Plan Review Details - Permit 12040126
Plan Review Stops For Permit 12040126
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-04-09 Cont ID  
Sent By rlecky Date 2012-04-09 Time 14:20 Rev Time 0.00
Received By rlecky Date 2012-04-09 Time 14:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2012-04-06 Time   Rev Time  
Received By   Date 2012-04-06 Time   Sent To E
Notes
2012-04-06 12:59:1204/06/2012
 PERMIT #12040126
 601 CLEARWATER PARK ROAD
  
 PLANS REVIEWED BY FIRE (PASSED)
  
 * LOSS OF POWER TO THE PART OF THE ACCES CONTROL SYSTEM
 THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK THE
 DOORS IN THE DIRECTION OF EGRESS.
  
 * THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
  
 * ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY REST.
  
  
 RONALD E. FERGUSON ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 PHONE (561) 804 - 4700
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-09 Cont ID  
Sent By rlecky Date 2012-04-09 Time 14:21 Rev Time 0.00
Received By rlecky Date 2012-04-05 Time 15:00 Sent To  
Notes
2012-04-05 15:00:48IN FIRE BOX