Plan Review Details - Permit 12030542
Plan Review Stops For Permit 12030542
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2012-04-11 Cont ID  
Sent By jwitmer Date 2012-04-11 Time 13:05 Rev Time 0.00
Received By jwitmer Date 2012-04-11 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-03-26 Cont ID  
Sent By rlecky Date 2012-03-26 Time 12:41 Rev Time 0.00
Received By rlecky Date 2012-03-26 Time 12:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-04-10 Cont ID  
Sent By wjolin Date 2012-04-10 Time 11:56 Rev Time 0.00
Received By wjolin Date 2012-04-04 Time 12:14 Sent To  
Notes
2012-04-10 11:56:467501 NORTH JOG ROAD
 PERMIT #12030542
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION HAS AN ADDRESS OF 7501 N JOG
 ROAD AND THE PLANS SHOW AN ADDRESS OF 6501 N JOG ROAD.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-09 Cont ID  
Sent By hmoser Date 2012-05-09 Time 14:57 Rev Time 0.00
Received By hmoser Date 2012-05-08 Time 18:38 Sent To  
Notes
2012-05-08 18:38:59TO HM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-11 Cont ID  
Sent By hmoser Date 2012-04-11 Time 14:33 Rev Time 0.00
Received By hmoser Date 2012-03-21 Time 07:36 Sent To  
Notes
2012-03-22 07:38:57B02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-05-09 Cont ID  
Sent By hmoser Date 2012-05-09 Time 14:49 Rev Time 0.00
Received By hmoser Date 2012-05-09 Time 14:49 Sent To  
Notes
2012-05-09 14:53:46PROVISO
 REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 FOR OUTSIDE AIR.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-04-11 Cont ID  
Sent By hmoser Date 2012-04-11 Time 14:30 Rev Time 0.00
Received By hmoser Date 2012-04-11 Time 11:17 Sent To  
Notes
2012-04-11 14:09:24PLAN DENIED
 1) PROVIDE A DETAIL FROM THE ENGINEER ON THE OUTDOOR
 AIR CURB TIE DOWN TO ROOF.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 2) REFER TO SECTION 606.2.1 SUPPLY AIR ( DUCT DETECTORS
 )
 AND 606.4.1 SUPERVISION 2010 FBC (M)
 3) REFER TO SECTION 403.5 MECHANICAL VENTILATION
 2010 FLORIDA ENERGY CODE
 4) REFER TO SECTION 403.6.1 EQUIPMENT SIZING 2010
 FLORIDA ENERGY CODE
 PLAN REVIEW BY HAROLD MOSER
 561- 805-6732
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2012-05-11 Cont ID  
Sent By eschneid Date 2012-05-11 Time 11:01 Rev Time 0.50
Received By eschneid Date 2012-05-11 Time 11:01 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-04-03 Cont ID  
Sent By eschneid Date 2012-04-03 Time 12:07 Rev Time 0.50
Received By eschneid Date 2012-04-03 Time 12:07 Sent To  
Notes
2012-04-03 12:12:38FAILED
  
 PLEASE PROVIDE THE FOLLOWING ON THE SECTION DRAWING:
  
 1) THE OVERALL HEIGHT OF THE BUILDING FROM GRADE TO THE
 ROOF.
  
 2) THE HEIGHT OF THE 14X12 INLET ABOVE THE ROOF.
  
 3) THE HEIGHT OF THE NEW CONDENSING UNIT, INCLUDING THE
 CURB AND ANY OTHER SUPPORT BRACING) ABOVE THE ROOF.
  
 PLEASE NOTE THAT THE COMMUNITY SERVICE HEIGHT LIMIT IS
 60 FEET AND THAT MECHANICAL EQUIPMENT MAY ONLY EXCEED
 THE DISTRICT HEIGHT BY 10 PERCENT - UP TO 66 FEET FROM
 GRADE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.