Plan Review Details - Permit 12040169
Plan Review Stops For Permit 12040169
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-04-13 Cont ID  
Sent By jwitmer Date 2012-04-13 Time 13:10 Rev Time 0.00
Received By jwitmer Date 2012-04-13 Time 12:32 Sent To  
Notes
2012-04-13 13:10:30BUILDING PROVISO:
 SHEET A-1.01
 1) REAR WATER CLOSET GRAB BAR FROM CENTER LINE WC TO
 THE SHORT END OF GRAB BAR MIN 12" APPROX 6 " TO
 WALL.2010 FBC-B 11-604.5.2
  
 2) HEIGHT OF GRAB BARS TO BE MEASURED FROM FINISH FLOOR
 TO THE TOP OF BAR, 33-36 INCHES.2010 FBC-B11-609.4.
  
 3) DRINKING FOUNTAIN THE HIGH DRINKING FOUNTAIN WILL
 NEED A SKIRT TO DROP DOWN TO THE HEIGHT OF 27" , 2010
 FBC-B 11-307.2 PROTRUDING OBJECTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-04-09 Cont ID  
Sent By rlecky Date 2012-04-09 Time 17:50 Rev Time 0.00
Received By rlecky Date 2012-04-09 Time 17:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-04-18 Cont ID  
Sent By wjolin Date 2012-04-18 Time 13:28 Rev Time 0.00
Received By wjolin Date 2012-04-18 Time 10:36 Sent To  
Notes
2012-04-18 12:48:229847 OKEECHOBEE BOULEVARD
 PERMIT #12040169
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SHELL ONLY***** NO TENANT
  
 A FLOOR PLAN SHOWING AISLE LAYOUTS, CHECKOUT STANDS,
 EQUIPMENT, STORAGE, ETC. WILL BE NEEDED WHEN A TENANT
 INTENDS TO OCCUPY THIS BUILDING.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-18 Cont ID  
Sent By wjolin Date 2012-04-18 Time 13:28 Rev Time 0.00
Received By wjolin Date 2012-04-06 Time 13:11 Sent To  
Notes
2012-04-06 13:12:16EXPEDITED
 B--21

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-04-13 Cont ID  
Sent By hmoser Date 2012-04-13 Time 12:29 Rev Time 0.00
Received By hmoser Date 2012-04-13 Time 10:26 Sent To  
Notes
2012-04-13 12:29:26PASS PROVISO
 REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROL'S
 2010 ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-04-18 Cont ID  
Sent By lwagner Date 2012-04-18 Time 09:19 Rev Time 0.00
Received By lwagner Date 2012-04-18 Time 09:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-04-17 Cont ID  
Sent By jroach Date 2012-04-17 Time 15:33 Rev Time 0.00
Received By jroach Date 2012-04-17 Time 15:33 Sent To  
Notes
***NONE***