Plan Review Details - Permit 12040070
Plan Review Stops For Permit 12040070
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-29 Cont ID  
Sent By hmoser Date 2012-05-29 Time 13:33 Rev Time 0.00
Received By hmoser Date 2012-05-24 Time 15:55 Sent To  
Notes
2012-05-24 15:55:48INCOMING SENT TO MECHANICAL BOX. <$5K. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-11 Cont ID  
Sent By ajones Date 2012-04-11 Time 09:48 Rev Time 0.00
Received By ajones Date 2012-04-04 Time 16:43 Sent To  
Notes
2012-04-04 16:43:15TO MECH < $5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-05-29 Cont ID  
Sent By hmoser Date 2012-05-29 Time 13:32 Rev Time 0.00
Received By hmoser Date 2012-05-29 Time 13:30 Sent To  
Notes
2012-05-29 13:32:51PROVISO
 REFER TO SECTION M1602.4 BALANCED RETURN AIR.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-04-09 Cont ID  
Sent By hmoser Date 2012-04-09 Time 13:56 Rev Time 0.00
Received By hmoser Date 2012-04-09 Time 13:46 Sent To Z
Notes
2012-04-09 13:56:24PLAN DENIED
 1) PROVIDE GRILLE SIZE AND DUCT SIZE ON PLAN.
 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 2010 FBC (R)
 3) PROVIDE ENERGY CALCULATION OR MANUAL J WITH THE PLAN
 PER SECTION 403.6.1 EQUIPMENT SIZING.2010 ENERGY CODE.
 4) REFER TO SECTIONM1305.1.3 APPLIANCE IN ATTIC.
 2010 FBC (R)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-04-11 Cont ID  
Sent By ajones Date 2012-04-11 Time 09:47 Rev Time 0.00
Received By ajones Date 2012-04-11 Time 09:06 Sent To  
Notes
2012-04-11 09:48:09FILED UNDER P- AV


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved