Plan Review Details - Permit 12030394
Plan Review Stops For Permit 12030394
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-05-01 Cont ID  
Sent By jwitmer Date 2012-05-01 Time 10:59 Rev Time 0.00
Received By jwitmer Date 2012-05-01 Time 10:59 Sent To  
Notes
2012-05-01 12:07:01BUILDING PROVISO:
  
 1) SHEET A-1 & LS2 RED-LINED DRAWINGS FOR THE DOOR
 SCHEDULE, DOOR (F) TO BE A 4'-0" WIDE EGRESS DOOR. 2007
 FBC-B 1008.1.1 ALLOWS SIDE SWING EGRESS DOORS TO BE A
 MAXIMUM OF 48", NOT 4'-6". 46"/0.2= 230 OCCUPANT LOAD
 THROUGH THE DOOR, OCCUPANT LOAD FOR BOTH STAIRWELLS ARE
 LESS THAN THE 230.
  
 2) SHEET LS-1 REDLINED- ATRIUM WALL MISSING THE 1 HOUR
 FIRE RATING DESIGNATION WITHIN THE REVISION BUBBLE.
 2007 FBC-B 404.5.
  
 3) 2007 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-04-12 Cont ID  
Sent By jwitmer Date 2012-04-12 Time 09:36 Rev Time 0.00
Received By jwitmer Date 2012-04-12 Time 09:36 Sent To  
Notes
2012-04-12 09:55:22BUILDING PLAN REVIEW
 PERMIT: 12030394
 ADD: 1889 PALM BEACH LAKES
 CONT: P & T CONSRUCTION, INC
 TEL: (561)324-8055
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
 APRIL 12/2012
  
 1) 2ND REQUEST, SHEET LS-1 & A-1 INDICATES THIS
 BUILDING AS A BUILDING TYPE IV PROTECTED, THIS
 NOMENCLATURE INDICATES THIS IS A CONSTRUCTED FROM HEAVY
 TIMBER. I BELIEVE THE DESIGNER IS USING
 BUILDING TYPES FROM THE 2001 FBC-B. THE 2001 FBC-B IV
 PROTECTED IS DEFINED UNDER THE 2007 FBC-B AS A TYPE IIA
 1 HOUR PROTECTED. THE PLANS ALSO INDICATE THIS
 STRUCTURE TO BE
 FULLY SPRINKLERED. PLEASE CORRECT TO THE 2007 FBC-B.
 THE DESIGNER DOES NOT STATE ON THIS SHEET TO WHICH CODE
 THE PLANS ARE DESIGNED. FIGURE 600 2007 FBC-B
 COMMENTARY.
  
 2) 2ND REQUEST, SEMI-COMPLIED. SEE ISST GRADE DOORS
 BACK TO BACK. 1028.3 DOORS THAT SWING INTO AN EXIT
 ACCESS CORRIDOR SHALL BE RECESSED TO PREVENT
 INTERFERENCE WITH CORRIDOR TRAFFIC; ANY DOORS NOT
 RECESSED SHALL OPEN 180 DEGREES (3.1 RAD) TO STOP
 AGAINST THE WALL. DOORS IN ANY POSITION SHALL NOT
 REDUCE THE REQUIRED CORRIDOR WIDTH BY MORE THAN
 ONE-HALF. NOTE NEITHER DOORS NOR CLASSROOMS ARE
 NUMBERED FOR IDENTIFYING PURPOSES, THESE CODE
 VIOLATIONS OCCUR BOTH IN THE DESIGN FIRST FLOOR AND
 SECOND FLOOR. MANY DOORS ARE CONFIGURERED IN THE CORNER
 OF CLASSROOMS BACK TO BACK SO THEY WOULD NOT BE ABLE TO
 SWING 180 DEGREES 6'-0" CORRIDORS WITH NO ALCOVES
 PROVIDED.
  
 3)2ND REQUEST. CHANGE OF OCCUPANCY, MIXED USE/ TO
 EDUCATIONAL 2007/09 EXISTING BLDG CODE 906.1
 ACCESSIBILITY. ACCESSIBILITY IN PORTIONS OF BUILDINGS
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING . 2007/09 FBC-B 11-4.1.3(5) PLEASE PROVIDE
 VERTICAL ACCESSIBILITY TO THE SECOND FLOOR. THE PLANS
 DO NOT INDICATE THE ELEVATOR OPENINGS, CURRENTLY IT
 APPEARS TO BE JUST A SHAFT.
  
