Plan Review Details - Permit 12040097
Plan Review Stops For Permit 12040097
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-01 Cont ID  
Sent By jwitmer Date 2012-06-01 Time 13:17 Rev Time 0.00
Received By jwitmer Date 2012-06-01 Time 13:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-04-18 Cont ID  
Sent By jwitmer Date 2012-04-18 Time 16:04 Rev Time 0.00
Received By jwitmer Date 2012-04-18 Time 15:58 Sent To  
Notes
2012-04-18 16:38:59BUILDING PLAN REVIEW
 PERMIT: 12040097
 ADD: 2481 OKEECHOBEE BLVD
 CONT: TO BE DETERMINED
 TEL: (407)661-9100
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1A) SHEET A-700 :PRODUCT APPROVAL
 STANLEY ACCESS TECHNOLOGIES
 NOA 09-0312.17
 DURA-GLIDE "3000" ALUMINUM AUTOMATIC SLIDDING GLASS
 DOOR, W BREAKOUT DOORS
 NON-IMPACT GLAZING, WILL REQUIRE EITHER IMPACT RATED
 GLAZING OR SHUTTERS WILL BE REQUIRED FOR THESE
 OPENINGS.
  
 1B) SHEET A-700 STANLEY DUR-GLIDE NOA IS MISSING SHEET
 THREE OF THE NOA.
  
 2) SHEET A-704 / A-707 PRODUCT APPROVAL
 JOHN MANVILLE ROOFING
 NOA 09-1013.05
 JM TPO SINGLE PLY ROOFING OVER STEEL DECK
 THE SUB-SYSTEMS ARE NOT CIRCLED INDICATING WHICH SYSTEM
 WILL BE INSTALLED, EACH SUB-SYSTEM HAS ITS OWN
 PRESSURES, SEE THE LAST PAGE OF THE NOA LIMITATION #7
 AND 9.
 ENHANCED FASTENING IS ALLOWED WITH LIMITATION NUMBER 7.
  
 3) SHEET A-121:
 3A) PLANS INDICATE THE USE OF A NEW ROOF HATCH RULE
 9N-3 (31)(A) ROOF ACCESS HATCHES REQUIRE PRODUCT
 APPROVALS/ 1609.COMPONENTS & CLADDING.
  
 3B) DETAIL A1 INDICATES THE USSE OF RAINLOC PANEL
 SYSTEM RULE 9N-3(31)(C) SIDING, WALL PANELS REQUIRE
 PRODUCT APPROVALS/ 1609. COMPONENTS & CLADDING.
  
 4) SHEET S-001 FOUNDATION NOTE B INDICATES THERE IS TO
 BE GEOTECHNICAL SOILS REPORT COMPLETED ANDSUBMITTED
 DESCRIBING THE INVESTIGATION AND ANY NON-CONFORMITIES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-05-17 Cont ID  
Sent By rlecky Date 2012-05-17 Time 08:41 Rev Time 0.00
Received By rlecky Date 2012-05-16 Time 16:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-05-07 Cont ID  
Sent By rlecky Date 2012-05-07 Time 09:18 Rev Time 0.00
Received By rlecky Date 2012-05-04 Time 14:53 Sent To  
Notes
2012-05-07 09:17:5112040097
 2471 OKEECHOBEE BLVD.
 ALDI FOOD STORE
  
