 BATT INSULATION DOESN'T FIT ON 2X8 ROOF
 RAFTERS. REVISE AS REQUIRED. NEED R-30 PER TABLE 402A
 OF ENERGY CALCULATIONS SUBMITTED.
  
 C) COORDINATE TYPE OF ROOFING SYSTEM TO BE INSTALLED
 WITH PRODUCT APPROVAL SUBMITTED. SEE ITEM 4(B) BELOW.
 REVISE AS REQUIRED.
  
 2- FLAT ROOF NOA 11-0425.07 SUBMITTED:
 A) IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
 ***NOTE: IF DESIGN PRESSURES ON SELECTED ASSEMBLY ARE
 GOOD FOR THE PERIMETER AND CORNER AREAS, THEN
 ADDITIONAL RAS 117 CALCULATIONS ARE NOT REQUIRED.
  
 3- NEED SEPARATE PERMITS FOR ELECTRICAL, MECHANICAL,
 PLUMBING, ROOFING. OWNER BUILDER CAN SIGN ON THE PERMIT
 APPLICATION FOR THESE SUBPERMITS OR CONTRACTORS MAY
 APPLY FOR THEIR OWN SUBPERMITS. INDICATE WHICH OPTION
 IS GOING TO BE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-06-25 Cont ID  
Sent By jgomez Date 2012-06-22 Time 14:51 Rev Time 0.00
Received By jgomez Date 2012-06-22 Time 14:51 Sent To  
Notes
2012-06-22 15:48:29RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW
 CHECKLIST.
 2010 FBC.
  
 1- WALL SECTION:
 A) REVISE R-VALUE INSULATION SHOWN ON THE WALL SECTION
 TO MATCH INFORMATION GIVEN ON THE ENERGY CALCULATIONS.
 REQUIRED BY TABLE 402.1.1 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) R-30 BATT INSULATION DOESN'T FIT ON 2X8 ROOF
 RAFTERS. REVISE AS REQUIRED. NEED R-30 PER TABLE
 402.1.1.
  
 C) FOOTING SHALL BE 12" MIN. BELOW GRADE AS REQUIRED BY
 SEC. R403.1.4. REPEAT COMMENT. NOT ADDRESSED. REVISE AS
 REQUIRED.
  
 D) COORDINATE TYPE OF ROOFING SYSTEM TO BE INSTALLED
 WITH PRODUCT APPROVAL SUBMITTED. SEE APPROVED FLAT ROOF
 SYSTEM SELECTED ON NOA SUBMITTED AND REVISE AS
 REQUIRED.
  
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF ASSEMBLY. NOA 08-0226.06 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA.
  
 ***NOTE: PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST PAGE OF
 NOA SUBMITTED. ENGINEER TO COORDINATE RAS 117
 CALCULATIONS WITH REVISED NOA.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) NEW PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 4- NEED SEPARATE PERMITS FOR ELECTRICAL, MECHANICAL,
 PLUMBING, ROOFING. OWNER BUILDER CAN SIGN ON THE PERMIT
 APPLICATION FOR THESE SUBPERMITS OR CONTRACTORS MAY
 APPLY FOR THEIR OWN SUBPERMITS. INDICATE WHICH OPTION
 IS GOING TO BE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-11 Cont ID  
Sent By jgomez Date 2012-05-11 Time 12:46 Rev Time 0.00
Received By jgomez Date 2012-05-11 Time 10:50 Sent To  
Notes
2012-05-11 13:17:36RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE. 2010 FBC
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 405.4.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- ONCE PLANS ARE REVISED, PLEASE BRING THEM TO PALM
 BEACH COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES
 ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.
  
 3- REVISE BUILDING CODE AND WIND LOAD DESIGN
 CERTIFICATION ON SHEET 1:
 A) CURRENT CODE EDITION IS 2010 FLORIDA RESIDENTIAL
 CODE. THERE IS NOT 2009 FBC.
  
