Plan Review Details - Permit 12030398
Plan Review Stops For Permit 12030398
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-23 Cont ID  
Sent By rmcdouga Date 2012-03-23 Time 15:01 Rev Time 0.00
Received By rmcdouga Date 2012-03-16 Time 10:49 Sent To  
Notes
2012-03-16 10:36:35INCOMING SENT TO ZONING BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-03-27 Cont ID  
Sent By rmcdouga Date 2012-03-27 Time 08:37 Rev Time 0.00
Received By rmcdouga Date 2012-03-27 Time 08:36 Sent To  
Notes
2012-03-27 08:38:10DESIGNER CAME IN AND CORRECTED THE PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-03-23 Cont ID  
Sent By rmcdouga Date 2012-03-23 Time 15:01 Rev Time 0.00
Received By rmcdouga Date 2012-03-23 Time 14:28 Sent To  
Notes
2012-03-23 15:00:262007 FBC W/2009 REVISIONS
  
 MECHANICAL REVISION DENIED
  
 1) BALANCED RETURN AIR IS REQUIRED BY FBCR M1602.4. THE
 FIRST FLOOR GUEST BEDROOM AND THE SECOND FLOOR OFFICE
 REQUIRE RETURNS.
  
 2) AIR HANDLERS LOCATED IN ATTICS SHALL BE LOCATED
 WITHIN 6 FEET OF AN ACCESS OPENING AND COMPLY WITH FBCR
 M1305.1.3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2012-03-21 Cont ID  
Sent By eschneid Date 2012-03-21 Time 09:34 Rev Time 0.25
Received By eschneid Date 2012-03-20 Time 16:25 Sent To M
Notes
2012-03-20 16:25:39GIVEN TO ES