Plan Review Details - Permit 12030498
Plan Review Stops For Permit 12030498
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-06-21 Cont ID  
Sent By jgomez Date 2012-06-19 Time 16:31 Rev Time 0.00
Received By jgomez Date 2012-06-19 Time 16:31 Sent To  
Notes
2012-06-19 17:05:29RESIDENTIAL (R3) RENOVATION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS.
 2010 FBC.
  
 1- ARCHITECT TO COORDINATE PLANS WITH THE REVISED
 ENERGY CALCULATIONS. NEED TO MEET THE MINIMUM
 REQUIREMENTS OF TABLE 402.1.1 OF 2010 FBC-ENERGY
 CONSERVATION. SEE COMMENTS ON ITEM 2 BELOW AND
 COORDINATE ACCORDINGLY.
  
 2- ENERGY CALCULATIONS SUBMITTED (SEC. 107.2.1 CITY
 AMENDMENTS TO FBC):
  
 A) NEED TO MEET ALL THE MINIMUM REQUIREMENTS OF TABLE
 402.1.1. REVISE THE WINDOWS AND DOORS FENESTRATION,
 CEILING INSULATION, WALL INSULATION, ETC. AND
 COORDINATE WITH REVISED ARCHITECT'S PLANS. SEE ITEM #1
 ABOVE.
  
 B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. SPECIFY BUILDER NAME. COORDINATE WITH OWNER. AND,
 REVISE THE JURISDICTION NO. THIS IS JURISDICTION 604700
 NOT 661200.
  
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 D) REVISE DOOR TYPE ON SHEET 3 OF 5. PRODUCT APPROVAL
 SUBMITTED FOR THE DOORS SHOW DOORS WITH MORE THAN 1/3
 OF GLAZING ON THE DOOR. REVISE AS REQUIRED BY SEC.
 405.5.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 E) TAKING CEILING FAN CREDIT ON ITEM #15. ARCHITECT'S
 PLANS DON'T SHOW CEILING FAN. COORDINATE/REVISE AS
 REQUIRED.
  
 F) THERE IS NOT KITCHEN ON THIS BUILDING. REVISE
 INFORMATION ON SHEET 2 OF 5.
  
 G) REVISE AREAS SHOWN ON THE WINDOWS ON SHEET 3 OF 5 TO
 MATCH FLOOR PLANS AND ELEVATIONS SHOWN BY THE
 ARCHITECT.
  
 H) SHEET 4 OF 5 SAYS NO MECHANICAL VENTILATION.
 COORDINATE WITH ARCHITECT'S PLANS AND REVISE AS
 REQUIRED.
  
 3- ARCHITECT TO REVISE ICYNENE INSULATION
 SPECIFICATIONS WALLS SECTIONS. ICYNENE IS AN OPEN CELL
 FOAM NOT CLOSED CELL. ALSO, COORDINATE WITH THE ENERGY
 CALCULATIONS AND THICKNESS REQUIRED TO MEET THE MINIMUM
 INSULATION REQUIRED BY TABLE 402.1.1.
  
 ***NOTE: PLEASE PROVIDE RESPONSE IN WRITING TO EXPEDITE
 THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-20 Cont ID  
Sent By jgomez Date 2012-04-20 Time 12:41 Rev Time 0.00
Received By jgomez Date 2012-04-20 Time 08:50 Sent To  
Notes
2012-04-20 13:14:50RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE.
  
 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) METAL ROOFING. FLORIDA PRODUCT APPROVAL FL12114-
 SUBMITTED IS FOR 2007 CODE VERSION. NEED TO PROVIDE
 PRODUCT APPROVAL FOR 2010 CODE VERSION.
  
 B) DOUBLE HUNG WINDOW. FLORIDA PRODUCT APPROVAL
 FL4765-R3 SUBMITTED IS FOR 2007 CODE VERSION. NEED 2010
 CODE VERSION.
  
 C) EXTERIOR INSWING DOOR AS SHOWN ON PLANS FOR NEW
 BATHROOM.
  
 D) EXTERIOR OUTSWING DOOR. FLORIDA PRODUCT APPROVAL
 FL4809-R6 SUBMITTED IS FOR 2007 CODE VERSION. NEED 2010
 CODE VERSION.
 ***NOTE: NOA 11-1026.04 SUBMITTED IS OK. YOU MAY SUBMIT
 NOA ALONE.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 4- ENERGY CALCULATIONS SUBMITTED:
 A) CODE IN EFFECT IS THE 2010 FBC. NEED TO USE FORM
 405. REVISE AS REQUIRED. SEE SEC. 405.4.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 B) REVISE ITEM #8(A). BUILDING IS NOT ON SLAB ON GRADE.
 SEE PLANS AND REVISE AS REQUIRED.
  
