Plan Review Details - Permit 12030770
Plan Review Stops For Permit 12030770
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-08-10 Cont ID  
Sent By rmcdouga Date 2012-08-10 Time 12:37 Rev Time 0.00
Received By rmcdouga Date 2012-08-10 Time 07:31 Sent To  
Notes
2012-08-10 12:37:222010 FBC
  
 DENIED BY BUILDING
  
 1) THE FLORIDA ENGINEER THAT SIGNED AND SEALED THE
 PLANS, LUIS LOPEZ P.E. #59805, VOLUNTARILY RELINQUISHED
 HIS LICENSE ON 4/27/2012 AND CAN NO LONGER CERTIFY
 PLANS AFTER THAT DATE. FS 471
  
 2) THE WINDSPEED SPECIFIED ON THE PLANS OF 160 MPH IS
 INCORRECT. THE CORRECT VULT WINDSPEED FOR THIS PROJECT
 IS 170 MPH PER 2010 FBC R301.2.1. PLEASE CORRECT.
  
 3) THE PRESCRIPTIVE ENERGY FORM 402-2010 CAN NOT BE
 USED FOR THIS PROJECT. THIS METHOD REQUIRES EACH
 COMPONENT TO MEET OR EXCEED EACH OF THE APPLICABLE
 PERFORMANCE CRITERIA. THE SHGC (SOLAR HEAT GAIN
 COEFFICIENT) FOR THE WINDOWS, THE WALL INSULATION AND
 CEILING INSULATION R-VALUES DO NOT MEET THE REQUIRED
 VALUES. FBC ENERGY CONSERVATION SECTION 402
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-01 Cont ID  
Sent By MCDOUGAL Date 2012-05-01 Time 16:56 Rev Time 0.00
Received By rmcdouga Date 2012-05-01 Time 16:56 Sent To  
Notes
2012-05-01 11:43:582010 FBC
  
 DENIED BY BUILDING
  
 1) THE APPLICATION DATE FOR THIS PERMIT IS MARCH 30,
 2012. THE 2010 FLORIDA BUILDING CODE BECAME EFFECTIVE
 ON MARCH 15, 2012. THEREFORE, THIS PROJECT IS REQUIRED
 TO COMPLY WITH THE 2010 FLORIDA BUILDING CODE. REVISE
 PLANS TO REFERENCE THE 2010 FBC AND ASCE 7-10.
  
 2) REVISE PLANS TO REFERENCE THE 2010 FBC DESIGN
 CRITERIA FOR WINDSPEEDS AND EXPOSURE CATEGORIES. FBC
 R301.1 AND R301.2.1.4.3
  
 3) REVISE THE OPENING DESIGN PRESSURES AS NECESSARY TO
 COMPLY WITH 2010 FBC SECTION R301.2.1.
  
 4) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT COMPLY
 WITH THE 2010 FBC FOR EXTERIOR DOORS, WINDOWS,
 STRUCTURAL MULLIONS AND STORM PANELS AS REQUIRED BY DCA
 RULE 9N-3.
  
 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4.1
  
 6) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE NEW
 ROOM AS REQUIRED BY 2010 FBC ENERGY CONSERVATION
 SECTION 401.2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-04-06 Cont ID  
Sent By rlecky Date 2012-04-06 Time 12:40 Rev Time 0.00
Received By rlecky Date 2012-04-06 Time 12:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-10 Cont ID  
Sent By rmcdouga Date 2012-08-10 Time 12:37 Rev Time 0.00
Received By rmcdouga Date 2012-07-14 Time 08:37 Sent To  
Notes
2012-07-14 08:37:40TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-01 Cont ID  
Sent By rmcdouga Date 2012-05-01 Time 16:56 Rev Time 0.00
Received By rmcdouga Date 2012-03-30 Time 15:19 Sent To  
Notes
2012-03-30 15:20:38R14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-08-10 Cont ID  
Sent By rmcdouga Date 2012-08-10 Time 12:38 Rev Time 0.00
Received By rmcdouga Date 2012-08-10 Time 12:38 Sent To  
Notes
2012-08-10 12:38:29SUBMIT A COPY OF THE PAID RECIEPT FOR THE COUNTY IMPACT
 FEES.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-05-01 Cont ID  
Sent By rmcdouga Date 2012-05-01 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2012-05-01 Time 11:38 Sent To  
Notes
2012-05-01 11:39:01SUBMIT A COPY OF THE PAID RECIEPT FOR THE COUNTY IMPACT
 FEES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2012-05-01 Cont ID  
Sent By rmcdouga Date 2012-05-01 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2012-05-01 Time 11:37 Sent To  
Notes
2012-05-01 11:37:46NO MECHANICAL WORK INDICATED ON PLANS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2012-05-01 Cont ID  
Sent By rmcdouga Date 2012-05-01 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2012-05-01 Time 11:36 Sent To  
Notes
2012-05-01 11:37:03NO PLUMBING INDICATED ON PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2012-04-24 Cont ID  
Sent By lfranco Date 2012-04-24 Time 20:56 Rev Time 0.50
Received By lfranco Date 2012-04-23 Time 11:13 Sent To  
Notes
***NONE***