| 2012-04-16 12:07:30 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | 2010 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE CONTRACTOR OF RECORD THAT IS RESPONSIBLE FOR |
| | THEIR PLAN FOR WHICH DISCIPLINE THEY ARE LICENSED SHALL |
| | PRINT THIER NAME, SIGN THEIR NAME & LICESE NUMBER TO |
| | THE PLANS. |
| | 106.1.1. |
| | |
| | 2) PLEASE PROVIDE A FLOOR PLAN OF THE COMPLETE TENANT |
| | SPACE AND THE LOCATION OF THE NEW STORAGE ROOM WITHIN |
| | THE WAREHOUSE. FLOOR PLAN. 106.3.5.1.1 MINIMUM CRITERIA |
| | FOR COMMERCIAL PLAN REVIEW. |
| | |
| | 3) THE SECOND SHEET OF THE PLANS INDICATES THE USE OF A |
| | HOPPER AND DUST COLLECTION SYSTEM,IS THIS PART OF THE |
| | NEW STORAGE ROOM? OR THIS ANOTHER AREA OF WORK TO BE |
| | COMPLETED UNDER THIS PERMIT? PLEASE PROVIDE ADDITIONAL |
| | INFOR MATION ON THE HOPPER AND DUST COLLECTION SYSTEM, |
| | WHAT TYPES OF DUST ARE TO BE REMOVED? |
| | |
| | 2010 FBC-B COMBUSTIBLE DUST TABLE 414.5 SEE FOOTNOTE"C" |
| | |
| | |
| | [F] 415.8.2.1 HAZARDOUS MATERIALS IN FABRICATION AREAS. |
| | |
| | [F] 415.8.2.1.1 AGGREGATE QUANTITIES. THE AGGREGATE |
| | QUANTITIES OF HAZARDOUS MATERIALS STORED AND USED IN A |
| | SINGLE FABRICATION AREA SHALL NOT EXCEED THE QUANTITIES |
| | SET FORTH IN TABLE 415.8.2.1.1. |
| | |
| | EXCEPTION: THE QUANTITY LIMITATIONS FOR ANY HAZARD |
| | CATEGORY IN TABLE 415.8.2.1.1 SHALL NOT APPLY WHERE THE |
| | FABRICATION AREA CONTAINS QUANTITIES OF HAZARDOUS |
| | MATERIALS NOT EXCEEDING THE MAXIMUM ALLOWABLE |
| | QUANTITIES PER CONTROL AREA ESTABLISHED BY TABLES |
| | 307.1(1) AND 307.1(2). |
| | |
| | [F] 415.8.2.1.2 HAZARDOUS PRODUCTION MATERIALS. THE |
| | MAXIMUM QUANTITIES OF HAZARDOUS PRODUCTION MATERIALS |
| | (HPM) STORED IN A SINGLE FABRICATION AREA SHALL NOT |
| | EXCEED THE MAXIMUM ALLOWABLE QUANTITIES PER CONTROL |
| | AREA ESTABLISHED BY TABLES 307.1(1) AND 307.1(2). |
| | |
| | [F] 415.8.2.2 SEPARATION. FABRICATION AREAS, WHOSE |
| | SIZES ARE LIMITED BY THE QUANTITY OF HAZARDOUS |
| | MATERIALS ALLOWED BY TABLE 415.8.2.1.1, SHALL BE |
| | SEPARATED FROM EACH OTHER, FROM CORRIDORS AND FROM |
| | OTHER PARTS OF THE BUILDING BY NOT LESS THAN 1-HOUR |
| | FIRE BARRIERS. |
| | |
| | 2010 FBC-B TABLE 415.8.2.1.1 COMBUSTIBLE DUST NOTE B |
| | B. QUANTITY OF HAZARDOUS MATERIALS IN A SINGLE |
| | FABRICATION SHALL NOT EXCEED THE MAXIMUM ALLOWABLE |
| | QUANTITIES PER CONTROL AREA IN TABLES 307.1(1) AND |
| | 307.1(2). |
| | |
| | 2010 FBC-M 510 WOODWORKING FACILITIES. |
| | EQUIPMENT OR MACHINERY LOCATED INSIDE BUILDINGS AT |
| | LUMBER YARDS AND WOODWORKING FACILITIES WHICH GENERATES |
| | OR EMITS COMBUSTIBLE DUST SHALL BE PROVIDED WITH AN |
| | APPROVED DUST-COLLECTION AND EXHAUST SYSTEM INSTALLED |
| | IN CONFORMANCE WITH THIS SECTION AND THE FLORIDA FIRE |
| | PREVENTION CODE . EQUIPMENT AND SYSTEMS THAT ARE USED |
| | TO COLLECT, PROCESS OR CONVEY COMBUSTIBLE DUSTS SHALL |
| | BE PROVIDED WITH AN APPROVED EXPLOSION-CONTROL SYSTEM. |
| | |
| | JAMES A. WITMER CBO |