 1. VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS
 BUILDING ARE SIX OR LESS AND GROUPED IN ONE LOCATION.
 THE SITE PLANS SUGGEST THIS BUILDING MAY ALREADY BE
 SERVED FROM ANOTHER LOCATION. NEC 230.2, 230.71, 230.72
 2. PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
 3. PROVIDE A LIGHTING DENSITY CALCULATION VERIFYING
 COMPLIANCE WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC EC 505.5.3
 4. PROVIDE A DETAIL WHICH PROVIDES A DEDICATED WORKING
 SPACE FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS.
 NEC 110.26, 240.24, 408.17
 5. A GFCI GENERAL PURPOSE RECEPTACLE IS REQUIRED AT AN
 ACCESSIBLE LOCATION FOR THE SERVICE OF HEATING, AIR
 CONDITIONING, AND REFRIGERATION EQUIPMENT LOCATED ON
 THE ROOF. NEC 210.63
 6. PROVIDE THE SPECIFICATIONS AND LISTINGS FOR THE
 GENERATOR QUICK CONNECT. NEC 90.7
 7. VERIFY LISTING BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY (NRTL) FOR THE FACTORY WIRED ?POWER WALL?
 ASSEMBLIES NOTED ON THE PLANS AS PANEL BOARD L1AND L2.
 NEC 90.7, 215.5
 8. VERIFY LISTING BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY OF THE FACTORY WIRED ?PROTOCOL RACK?
 ASSEMBLY NOTED ON THE PLANS FOR REFRIGERATION. NEC 90.7
 9. VERIFY LISTING BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY OF THE OWNER SUPPLIED UPS. NEC 90.7
 10. PROVIDE A SAFETY LABELING SCHEDULE FOR THE
 ELECTRICAL EQUIPMENT WHICH INCLUDES SPECIFIC WORDING
 REGARDING THE SIZE AND TYPE OF HAZARDS. NEC 110.22,
 110.16
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, SECURITY, VOICE AND DATA.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2012-05-03 Cont ID  
Sent By mgonzale Date 2012-05-03 Time   Rev Time 1.00
Received By mgonzale Date 2012-05-03 Time   Sent To  
Notes
2012-05-03 14:33:01PROVISOS:
  
 #1 SUBMITTAL DOES NOT INCLUDE EXTERIOR WORK THAT WILL
 BE REVIEWED BY PLANNING AND ZONING.
  
 #2 PERMIT ONLY EXTERIOR ELEMENTS EXCLUDING UTILITY
 ELEMENTS THAT WILL BE REVIEWED BY ENGINEERING SERVICES
 UNDER PERMIT # E12040007
  
 #3 EXCLUDE UTILITY ELEMENTS FROM THE VALUATION AT DSD.
  
 PLEASE CONTACT ME IF ANY QUESTIONS. THANK YOU!
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-06-05 Cont ID  
Sent By wjolin Date 2012-06-05 Time 10:51 Rev Time 0.00
Received By wjolin Date 2012-06-05 Time 10:30 Sent To  
Notes
2012-06-05 10:51:362481 OKEECHOBEE BOULEVARD
 PERMIT #12040097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 A KNOX-BOX KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 EXIT DOORS EQUIPPED WITH DELAYED EGRESS LOCKING SYSTEMS
 SHALL COMPLY WITH THE FOLLOWING:
 1) UNLOCK UPON ACTUATION OF THE FIRE SPRINKLER OR FIRE
 ALARM SYSTEM
 2) UNLOCK UPON LOSS OF POWER CONTROLLING THE LOCKING
 MECHANISM
 3) AN IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK
 WITHIN 15 SECONDS, UPON APPLICATION OF A FORCE TO THE
 RELEASE DEVICE REQUIRED IN 7.2.1.5.9 UNDER THE
 FOLLOWING CONDITIONS:
 (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF
 (67 N).
 (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY
 APPLIED FOR MORE THAN 3 SECONDS.
 (C) THE INITIATION OF THE RELEASE PROCESS SHALL
 ACTIVATE AN AUDIBLE SIGNAL IN THE VICINITY OF THE DOOR
 OPENING.
 (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION
 OF FORCE TO THE RELEASING DEVICE, RELOCKING SHALL BE BY
 MANUAL MEANS ONLY.
 (4)A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. HIGH AND NOT LESS THAN 1/8 IN. IN STROKE
 WIDTH ON A CONTRASTING BACKGROUND THAT READS AS FOLLOWS
 SHALL BE LOCATED ON THE DOOR LEAF ADJACENT TO THE
 RELEASE DEVICE: "PUSH UNTILALARM SOUNDS DOOR CAN BE
 OPENED IN 15 SECONDS"
  