 4) SEMI-COMPLIED. 1ST FLOOR PLEASE REVIEW ROOMS WITH
 660 SQ FT /33 TOTAL OCC LOAD, 2ND FLOOR ROOMS WITH 671
 SQ FT / 34 TOTAL OCC LOAD.
 DOOR SCHEDULE ON LS-2 INDICATES THE NEW ATRIUM DOORS AS
 EXISTING, NOT SHOWN ON THE EARLIER SET OF PLANS, PLEASE
 EXPLAIN THE COMMENT EXISTING?
 THE SECOND ISSUE WITH THE DOOR SCHEDULE ALL DOORS
 WITHIN THE DOOR SCHEDULE ARE INDICATED AS A 1INCH DOOR.
 PROVIDE DOCUMENTATION FOR ONE INCHE FIRE RATED DOORS.
 PLEASE PROVIDE A LIFE SAFETY PLAN PROVIDING EXITING,
 EXIT SIGNAGE, EMERGENCY LIGHTING OCCUPANT LOADS ROOMS,
 CORRIDORS, STAIRS & EXIT DOOR WAYS. ADMINISTATIVE CODE
 106.3.5.1.1
 THE CURRENT LS SHEET DOES NOT PROVIDE ENOUGH
 INFORMATION TO REVIEW FOR CODE COMPLIANCE.
 EXIST BLDG CODE 912.4.3 EGRESS CAPACITY. EGRESS
 CAPACITY SHALL MEET OR EXCEED THE OCCUPANT LOAD AS
 SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING , FOR
 THE NEW OCCUPANCY.
 EXIST BLDG CODE. 805.2 MEANS OF EGRESS LIGHTING. MEANS
 OF EGRESS FROM THE HIGHEST WORK AREA FLOOR TO THE FLOOR
 OF EXIT DISCHARGE SHALL BE PROVIDED WITH ARTIFICIAL
 LIGHTING WITHIN THE EXIT ENCLOSURE IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING
 .
  
 EXIST BLDG CODE 805.3 EXIT SIGNS. MEANS OF EGRESS FROM
 THE HIGHEST WORK AREA FLOOR TO THE FLOOR OF EXIT
 DISCHARGE SHALL BE PROVIDED WITH EXIT SIGNS IN
 ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING .
  
 5) SEMI-COMPLIED. LIFE SAFETY SHEETS DO NOT INDICATE
 FIRE NOR SMOKE RATED WALLS. THE 1ST FLOOR AND 2ND FLOOR
 A SHEETS INDICATE THE ATRIUM WALLS AS 1 HOUR RATED,
 MECHANICAL ARE MISSING FIRE DAMPERS AND THE 1ST AND 2ND
 FLOOR CORRIDOR WALLS ARE INDICATED AS SMOKE PARTITIONS
 BUT ARE MISSING THE FIRE SMOKE DAMPERS. SEE 2007/09
 FBC-B SECTION 716.
  
 2007/09 EXISTING BUILDING CODE 902.1 (2) ATRIUMS.
 PLEASE PROVIDE DOCUMENTATION FOR CODE COMPLIANCE WITH
 THE FOLLOWING :
  
 2007/09 FBC-B 404.5 ENCLOSURE OF ATRIUMS. ATRIUM SPACES
 SHALL BE SEPARATED FROM ADJACENT SPACES BY A 1-HOUR
 FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH SECTION 706
 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH.
 EXCEPTIONS:
 1. A GLASS WALL FORMING A SMOKE PARTITION WHERE
 AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR
 LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE
 ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM
 SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND
 305 MM) AWAY FROM THE GLASS AND DESIGNED SO THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM WITHOUT OBSTRUCTION. THE GLASS
 SHALL BE INSTALLED IN A GASKETED FRAME SO THAT THE
 FRAMING SYSTEM DEFLECTS WITHOUT BREAKING (LOADING) THE
 GLASS BEFORE THE SPRINKLER SYSTEM OPERATES.
 2. A GLASS-BLOCK WALL ASSEMBLY IN ACCORDANCE WITH
 SECTION 2110 AND HAVING A 3/4-HOUR FIRE PROTECTION
 RATING.
 NOTE NONE OF THE CORRIDOR WALLS ARE INDICATED AS 1 HOUR
 RATED WALLS ALTHOUGH ALL OF THE DOORS INDICATE AS 1
 HOUR FIRE RATING.
 ----------------------
 NOTE!!!!! 2007/09 EXISTING BUILDING CODE 912.1.1
 COMPLIANCE WITH CHAPTER 8. ALSSO SEE 801.2 IN ADDITION
 TO THE PROVISIONS OF THIS CHAPTER, WORK SHALL COMPLY
 WITH ALL OF THE REQUIREMENTS OF CHAPTERS 6 &7.
  