 B) REVISE BASIC WIND SPEED. 2010 FLORIDA RESIDENTIAL
 CODE IS BASED ON THE ULTIMATE DESIGN WIND SPEED VULT
 AND THE NOMINAL DESIGN WIND SPEED VASD. SEE SEC.
 R301.2..1.3. NOTE: CITY OF WEST PALM BEACH ULTIMATE
 DESIGN WIND SPEED IS 170MPH.
  
 4- PROVIDE LICENSE NUMBER FOR CARLOS M. GONZALEZ AS
 REQUIRED BY CHAPTER 481 FLORIDA STATUTE. TITLE BLOCK
 SHOWS CARLOS GONZALEZ OFFERING THE PROFESSIONAL
 SERVICES OF ARCHITECTURE, PLANNING AND INTERIOR DESIGN.
 LICENSE IS REQUIRED BY CHAPTER 481 FLORIDA STATUTE OR
 REMOVE FROM TITLE BLOCK.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) EXTERIOR DOOR AS SHOWN ON PLANS.
  
 B) FLAT ROOF ASSEMBLY. CLEARLY SPECIFY APPROVED
 ASSEMBLY AND PROVIDE THE RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7.
 ***NOTE: IF PRODUCT APPROVAL SUBMITTED REQUIRES SIGNED
 AND SEALED RAS 117 CALCULATIONS, THEN THOSE
 CALCULATIONS ARE REQUIRED TO BE SIGNED AND SEALED.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE SPECIFIED CONNECTOR. THIS APPLIES FOR
 STRUCTURAL CONNECTORS ONLY.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 7- REVISE WALL SECTION ON SHEET 1:
 A) SPECIFY THICKNESS OF ROOF SHEATHING.
 B) SPECIFY ROOF SHEATHING FASTENING. SEC. R803.2.3.1.
 NEED MIN. 8D RING SHANK NAILS AND ZONE 3 REQUIRES
 FASTENING @ 4"O.C.
 C) SPECIFY ROOF INSULATION. COORDINATE WITH THE ENERGY
 CALCULATIONS.
 D) SPECIFY INSIDE CEILING HEIGHT. SEC. R305.
 E) MINIMUM DEPTH OF CONCRETE FOOTING BELOW GRADE IS
 12". CLEARLY INDICATE THE FINISH GRADE LINE AND REVISE
 AS REQUIRED. SEC. R403.1.4.
  
 8- FOUNDATION PLAN: PLEASE PROVIDE COMPLETE
 SPECIFICATIONS FOR 8"X8" COLUMNS WITH 3000PSI CONCRETE.
 CLARIFY WHY THERE ARE IS NOT STEEL BAR SPECIFIED.
 PROVIDE ENGINEERING ANALYSIS SHOWING WHY REINFORCEMENT
 IS NOT REQUIRED. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC.
  
 9- NEED SEPARATE PERMITS FOR ELECTRICAL, MECHANICAL,
 PLUMBING, ROOFING. OWNER BUILDER CAN SIGN ON THE PERMIT
 APPLICATION FOR THESE SUBPERMITS OR CONTRACTORS MAY
 APPLY FOR THEIR OWN SUBPERMITS.
  
 10- ROOF FRAMING PLAN:
 A) PLEASE SPECIFY FROM WHICH CATALOG IS THE LUP28 JOIST
 HANGER TAKEN FROM?. UNABLE TO FIND IT IN THE SIMPSON
 CATALOG. PROVIDE PRODUCT APRPOVAL FOR THIS PRODUCT.
 SEC. 107.2.1.3 CITY AMENDMENTS TO FBC.
  
