Plan Review Details - Permit 12030532
Plan Review Stops For Permit 12030532
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2012-04-16 Cont ID  
Sent By jgomez Date 2012-04-16 Time 14:05 Rev Time 0.00
Received By jgomez Date 2012-04-16 Time 14:04 Sent To  
Notes
2012-04-16 14:07:37BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- NEED TAS 105 TEST AS REQUIRED BY GENERAL LIMITATION
 #5 ON STEEL DECK NOA 11-0601.08

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2012-04-13 Cont ID  
Sent By jgomez Date 2012-04-13 Time 14:50 Rev Time 0.00
Received By jgomez Date 2012-04-13 Time 14:50 Sent To  
Notes
2012-04-13 14:51:14GOOD MORNING JASON,
 THE RAS 117 CALCULATIONS ARE OK. PLEASE PROVIDE 2
 COPIES WITH ORIGINAL SEAL AND SIGNATURE. PLEASE PROVIDE
 2 COPIES OF NOA. PLEASE PROVIDE FASTENER PULL OUT TEST
 REPORT TAS 105 AS REQUIRED BY GENERAL LIMITATION #5 ON
 LAST PAGE OF NOA (THIS IS REQUIRED BECAUSE IF PULL OUT
 RESISTANCE IS LESS THAN THE INDICATED VALUE, THEN IT
 WILL NOT BE ACCEPTABLE).
 REGARDING THE 208FR SPECS I SUGGEST YOU TO CONTACT
 TAMKO. PLEASE NOTICE THAT PAGE 8 OF THE NOA CALLS FOR
 BASE INSULATION LAYER MINIMUM 1.5" THICK AND TOP
 INSULATION LAYER MINIMUM 1/2" THICK. REGARDING THE
 NUMBER OF PLY SHEETS THE NOA SAYS ONE OR MORE PLIES.
 THIS IS WHAT I WILL ASK TAMKO FOR CLARIFICATION.
 PLEASE CONTACT ME IF YOU HAVE ANY OTHER QUESTION,
 SINCERELY,
  
  
  
 JULIO C. GOMEZ
 CITY OF WEST PALM BEACH
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2012-04-12 Cont ID  
Sent By jgomez Date 2012-04-12 Time 12:45 Rev Time 0.00
Received By jgomez Date 2012-04-12 Time 12:44 Sent To  
Notes
2012-04-12 12:47:59RE-ROOF BUILDING REVIEW 5TH CHECKLIST:
 2010 FBC.
  
 ***NOTE: E-MAIL COPY OF THIS COMMENTS WERE SENT TO
 ROBERT BROWN (ASSISTANT BUILDING OFFICIAL) FOR HIS
 REVIEW. THIS IS THE 5TH TIME THAT THE RAS 117
 CALCULATIONS WERE REQUESTED.
  
 1- ENGINEER TO PROVIDE RAS 117 CALCULATIONS AS REQUIRED
 BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA 11-0601.08
 SUBMITED FOR THE STEEL DECK.
 ENGINEER CALCULATIONS SUBMITTED ARE NOT THE REQUESTED
 RAS 117 CALCULATIONS. ENGINEER NEEDS TO GET FAMILIAR ON
 HOW THE RAS 117 CALCULATIONS ARE DONE. THEN, THE
 ENGINEER NEEDS TO REVIEW THE SELECTED APPROVED ASSEMBLY
 FROM THE PRODUCT APPROVAL FOR THE STEEL DECK. AND,
 THEN, DO THE RAS 117 CALCULATIONS.
 (NOTE: APPROVED ASSEMBLIES THAT ARE LIMITED BY GENERAL
 LIMITATION #9 CAN'T BE USED. SEE GENERAL LIMITATION #9
 ON LAST PAGE OF NOA SUBMITTED).
  
 2- ENGINEER TO TAKE INTO CONSIDERATION THAT ACCORDING
 TO SEC. 1609.4.3 THIS BUILDING IS LOCATED ON EXPOSURE
 "C" NOT "B". NEED TO REVISE THE DESIGN PRESSURES
 CALCULATIONS SUBMITTED AT THIS TIME WHEN DOING THE RAS
 117 CALCULATIONS.
  
 3- PLEASE SUBMIT 2 COPIES OF THE NOA FOR THE STEEL DECK
 ALONG WITH THE SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED. (DCA RULE 9N-3).
  
 4- A) ALL CALCULATIONS COMING FROM THE ENGINEER NEED
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 B) ENGINEER NEEDS TO PROVIDE ALL HIS INFORMATION ON THE
 CALCULATIONS AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES WHEN SUBMITTING CALCULATIONS FOR PUBLIC
 RECORDS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2012-04-06 Cont ID  
Sent By jgomez Date 2012-04-06 Time 15:23 Rev Time 0.00
Received By jgomez Date 2012-04-06 Time 15:22 Sent To  
Notes
2012-04-06 15:25:45RE-ROOF FOURTH BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- STEEL DECK NOA 11-0601.08 SUBMITTED: THE SELECTED
 APPROVED ASSEMBLY ON PAGE 6 AND 7 IS LIMITED BY GENERAL
 LIMITATION #9. THIS ASSEMBLY CAN'T BE USED BECAUSE
 LIMITATION #9 DOESN'T ALLOW NAIL ENHANCING AND THE
 DESIGN PRESSURES ARE TOO LOW TO MEET THE DESIGN
 PRESSURES OF FBC SEC. 1609. SEE GENERAL LIMITATION #9
 ON LAST PAGE OF NOA.
  