 C) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. SPECIFY BUILDER NAME. COORDINATE WITH OWNER. AND,
 REVISE THE JURISDICTION NO. THIS IS JURISDICTION 604700
 NOT 661200.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 E) REVISE DOOR TYPE ON SHEET 3 OF 5. PRODUCT APPROVAL
 SUBMITTED FOR THE DOORS SHOW DOORS WITH MORE THAN 1/3
 OF GLAZING ON THE DOOR. REVISE AS REQUIRED BY SEC.
 405.5.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 F) THERE IS NOT GARAGE. REVISE INFORMATION ON SHEET 3
 OF 5 SUBMITTED.
  
 5- SPECIFY LANDING ON EXTERIOR SIDE OF DOOR AT THE
 BATHROOM AS REQUIRED BY SEC. R311.3.
  
 6- PROVIDE COMPLETE MANUFACTURER SPECIFICATIONS FOR
 TYPE OF FOAM INSULATION SPECIFIED ON PLANS TO VERIFY
 COMPLIANCE WITH SEC. R316. . ARCHITECT TO REVIEW SPECS
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 7- DRAWING S-1 IS MISSING THE ENGINEER'S SEAL AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 8- SHEET C-1.0:
 A) REVISE ALL THE GENERAL NOTES THAT REFERENCE THE 2007
 FBC. CURRENT CODE IS THE 2010 FLORIDA RESIDENTIAL CODE
 AND 2010 EXISTING BUILDING CODE.
  
 B) THIS IS NOT ALTERATION TYPE 2. SCOPE OF WORK IS MORE
 THAN 50%. THIS IS ALT. TYPE 3. SEE CHAPTER 4 OF 2010
 EXISTING BUILDING CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-03-21 Cont ID  
Sent By rlecky Date 2012-03-21 Time 14:08 Rev Time 0.00
Received By rlecky Date 2012-03-21 Time 13:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-20 Cont ID  
Sent By jgomez Date 2012-06-20 Time 17:24 Rev Time 0.00
Received By jgomez Date 2012-06-15 Time 09:32 Sent To  
Notes
2012-06-15 09:33:16TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-02 Cont ID  
Sent By shill Date 2012-05-02 Time 08:10 Rev Time 0.00
Received By shill Date 2012-03-20 Time 13:23 Sent To  
Notes
2012-03-20 13:24:05INCOMING SENT TO R06 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2012-04-25 Cont ID  
Sent By jgomez Date 2012-04-20 Time 11:01 Rev Time 0.00
Received By jgomez Date 2012-04-20 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-06-20 Cont ID  
Sent By jgomez Date 2012-06-20 Time 17:22 Rev Time 0.00
Received By jgomez Date 2012-06-20 Time 17:22 Sent To  
Notes
2012-06-20 17:24:43RESIDENTIAL (R3) SECOND MECHANICAL REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE.
  
 1- PROVIDE A/C EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY SEC. 403.6 OF THE 2010 FLORIDA BUILDING
 CODE-ENERGY CONSERVATION.
  
 ***NONE SUBMITTED....
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-04-20 Cont ID  
Sent By jgomez Date 2012-04-20 Time 13:52 Rev Time 0.00
Received By jgomez Date 2012-04-20 Time 13:52 Sent To  
Notes
2012-04-20 14:03:11RESIDENTIAL (R3) MECHANICAL REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE.
  
 1- PROVIDE A/C EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY SEC. 403.6 OF THE 2010 FLORIDA BUILDING
 CODE-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-04-20 Cont ID  
Sent By jgomez Date 2012-04-20 Time 11:25 Rev Time 0.00
Received By jgomez Date 2012-04-20 Time 11:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-05-01 Cont ID  
Sent By lfranco Date 2012-05-01 Time 17:22 Rev Time 0.00
Received By lfranco Date 2012-04-30 Time 12:22 Sent To I
Notes
2012-05-01 17:26:31PLANNING: **** PASSED PER PERMIT 10120354, WITH
 PROVISO: UNIT IS FOR GUEST/HOME OWNER USE ONLY, NOT FOR
 RENTAL PURPOSES. THE EXISTING CONFIGURATION OF THE
 BUILDING SHALL REMAIN AS IS AND CANNOT EXPAND. IF AN
 EXPANSION OF THE UNIT IS APPLIED FOR IN THE FUTURE, IT
 SHALL MEET THE MINIMUM FIVE (5) FOOT SIDE SETBACK. PER
 ANGELLA VANN (PLANNING AND ZONING ADMINISTRATOR). *****
  
  
  
  
  
  
2012-04-23 11:11:33PERMIT NOT IN BIN