 11- FLOOR TO FLOOR CONNECTION DETAIL SHOWS NEW CONCRETE
 SLAB AT THE SAME LEVEL AS THE EXISTING SLAB, WHILE
 FOUNDATION PLANS SHOWS A 6" DROP. CLARIFY AND REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-01 Cont ID  
Sent By jleahy Date 2012-05-01 Time 09:27 Rev Time 0.00
Received By jleahy Date 2012-05-01 Time 09:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-10-09 Cont ID  
Sent By jgomez Date 2012-10-09 Time 11:07 Rev Time 0.00
Received By jgomez Date 2012-10-09 Time 11:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2012-09-14 Cont ID  
Sent By jgomez Date 2012-09-14 Time 15:44 Rev Time 0.00
Received By jgomez Date 2012-09-05 Time 16:48 Sent To  
Notes
2012-09-05 16:49:10SENT TO J GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-25 Cont ID  
Sent By jgomez Date 2012-06-25 Time 13:56 Rev Time 0.00
Received By jgomez Date 2012-06-15 Time 10:24 Sent To  
Notes
2012-06-15 10:26:41GAVE TO JULIO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-11 Cont ID  
Sent By jgomez Date 2012-05-11 Time 16:41 Rev Time 0.00
Received By jgomez Date 2012-04-10 Time 12:41 Sent To  
Notes
2012-04-10 12:42:44R17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-06-22 Cont ID  
Sent By jgomez Date 2012-06-22 Time 15:48 Rev Time 0.00
Received By jgomez Date 2012-06-22 Time 15:48 Sent To  
Notes
2012-06-22 15:50:47NO IMPACT FEES DUE. PALM BEACH COUNTY STAMP DATED JUNE
 15, 2012. MU 2012-11054.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-05-11 Cont ID  
Sent By jgomez Date 2012-05-11 Time 16:42 Rev Time 0.00
Received By jgomez Date 2012-05-11 Time 16:42 Sent To  
Notes
2012-05-11 16:43:10PLEASE BRING REVISED PLANS TO PALM BEACH COUNTY TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-09-14 Cont ID  
Sent By jgomez Date 2012-09-14 Time 15:43 Rev Time 0.00
Received By jgomez Date 2012-09-14 Time 15:43 Sent To  
Notes
2012-09-14 15:46:27EXISTING DRYER VENT. SEE NOTE ON FLOOR PLANS SHEET 1 OF
 1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-06-25 Cont ID  
Sent By jgomez Date 2012-06-25 Time 12:44 Rev Time 0.00
Received By jgomez Date 2012-06-25 Time 12:44 Sent To  
Notes
2012-06-25 12:49:14RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW SECOND
 CHECKLIST.
 2010 FBC.
  
 1- PLEASE PROVIDE SPECIFICATIONS ON PLANS SHOWING
 COMPLIANCE WITH THE CLOTHES DRYER EXHAUST AS REQUIRED
 BY SEC. M1502. NOT ADDRESSED. EXHAUST FAN NOT SHOWN.
  
 2- PERSON RESPONSIBLE FOR THE DESIGN OF MECHANICAL
 DRAWING M.1 NEEDS TO PROVIDE NAME AND SIGNATURE AS
 REQUIRED BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-11 Cont ID  
Sent By jgomez Date 2012-05-11 Time 16:47 Rev Time 0.00
Received By jgomez Date 2012-05-11 Time 16:47 Sent To  
Notes
2012-05-11 16:49:25RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW COMMENTS.
 2010 FBC.
  
 1- PLEASE PROVIDE SPECIFICATION SHOWING COMPLIANCE WITH
 THE CLOTHES DRYER EXHAUST AS REQUIRED BY SEC. M1502.
  
 2- PLEASE PROVIDE COMPLETE INFORMATION ON DRAWINGS FOR
 FOR A/C WORK TO BE PERFORMED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-25 Cont ID  
Sent By jgomez Date 2012-06-25 Time 12:49 Rev Time 0.00
Received By jgomez Date 2012-06-25 Time 12:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-05-11 Cont ID  
Sent By jgomez Date 2012-05-11 Time 16:37 Rev Time 0.00
Received By jgomez Date 2012-05-11 Time 16:37 Sent To  
Notes
2012-05-11 16:41:47RESIDENTIAL (R3) ADDITION PLUMBING REVIEW COMMENTS.
 2010 FBC
  
 1- PROVIDE PLUMBING RISER DIAGRAM FOR NEW CLOTHES
 DISHWASHER AS REQUIRED BY SEC. 107.3.5.3(11) OF CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 1 Status P Date 2012-05-10 Cont ID  
Sent By lfranco Date 2012-04-30 Time 18:15 Rev Time 0.25
Received By lfranco Date 2012-04-30 Time 17:43 Sent To  
Notes
***NONE***