Plan Review Details - Permit 12030519
Plan Review Stops For Permit 12030519
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-04-05 Cont ID  
Sent By ddaniels Date 2012-04-05 Time 10:39 Rev Time 0.00
Received By ddaniels Date 2012-04-05 Time 10:25 Sent To  
Notes
2012-04-05 10:34:37 
  
 1.) A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG
 THE EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A
 MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE
 DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR
 AND SHALL CLEARLY IDENTIFY THE HAZARD PROTECTED PER FBC
 904.11.1.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2012-03-27 Time   Rev Time  
Received By   Date 2012-03-27 Time   Sent To  
Notes
2012-03-27 14:50:4103/27/12
 PERMIT #12030519
  
 PLANS REVIEWED BY FIRE (RF)
  
 * (FAILED) SEE MACHANICAL NOTES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-05 Cont ID  
Sent By ddaniels Date 2012-04-05 Time 10:39 Rev Time 0.00
Received By ddaniels Date 2012-03-30 Time 11:30 Sent To  
Notes
2012-03-30 11:31:03TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-27 Cont ID  
Sent By shill Date 2012-03-27 Time 15:51 Rev Time 0.00
Received By shill Date 2012-03-21 Time 14:06 Sent To  
Notes
2012-03-21 14:06:33SENT TO MECHANICAL BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-04-04 Cont ID  
Sent By hmoser Date 2012-04-04 Time 13:36 Rev Time 0.00
Received By hmoser Date 2012-04-04 Time 13:36 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-03-26 Cont ID  
Sent By hmoser Date 2012-03-26 Time 14:05 Rev Time 0.00
Received By hmoser Date 2012-03-26 Time 12:38 Sent To FIRE
Notes
2012-03-26 14:05:33PLANS DENIED
 1) REFER TO SECTION 506.3.12.3 TERMINATION 2007 FBC (M)
 2) REFER TO SECTION 507.2.1.1 OPERATION 2007 FBC (M)
 3) REFER TO SECTION 507.16.1 CAPTURE AND CONTAINMENT
 2007 FBC (M)
 4) REFER TO SECTION 304.10 GUARDS IF DUCT IS LESS THEN
 10 FT. FROM ROOF EDGE
 2007 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  