 6)SEMI-COMPLIED SEE COMMENT # 5. PROVIDE INFORMATION
 FOR MONUMENTAL STAIR, IS IT PART OF THE REQUIRED MEANS
 OF EGRESS?
 2007 EXIST BLDG CODE 703.2.3 SUPPLEMENTAL STAIRWAY
 ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON ANY
 FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS
 THAT ARE PART OF THE MEANS OF EGRESS SERVING THE WORK
 AREA SHALL, AT A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT
 CONSTRUCTION ON THE HIGHEST WORK AREA FLOOR AND ALL
 FLOORS BELOW.
 EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY
 THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE
 PREVENTION CODE.
 2007/09 FBC-B 707.2 SHAFT ENCLOSURE NOT REQUIRED SEE
 EXCEPTION # 2. (DRAFT CURTAIN).
  
 7) 2ND REQUEST. PLEASE SEE EXIT ACCESS CORRIDOR THAT
 LEEDS PAST THE PANTRY THIS CORRIDOR SHOULD BE A MINIMUM
 OF 72" FBC-B 1017.2 EX # 4 .WITH OCCUPANT LOADS GREATER
 THAN 100 THIS CORRIDOR WILL NEED TO BE A MINIMUM OF 72"
 WIDE.
  
 8)2ND REQUEST. PLEASE SEE 2ND FLOOR PLAN THE CORRIDOR
 THAT LEEDS TO THE SIDE EXIT, IT APPEARS THE OCCUPANT
 LOAD FOR THE 2ND FLOOR IS OVER 100 REQUIRING THIS
 CORRIDOR TO BE 72 INCHES WIDE.
 FBC-B 1017.2 EX # 4.
  
 9)COMPLIED.
  
 10) 2ND REQUEST. EXIST BLDG CODE 912.2.1 PLEASE PROVIDE
 FIR SPRINKLER PLAN BASED ON THE NEW WALL CONFIGURATION
 & OCCUPANCY.WEST PALM BEACH ADMINISTRATIVE CODE
 106.3.5.1.1(5).
  
 11)2ND REQUEST. EIXST BLDG CODE 912.2.2 FIRE ALARM AND
 DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY
 CLASSIFICATION OCCURS THAT REQUIRES A FIRE ALARM AND
 DETECTION SYSTEM TO BE PROVIDED BASED ON THE NEW
 OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING , SUCH SYSTEM SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS. EXISTING ALARM NOTIFICATION APPLIANCES SHALL BE
 AUTOMATICALLY ACTIVATED THROUGHOUT THE BUILDING. WHERE
 THE BUILDING IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM,
 ALARM NOTIFICATION APPLIANCES SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
  
 12) 2ND REQUEST. NOT SHOWN ON PLANS:
 912.4.4 HANDRAILS. EXISTING STAIRWAYS SHALL COMPLY WITH
 THE HANDRAIL REQUIREMENTS OF SECTION 705.9 IN THE AREA
 OF THE CHANGE OF OCCUPANCY CLASSIFICATION.
  
 13) 2ND REQUEST. NOT SHOWN ON PLAN. 912.4.5 GUARDS.
 EXISTING GUARDS SHALL COMPLY WITH THE REQUIREMENTS IN
 SECTION 705.10 IN THE AREA OF THE CHANGE OF OCCUPANCY
 CLASSIFICATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-22 Cont ID  
Sent By jwitmer Date 2012-03-22 Time 08:53 Rev Time 0.00
Received By jwitmer Date 2012-03-22 Time 08:39 Sent To  
Notes
2012-03-22 09:50:34BUILDING PLAN REVIEW
 PERMIT: 12030394
 ADD: 1889 PALM BEACH LAKES
 CONT: P & T CONSRUCTION, INC
 TEL: (561)324-8055
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET SP-1 & A-1 INDICATES THIS BUILDING AS A
 BUILDING TYPE IV PROTECTED, THIS NOMENCLATURE INDICATES
 THIS IS A CONSTRUCTED FROM HEAVY TIMBER. I BELIEVE THE
 DESIGNER IS USING
 BUILDING TYPES FROM THE 2001 FBC-B. THE 2001 FBC-B IV
 PROTECTED IS DEFINED UNDER THE 2007 FBC-B AS A TYPE IIA
 1 HOUR PROTECTED. THE PLANS ALSO INDICATE THIS
 STRUCTURE TO BE
 FULLY SPRINKLERED. PLEASE CORRECT TO THE 2007 FBC-B.
 THE DESIGNER DOES NOT STATE ON THIS SHEET TO WHICH CODE
 THE PLANS ARE DESIGNED. FIGURE 600 2007 FBC-B
 COMMENTARY.
  