 2- NEED TO SPECIFY APPROVED ASSEMBLY WITH GENERAL
 LIMITATION #7 AND NEED SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7.
 ***NOTE: CALCULATIONS SUBMITTED FROM ECS FLORIDA LLC
 ARE NOT THE RAS 117 CALCULATIONS. ENGINEER FROM ECS
 FLORIDA NEEDS TO REVIEW SELECTED ASSEMBLY FROM NOA FOR
 STEEL DECKS AND THEN PROVIDE THE RAS 117 CALCULATIONS.
 COORDINATE WITH ITEM #1 ABOVE.
 ALSO, ENGINEER TO USE CURRENT CODE 2010 FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-03-29 Cont ID  
Sent By jgomez Date 2012-03-29 Time 16:57 Rev Time 0.00
Received By jgomez Date 2012-03-29 Time 16:57 Sent To  
Notes
2012-03-29 16:57:59RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- STEEL DECK NOA 11-0601.08 SUBMITTED: THE SELECTED
 APPROVED ASSEMBLY ON PAGE 6 AND 7 IS LIMITED BY GENERAL
 LIMITATION #9. THIS ASSEMBLY CAN'T BE USED BECAUSE
 LIMITATION #9 DOESN'T ALLOW NAIL ENHANCING AND THE
 DESIGN PRESSURES ARE TOO LOW TO MEET THE DESIGN
 PRESSURES OF FBC SEC. 1609.
  
 2- NEED ASSEMBLY WITH GENERAL LIMITATION #7 AND NEED
 SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-03-26 Cont ID  
Sent By jgomez Date 2012-03-26 Time 10:58 Rev Time 0.00
Received By jgomez Date 2012-03-26 Time 10:57 Sent To  
Notes
2012-03-26 11:08:14RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- STEEL DECK NOA 11-0601.08 SUBMITTED: THE SELECTED
 APPROVED ASSEMBLY ON PAGE 6 AND 7 IS LIMITED BY GENERAL
 LIMITATION #9. THIS ASSEMBLY CAN'T BE USED BECAUSE
 LIMITATION #9 DOESN'T ALLOW NAIL ENHANCING AND THE
 DESIGN PRESSURES ARE TOO LOW TO MEET THE DESIGN
 PRESSURES OF FBC SEC. 1609.
  
 2- NEED ASSEMBLY WITH GENERAL LIMITATION #7 AND NEED
 SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7.
  
 3- REVISE THE RAS 117 CALCULATIONS SUBMITTED FOR THE
 WOOD DECK. NEED TO REVISE THE DESIGN PRESSURES AS
 CALCULATED BY FBC 2010 WHICH IS THE CURRENT CODE THAT
 WENT INTO EFFECT ON MARCH 15 2012.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-22 Cont ID  
Sent By jgomez Date 2012-03-22 Time 18:53 Rev Time 0.00
Received By jgomez Date 2012-03-22 Time 18:44 Sent To  
Notes
2012-03-22 18:54:43RE-ROOF BUILDING REVIEW COMMENTS
 2010 FBC.
  
 1- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA 09-0820.11 SUBMITTED.
 NEED NAIL ENHANCING TO MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. 1609 FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2012-04-16 Cont ID  
Sent By jgomez Date 2012-04-16 Time 14:05 Rev Time 0.00
Received By jgomez Date 2012-04-16 Time 14:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2012-04-13 Cont ID  
Sent By jgomez Date 2012-04-13 Time 14:50 Rev Time 0.00
Received By jgomez Date 2012-04-13 Time 14:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2012-04-12 Cont ID  
Sent By jgomez Date 2012-04-12 Time 12:44 Rev Time 0.00
Received By jgomez Date 2012-04-12 Time 12:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-04-06 Cont ID  
Sent By jgomez Date 2012-04-06 Time 15:22 Rev Time 0.00
Received By jgomez Date 2012-04-06 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-03-29 Cont ID  
Sent By jgomez Date 2012-03-29 Time 16:56 Rev Time 0.00
Received By jgomez Date 2012-03-29 Time 16:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-26 Cont ID  
Sent By jgomez Date 2012-03-26 Time 10:58 Rev Time 0.00
Received By jgomez Date 2012-03-26 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-22 Cont ID  
Sent By jgomez Date 2012-03-22 Time 18:44 Rev Time 0.00
Received By jgomez Date 2012-03-22 Time 18:44 Sent To  
Notes
***NONE***