Plan Review Details - Permit 12040066
Plan Review Stops For Permit 12040066
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-04-06 Cont ID  
Sent By rlecky Date 2012-04-06 Time 16:29 Rev Time 0.00
Received By rlecky Date 2012-04-06 Time 16:12 Sent To  
Notes
2012-04-06 16:13:37PLANS REVISED TO PROVIDE A NEW SERVICE AND REFEED THE
 EXISTING PANEL BOARD.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-04-05 Cont ID  
Sent By rlecky Date 2012-04-05 Time 14:52 Rev Time 0.00
Received By rlecky Date 2012-04-05 Time 14:19 Sent To  
Notes
2012-04-05 14:53:4212040066
 1020 CHARLOTTE AVE
 NEW 200 AMP ELECTRIC SERVICE
  
 INDICATE THE VOLTAGE OF THE NEW AND EXISTING SERVICE.
 PROVIDE DOCUMENTATION TO JUSTIFY THE NEED FOR AN
 ADDITIONAL ELECTRICAL SERVICE. PROVIDE A LABELING
 SCHEDULE IF TWO SERVICES ARE TO BE UTILIZED. NEC 230
 (D) AND (E)
  
 ROBERT LECKY, CBO
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-06 Cont ID  
Sent By rlecky Date 2012-04-06 Time 16:29 Rev Time 0.00
Received By rlecky Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-05 Cont ID  
Sent By rlecky Date 2012-04-05 Time 14:52 Rev Time 0.00
Received By rlecky Date 2012-04-04 Time 16:43 Sent To  
Notes
2012-04-04 16:43:42TO ELEC
  