 2) 1028.3 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR
 SHALL BE RECESSED TO PREVENT INTERFERENCE WITH CORRIDOR
 TRAFFIC; ANY DOORS NOT RECESSED SHALL OPEN 180 DEGREES
 (3.1 RAD) TO STOP AGAINST THE WALL. DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED CORRIDOR WIDTH
 BY MORE THAN ONE-HALF. NOTE NEITHER DOORS NOR
 CLASSROOMS ARE NUMBERED FOR IDENTIFYING PURPOSES, THESE
 CODE VIOLATIONS OCCUR BOTH IN THE DESIGN FIRST FLOOR
 AND SECOND FLOOR. MANY DOORS ARE CONFIGURERED IN THE
 CORNER OF CLASSROOMS BACK TO BACK SO THEY WOULD NOT BE
 ABLE TO SWING 180 DEGREES 6'-0" CORRIDORS WITH NO
 ALCOVES PROVIDED.
  
 3) CHANGE OF OCCUPANCY, MIXED USE/ TO EDUCATIONAL
 2007/09 EXISTING BLDG CODE 906.1 ACCESSIBILITY.
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE, BUILDING .
 2007/09 FBC-B 11-4.1.3(5) PLEASE PROVIDE VERTICAL
 ACCESSIBILITY TO THE SECOND FLOOR. THE PLANS DO NOT
 INDICATE THE ELEVATOR OPENINGS, CURRENTLY IT APPEARS TO
 BE JUST A SHAFT.
  
 4) PLEASE PROVIDE A LIFE SAFETY PLAN PROVIDING EXITING,
 EXIT SIGNAGE, EMERGENCY LIGHTING OCCUPANT LOADS ROOMS,
 CORRIDORS, STAIRS & EXIT DOOR WAYS. ADMINISTATIVE CODE
 106.3.5.1.1
 THE CURRENT LS SHEET DOES NOT PROVIDE ENOUGH
 INFORMATION TO REVIEW FOR CODE COMPLIANCE.
 EXIST BLDG CODE 912.4.3 EGRESS CAPACITY. EGRESS
 CAPACITY SHALL MEET OR EXCEED THE OCCUPANT LOAD AS
 SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING , FOR
 THE NEW OCCUPANCY.
 EXIST BLDG CODE. 805.2 MEANS OF EGRESS LIGHTING. MEANS
 OF EGRESS FROM THE HIGHEST WORK AREA FLOOR TO THE FLOOR
 OF EXIT DISCHARGE SHALL BE PROVIDED WITH ARTIFICIAL
 LIGHTING WITHIN THE EXIT ENCLOSURE IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING
 .
  
 EXIST BLDG CODE 805.3 EXIT SIGNS. MEANS OF EGRESS FROM
 THE HIGHEST WORK AREA FLOOR TO THE FLOOR OF EXIT
 DISCHARGE SHALL BE PROVIDED WITH EXIT SIGNS IN
 ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING .
  
 5) 2007/09 EXISTING BUILDING CODE 902.1 (2) ATRIUMS.
 PLEASE PROVIDE DOCUMENTATION FOR CODE COMPLIANCE WITH
 THE FOLLOWING :
  
 2007/09 FBC-B 404.5 ENCLOSURE OF ATRIUMS. ATRIUM SPACES
 SHALL BE SEPARATED FROM ADJACENT SPACES BY A 1-HOUR
 FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH SECTION 706
 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH.
 EXCEPTIONS:
 1. A GLASS WALL FORMING A SMOKE PARTITION WHERE
 AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR
 LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE
 ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM
 SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND
 305 MM) AWAY FROM THE GLASS AND DESIGNED SO THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM WITHOUT OBSTRUCTION. THE GLASS
 SHALL BE INSTALLED IN A GASKETED FRAME SO THAT THE
 FRAMING SYSTEM DEFLECTS WITHOUT BREAKING (LOADING) THE
 GLASS BEFORE THE SPRINKLER SYSTEM OPERATES.
 2. A GLASS-BLOCK WALL ASSEMBLY IN ACCORDANCE WITH
 SECTION 2110 AND HAVING A 3/4-HOUR FIRE PROTECTION
 RATING.
 NOTE NONE OF THE CORRIDOR WALLS ARE INDICATED AS 1 HOUR
 RATED WALLS ALTHOUGH ALL OF THE DOORS INDICATE AS 1
 HOUR FIRE RATING.
 ----------------------
 NOTE!!!!! 2007/09 EXISTING BUILDING CODE 912.1.1
 COMPLIANCE WITH CHAPTER 8. ALSSO SEE 801.2 IN ADDITION
 TO THE PROVISIONS OF THIS CHAPTER, WORK SHALL COMPLY
 WITH ALL OF THE REQUIREMENTS OF CHAPTERS 6 &7.
  
 6) PROVIDE INFORMATION FOR MONUMENTAL STAIR, IS IT PART
 OF THE REQUIRED MEANS OF EGRESS?
 2007 EXIST BLDG CODE 703.2.3 SUPPLEMENTAL STAIRWAY
 ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON ANY
 FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS
 THAT ARE PART OF THE MEANS OF EGRESS SERVING THE WORK
 AREA SHALL, AT A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT
 CONSTRUCTION ON THE HIGHEST WORK AREA FLOOR AND ALL
 FLOORS BELOW.
 EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY
 THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE
 PREVENTION CODE.
 2007/09 FBC-B 707.2 SHAFT ENCLOSURE NOT REQUIRED SEE
 EXCEPTION # 2. (DRAFT CURTAIN).
  
 7) PLEASE SEE EXIT ACCESS CORRIDOR THAT LEEDS PAST THE
 PANTRY THIS CORRIDOR SHOULD BE A MINIMUM OF 72" FBC-B
 1017.2 EX # 4.
  
 8) PLEASE SEE 2ND FLOOR PLAN THE CORRIDOR THAT LEEDS TO
 THE SIDE EXIT, IT APPEARS THE OCCUPANT LOAD FOR THE 2ND
 FLOOR IS OVER 100 REQUIRING THIS CORRIDOR TO BE 72
 INCHES WIDE.
 FBC-B 1017.2 EX # 4.
  
 9) 2ND FLOOR PLAN, DOORS THAT DO NOT HAVE THE 18"
 CLEARANCE ON THE LATCH SIDE OF THE DOOR, FBC-B
 11-4.13.6. SEE DOOR NEAR GRID LINE E-4, STAFF ROOM AND
 CLASSROOM LOCATED NEAR GRID LINE 12 HALF WAY BETWEEN A
 & B.
  
 10) EXIST BLDG CODE 912.2.1 PLEASE PROVIDE FIR
 SPRINKLER PLAN BASED ON THE NEW WALL CONFIGURATION &
 OCCUPANCY.
  
 11) EIXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION
 SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION
 OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM
 TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING ,
 SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE
 THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM
 NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY
 ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING
 IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM
 NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT
 THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL
 BE AUTOMATICALLY ACTIVATED.
  
 12) NOT SHOWN ON PLANS:
 912.4.4 HANDRAILS. EXISTING STAIRWAYS SHALL COMPLY WITH
 THE HANDRAIL REQUIREMENTS OF SECTION 705.9 IN THE AREA
 OF THE CHANGE OF OCCUPANCY CLASSIFICATION.
  
 912.4.5 GUARDS. EXISTING GUARDS SHALL COMPLY WITH THE
 REQUIREMENTS IN SECTION 705.10 IN THE AREA OF THE
 CHANGE OF OCCUPANCY CLASSIFICATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-04-30 Cont ID  
Sent By rlecky Date 2012-04-30 Time 09:04 Rev Time 0.00
Received By rlecky Date 2012-04-30 Time 08:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-04-23 Cont ID  
Sent By rlecky Date 2012-04-23 Time 11:56 Rev Time 0.00
Received By rlecky Date 2012-04-23 Time 10:00 Sent To  
Notes
2012-04-23 11:25:15PROVIDE DETAIL FOR FIRE PROTECTION OF 1 HOUR RATED
 WALLS WHICH ENCLOSE ELECTRICAL PANELBOARDS. NEC 300-21
  
 ROBERT LECKY, CBO
 PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-03-19 Cont ID  
Sent By rlecky Date 2012-03-19 Time 09:49 Rev Time 0.00
Received By rlecky Date 2012-03-19 Time 07:59 Sent To  
Notes
2012-03-19 10:05:1212030394
 1889 PALM BEACH LAKES BLVD
 NEW EDUCATIONAL FACILITY
  
 VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING
 RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND
 CURRENT THAT IS AVAILABLE. NEC 110.9
 PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS.
 NEC 110.26, 240.24, 408.17
 SHOW LOCATION OF ALL PANEL BOARDS. PROVIDE PANEL
 SCHEDULE SHOWING RATING, SIZE AND WIRING METHOD FOR THE
 NEW ELECTRICAL CIRCUITS. NEC 210.3
 SHOW SERVICE LOCATION ON THE PLAN. VERIFY THE EXISTING
 SERVICE RISER HAS ADEQUATE SIZE AND CLEARANCE. NEC
 230.24, 230.72
 SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5, NEC
 250.20
 VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND
 GROUPED IN ONE LOCATION. NEC 230.2, 230.71
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 230.31
 A FIRE ALARM SYSTEM IS REQUIRED FOR THIS FACILITY. A
 SEPARATE PERMIT WITH PLAN AND SHOP DRAWINGS IS
 REQUIRED. NFPA 101 15.3.4, FBC 907
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-05-04 Cont ID  
Sent By ddaniels Date 2012-05-03 Time 16:17 Rev Time 0.00
Received By ddaniels Date 2012-05-03 Time 16:17 Sent To  
Notes
2012-05-03 16:34:10 
 1889 PALM BEACH LAKES BOULEVARD
 PERMIT #12030394
 REVIEW COMMENTS - FIRE DEPARTMENT PLANS ***APPROVED***
  