 EXIT DOORS EQUIPPED WITH POWERED DOOR LEAF OPERATION
 SHALL COMPLY WITH THE FOLLOWING:
 1) IN THE EVENT OF POWER FAILURE, THE LEAVES OPEN
 MANUALLY TO ALLOW EGRESS TRAVEL OR CLOSE WHEN NECESSARY
 TO SAFEGUARD THE MEANS OF EGRESS.
 2) THE FORCE REQUIRED TO SET THE LEAF IN MOTION SHALL
 NOT EXCEED 50 LBF (222 N).
 3) THE DOOR ASSEMBLY SHALL BE DESIGNED AND INSTALLED SO
 THAT, WHEN A FORCE IS APPLIED TO THE DOOR LEAF ON THE
 SIDE FROM WHICH EGRESS IS MADE, IT SHALL BE CAPABLE OF
 SWINGING FROM ANY POSITION TO PROVIDE FULL USE OF THE
 REQUIRED WIDTH OF THE OPENING IN WHICH IT IS INSTALLED.
 4) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. HIGH ON A CONTRASTING BACKGROUND THAT READS
 AS FOLLOWS SHALL BE LOCATED ON THE EGRESS SIDE OF EACH
 DOOR OPENING: "IN EMERGENCY - PUSH TO OPEN"
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-04-17 Cont ID  
Sent By wjolin Date 2012-04-17 Time 14:37 Rev Time 0.00
Received By wjolin Date 2012-04-17 Time 13:05 Sent To  
Notes
2012-04-17 14:37:532471 OKEECHOBEE BOULEVARD
 PERMIT #12040097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 A KNOX-BOX KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 EXIT DOORS EQUIPPED WITH DELAYED EGRESS LOCKING SYSTEMS
 SHALL COMPLY WITH THE FOLLOWING:
 1) UNLOCK UPON ACTUATION OF THE FIRE SPRINKLER OR FIRE
 ALARM SYSTEM
 2) UNLOCK UPON LOSS OF POWER CONTROLLING THE LOCKING
 MECHANISM
 3) AN IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK
 WITHIN 15 SECONDS, UPON APPLICATION OF A FORCE TO THE
 RELEASE DEVICE REQUIRED IN 7.2.1.5.9 UNDER THE
 FOLLOWING CONDITIONS:
 (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF
 (67 N).
 (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY
 APPLIED FOR MORE THAN 3 SECONDS.
 (C) THE INITIATION OF THE RELEASE PROCESS SHALL
 ACTIVATE AN AUDIBLE SIGNAL IN THE VICINITY OF THE DOOR
 OPENING.
 (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION
 OF FORCE TO THE RELEASING DEVICE, RELOCKING SHALL BE BY
 MANUAL MEANS ONLY.
 (4)A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. HIGH AND NOT LESS THAN 1/8 IN. IN STROKE
 WIDTH ON A CONTRASTING BACKGROUND THAT READS AS FOLLOWS
 SHALL BE LOCATED ON THE DOOR LEAF ADJACENT TO THE
 RELEASE DEVICE: "PUSH UNTILALARM SOUNDS DOOR CAN BE
 OPENED IN 15 SECONDS"
  
 EXIT DOORS EQUIPPED WITH POWERED DOOR LEAF OPERATION
 SHALL COMPLY WITH THE FOLLOWING:
 1) IN THE EVENT OF POWER FAILURE, THE LEAVES OPEN
 MANUALLY TO ALLOW EGRESS TRAVEL OR CLOSE WHEN NECESSARY
 TO SAFEGUARD THE MEANS OF EGRESS.
 2) THE FORCE REQUIRED TO SET THE LEAF IN MOTION SHALL
 NOT EXCEED 50 LBF (222 N).
 3) THE DOOR ASSEMBLY SHALL BE DESIGNED AND INSTALLED SO
 THAT, WHEN A FORCE IS APPLIED TO THE DOOR LEAF ON THE
 SIDE FROM WHICH EGRESS IS MADE, IT SHALL BE CAPABLE OF
 SWINGING FROM ANY POSITION TO PROVIDE FULL USE OF THE
 REQUIRED WIDTH OF THE OPENING IN WHICH IT IS INSTALLED.
 4) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. HIGH ON A CONTRASTING BACKGROUND THAT READS
 AS FOLLOWS SHALL BE LOCATED ON THE EGRESS SIDE OF EACH
 DOOR OPENING: "IN EMERGENCY - PUSH TO OPEN"
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-07 Cont ID  
Sent By shill Date 2012-06-07 Time 17:57 Rev Time 0.00
Received By shill Date 2012-05-16 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-07 Cont ID  
Sent By rlecky Date 2012-05-07 Time 09:56 Rev Time 0.00
Received By rlecky Date 2012-04-05 Time 10:45 Sent To  
Notes
2012-04-05 10:46:13INCOMING SENT TO C-04. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-06-27 Cont ID  
Sent By rbrown Date 2012-06-27 Time 11:36 Rev Time 0.00
Received By rbrown Date 2012-06-27 Time 11:35 Sent To  
Notes
2012-06-27 11:37:11PALM BEACH COUNTY PROVIDED IMPACT FEE STAMP ON PLAN
 STATING THAT NO IMPACT FEES ARE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2012-04-24 19:42:14PER COUNTY TRAFFIC ENGINEERING LETTER RENOVATIONS ADDED
 324 SF TO EXISTING BUILDING. NEED COUNTY IMPACT
 APPROVAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-04-17 Cont ID  
Sent By hmoser Date 2012-04-17 Time 08:56 Rev Time 0.00
Received By hmoser Date 2012-04-16 Time 13:35 Sent To  
Notes
2012-04-17 08:56:47PROVISO
 1) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE ( OUT SIDE AIR)
 2) REFER TO SECTION 307.2.3.1 WATER LEVEL MONITORING
 DEVICE. 2010 FBC (M)
 3) REFER TO SECTION 307.2.1 CONDENSATE DISPOSAL. 2010
 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-04-20 Cont ID  
Sent By lwagner Date 2012-04-20 Time 14:48 Rev Time 0.00
Received By lwagner Date 2012-04-20 Time 14:08 Sent To  
Notes
2012-04-20 14:47:58***PROVISO***
 NO HORIZONTAL DRY VENTS PERMITTED 905.4

Review Stop Z ZONING
Rev No 1 Status P Date 2012-05-03 Cont ID  
Sent By lfranco Date 2012-05-03 Time 14:01 Rev Time 0.00
Received By lfranco Date 2012-04-23 Time 11:23 Sent To  
Notes
2012-05-03 14:19:275/3/12 PERMIT WAS PICKED-UP FROM ENGINEERING. LMF
2012-05-03 14:18:55 
  
 PLANNING: **** PASSED WITH PROVISO, SUBMIT SEPARATE
 PERMITS FOR THE EXTERIOR WORK (INCLUDING, BUT NOT
 LIMITED TO THE NEW SIDEWALK ACCESS AND RECONFIGURED
 PARKING STALLS LOCATED ON THE WEST SIDE OF THE ALDI'S
 BUILDING AND A SEPARATE PERMIT FOR THE WALL SIGNAGE.
 ALL SCOPE OF WORK SHALL MATCH THE WESTWARD SHOPPING CTR
 MINOR DSI AMENDMENT APPROVED PLANS (PB 1520G) BY THE
 PLANNING DIVISION AND PREPARED BY BOHLER ENGINEERING. A
 FINAL ZONING SIGN-OFF FOR CERTIFICATE OF COMPLETION OR
 C.O. WILL NOT BE APPROVED, UNLESS PROVISO ABOVE IS
 ADDRESSED.
  
  
 NOTE TO BOHLER ENGINEERING (MIKE TROXELL): SHEET C-2
 SUBMITTED AS PART OF THIS PERMIT WAS REVISED AFTER
 MARCH 8, 2012. TWO (2) EXTRA REVISED SHEETS OF C-2 WERE
 SUBMITTED TO THE PLANNING DIVISION. COORDINATE WITH ME
 TO GET THESE SHEETS BACK OR PROVIDE A SET THAT INCLUDES
 LATEST REVISED SHEETS, INCLUDING SHEET C-2 WITH SQUARE
 FOOTAGE REVISION OF TOTAL GROSS BUILDING OF 238, 704.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  
2012-04-24 20:12:464/24/12 ROUTED TO ENGINEERING FOR REVIEW. LMF