  
 1.) PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
 2.) PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTIONS
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6722
  
2012-05-03 16:13:21DERRICK TOOK PLANS TO FIRE STATION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-04-18 Cont ID  
Sent By wjolin Date 2012-04-18 Time 14:11 Rev Time 0.00
Received By wjolin Date 2012-04-18 Time 13:49 Sent To  
Notes
2012-04-18 14:11:481889 PALM BEACH LAKES BOULEVARD
 PERMIT #12030394
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ****NO COMMENTS ADDRESSED FROM PREVIOUS PLAN
 REVIEW*****
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 PROVIDE ROOM NUMBERS (OR SIMILAR).
  
 INDICATE ALL DOORS TO BE EQUIPPED WITH PANIC OR FIRE
 EXIT HARDWARE.
  
 INDICATE THE AGE GROUPS THAT WILL BE UTILIZING THE
 SECOND FLOOR.
  
 INDICATE THE USE AND FIRE SEPARATION FOR THE
 MULTIPURPOSE ROOM. COMMON PATH OF TRAVEL EXCEEDS 20
 FEET AND SERVES MORE THAN 50 PERSONS. THE MULTIPURPOSE
 ROOM INDICATES AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER
 PERSON; HOWEVER, NO FURNITURE OR SEATING IS INDICATED
 JUSTIFYING LESS CONCENTRATED USE (7 SQ. FT. PER
 PERSON).
  
 THE LARGE FLOOR OPENING AND ORNAMENTAL STAIR LOCATED
 CENTRALLY IN THE BUILDING SHALL MEET THE REQUIREMENTS
 OF SECTION 8.6.8 (CONVENIENCE OPENINGS) OF NFPA 101
 FLORIDA EDITION.
  
 EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 NO INTERIOR FLOOR/WALL/CEILING FINISH INFORMATION
 PROVIDED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 ALL EXIT ACCESS CORRIDORS SHALL BE AT LEAST 6'-0" WIDE
 (CLEAR WIDTH).
  
 PROVIDE STAIR AND HANDRAIL DETAILS.
  
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, CORRIDOR, HALLWAY OR LANDING UNOBSTRUCTED AND
 SHALL PROJECT NOT MORE THAN 7-INCHES INTO THE REQUIRED
 WIDTH OF THE EGRESS PATH WHEN FULLY OPEN.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR THE INSTALLATION OR MODIFICATION OF THE
 FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 NO HVAC PLANS PROVIDED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-03 Cont ID  
Sent By wjolin Date 2012-04-03 Time 10:20 Rev Time 0.00
Received By wjolin Date 2012-04-03 Time 09:19 Sent To  
Notes
2012-04-03 10:20:291889 PALM BEACH LAKES BOULEVARD
 PERMIT #12030394
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 PROVIDE ROOM NUMBERS (OR SIMILAR).
  
 INDICATE ALL DOORS TO BE EQUIPPED WITH PANIC OR FIRE
 EXIT HARDWARE.
  
 INDICATE THE AGE GROUPS THAT WILL BE UTILIZING THE
 SECOND FLOOR.
  
 INDICATE THE USE AND FIRE SEPARATION FOR THE
 MULTIPURPOSE ROOM.
  
 THE LARGE FLOOR OPENING AND ORNAMENTAL STAIR LOCATED
 CENTRALLY IN THE BUILDING SHALL MEET THE REQUIREMENTS
 OF SECTION 8.6.8 (CONVENIENCE OPENINGS) OF NFPA 101
 FLORIDA EDITION.
  
 EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 NO INTERIOR FLOOR/WALL/CEILING FINISH INFORMATION
 PROVIDED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 ALL EXIT ACCESS CORRIDORS SHALL BE AT LEAST 6'-0" WIDE
 (CLEAR WIDTH).
  
 PROVIDE STAIR AND HANDRAIL DETAILS.
  
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, CORRIDOR, HALLWAY OR LANDING UNOBSTRUCTED AND
 SHALL PROJECT NOT MORE THAN 7-INCHES INTO THE REQUIRED
 WIDTH OF THE EGRESS PATH WHEN FULLY OPEN.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR THE INSTALLATION OR MODIFICATION OF THE
 FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 NO HVAC PLANS PROVIDED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status P Date 2012-05-04 Cont ID  
Sent By lmartine Date 2012-05-04 Time 14:36 Rev Time 0.00
Received By lmartine Date 2012-05-04 Time 14:36 Sent To  
Notes
2012-05-04 14:40:30ERROR THIS NOTE SHOULD HAVE BEEN FOR THE 'IMPACT FEE'
 STOP.
2012-05-04 14:38:57WILLIE SWOOPE SIGNED PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-05-04 Cont ID  
Sent By lmartine Date 2012-05-04 Time 14:33 Rev Time 0.00
Received By lmartine Date 2012-05-03 Time 16:10 Sent To  
Notes
2012-05-04 11:21:31IMPACT FEE CONFIRMATION ROUTED TO JW.
2012-05-03 16:12:00GAVE TO HAROLD
2012-05-03 16:11:44ADDRESS MECHANICAL COMMENTS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-05-04 Cont ID  
Sent By lmartine Date 2012-05-03 Time 14:33 Rev Time 0.00
Received By lmartine Date 2012-04-25 Time 14:57 Sent To  
Notes
2012-04-25 14:57:46C05

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-23 Cont ID  
Sent By rlecky Date 2012-04-23 Time 11:56 Rev Time 0.00
Received By rlecky Date 2012-04-06 Time 16:07 Sent To  
Notes
2012-04-06 16:07:42C05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-04 Cont ID  
Sent By lmartine Date 2012-04-04 Time 14:50 Rev Time 0.00
Received By lmartine Date 2012-03-14 Time 13:06 Sent To  
Notes
2012-03-15 13:07:05EXPEDITED
 B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2012-05-04 Cont ID  
Sent By lmartine Date 2012-05-04 Time 14:40 Rev Time 0.00
Received By lmartine Date 2012-05-04 Time 14:40 Sent To  
Notes
2012-05-04 14:52:24SEE PLANS

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-05-01 Cont ID  
Sent By jwitmer Date 2012-05-01 Time 12:07 Rev Time 0.00
Received By jwitmer Date 2012-05-01 Time 12:07 Sent To  
Notes
2012-05-01 12:08:00BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-04-23 Cont ID  
Sent By rlecky Date 2012-04-23 Time 12:00 Rev Time 0.00
Received By rlecky Date 2012-04-23 Time 12:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2012-05-04 Cont ID  
Sent By hmoser Date 2012-05-04 Time 09:54 Rev Time 0.00
Received By hmoser Date 2012-05-04 Time 09:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2012-05-02 Cont ID  
Sent By hmoser Date 2012-05-02 Time 10:45 Rev Time 0.00
Received By hmoser Date 2012-05-01 Time 14:13 Sent To  
Notes
2012-05-02 10:28:50PLAN DENIED
 1) MISSING FIRE DAMPER IN 34X18 DUCT AND 8" DUCT ON
 FIRST FLOOR.
 MISSING FIRE DAMPERS IN 36X18 DUCT AND 48X20 DUCT ON
 SECOND FLOOR.
 PER SECTION 607.5.1 2007 FBC (M)
 2) WHAT SECTION OF THE BUILDING DOES RTU # 3 COOL.
 3) ON SECOND FLOOR WHAT SIZE DUCT IS THE 36X16 AND
 48X20 TIEING IN TO.
 4) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER
 TABLE 403.3 FBC (M)
 5) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER
 CONTROLS.2007
 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-04-16 Cont ID  
Sent By hmoser Date 2012-04-16 Time 09:58 Rev Time 0.00
Received By hmoser Date 2012-04-13 Time 12:44 Sent To  
Notes
2012-04-16 09:58:29PLANS DENIED
 1) REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC(M)
 .PAGE M101 A
 AND PAGE M120 A OF PLANS.
 2) INDICATE ON THE PLANS WHAT PART OF THE BUILDING RTU
 1,2,AND 3 COOL
 PER SECTION 106.3.4 SITE DRAWINGS.
 3) PAGE M601 OF THE PLANS SHOW TWO MINI SPLIT A/C UNITS
 INDICATE ON THE PLANS
 WHERE THEY ARE. PER SECTION 106.3.4 SITE DRAWINGS.
 4) REFER TO SECTION 13-409.AB.3.3 DAMPER SHUTOFF
 CONTROLS.
 2007 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-04-04 Cont ID  
Sent By hmoser Date 2012-04-04 Time 14:38 Rev Time 0.00
Received By hmoser Date 2012-04-04 Time 14:20 Sent To  
Notes
2012-04-04 14:40:35NO MECHANICAL PLANS SUBMITTED.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-05-02 Cont ID  
Sent By lwagner Date 2012-05-02 Time 12:01 Rev Time 0.00
Received By lwagner Date 2012-05-01 Time 12:02 Sent To  
Notes
2012-05-02 12:00:54THE GANG RESTROOM CONFIGERATION WAS VERIFIED BY PALM
 BEACH SCHOOL BUILDING DIRECTOR FOR STANDARD LOCATION OF
 LAVATORIES.
  
 PER ARCHITECT THE 2ND FLOOR CIRCUIT VENT STACK WAS
 MOVED TO THE BUILDING SEWER FROM THE FIRST FLOOR
 CIRCUIT VENT SYSTEM.

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-04-18 Cont ID  
Sent By lwagner Date 2012-04-18 Time 13:16 Rev Time 0.00
Received By rlecky Date 2012-04-18 Time 11:37 Sent To  
Notes
2012-04-18 13:10:02FBC 2007 PLUMBING REVIEW #2
 DENIED:
  
 1. SHEET A-1 SHOWS 8 SINGLE USER RESTROOMS. SHEET P-1
 SHOWS 5 SINGLE USER RESTROOMS.
  
 2. SHEETS A-1 & A-2 SHOW A TOTAL OF 7 SINKS THAT DO NOT
 APPEAR ON THE PLUMBING DRAWINGS.
  
 3. SHEET A-1 PLUMBING TABLE LISTS 18 DRINKING FOUNTAINS
 AND 2 SERVICE SINKS THAT DO NOT APPEAR ON A-1, A-2,
 P-1, OR P-2
  
 4. SHEET P-1 - 3 WATER CLOSETS AND 4 LAVS ARE MISSING
 IN THE GANG RESTROOMS ON EACH FLOOR.
  
 5. PLEASE SHOW THE LOCATION AND SIZE OF THE WATER
 HEATER/S.
 NOTE- 607.2 HOT WATER SUPPLY TEMPERATURE MAINTENANCE.
 WHERE THE DEVELOPED LENGTH OF HOT WATER PIPING FROM THE
 SOURCE OF HOT WATER SUPPLY TO THE FARTHEST FIXTURE
 EXCEEDS 100 FEET (30 480 MM), THE HOT WATER SUPPLY
 SYSTEM SHALL BE PROVIDED WITH A METHOD OF MAINTAINING
 THE TEMPERATURE IN ACCORDANCE WITH CHAPTER 13 OF THE
 FLORIDA BUILDING CODE, BUILDING .
 607.2.1 CIRCULATING SYSTEMS. PIPING INSULATION SHALL
 CONFORM TO THE REQUIREMENTS OF TABLE 607.1.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-03-26 Cont ID  
Sent By lwagner Date 2012-03-26 Time 15:33 Rev Time 0.00
Received By lwagner Date 2012-03-26 Time 14:28 Sent To  
Notes
2012-03-26 15:32:44FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. NO TOTAL OCCUPANT LOAD WAS FOUND ON THE PLANS TO
 CALCULATE REQUIRED FIXTURES
 403.1 MINIMUM NUMBER OF FIXTURES.
 EDUCATIONAL:
 WATER CLOSETS 1 PER 50 REQUIRED
 LAVATORIES 1 PER 50 REQUIRED
 DRINKING FOUNTAIN 1 PER 100 OCCUPANTS REQUIRED
 1 SERVICE SINK REQUIRED
  
 2. PLEASE INCLUDE THE FOLLOWING FOR REVIEW:
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 PLUMBING
 1. MINIMUM PLUMBING FACILITIES
 3. WATER SUPPLY PIPING
 5. WATER HEATERS
 6. VENTS
 10. LOCATION OF WATER SUPPLY LINE
 13. PLUMBING RISER (HOT AND COLD WATER)
  
 3. A CLEANOUT IS REQUIRED AT THE BASE OF STACKS
 708.3.4 BASE OF STACK. A CLEANOUT SHALL BE PROVIDED AT
 THE BASE OF EACH WASTE OR SOIL STACK.
  
 4. THE FOLLOWING VENTS ARE MISSING FROM PLAN:
 THE CURCUIT VENTS BETWEEN THE 2 MOST UPSTREAM WATER
 CLOSETS IN THE WOMENS ROOMS.
 911.2 VENT CONNECTION.
  
 THE COMMON VENT BETWEEN THE MENS WATER CLOSETS
 908.1 INDIVIDUAL VENT AS COMMON VENT.
  
 THE VENTS FOR THE URINALS.
 907.1 INDIVIDUAL VENT PERMITTED.
  
 5. THE LAVS IN THE ADA STALLS APPEAR TO BE TOO CLOSE TO
 THE WATER CLOSET. PER FIGURE 30(E) THE LAV IS REQUIRED
 TO BE OUTSIDE OF THE 5' CLEAR SPACE OF THE WATER
 CLOSET.
 11-4.17.3 SIZE AND ARRANGEMENT.
 THE STANDARD ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN
 ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH
 LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30(A) AND FIGURE 30(E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2012-04-10 Cont ID  
Sent By jroach Date 2012-04-10 Time 15:21 Rev Time 0.00
Received By jroach Date 2012-04-10 Time 14:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-03-27 Cont ID  
Sent By jroach Date 2012-03-27 Time 11:32 Rev Time 0.00
Received By jroach Date 2012-03-27 Time 11:32 Sent To  
Notes
***NONE***