Plan Review Details - Permit 12030372
Plan Review Stops For Permit 12030372
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-16 Cont ID  
Sent By jgomez Date 2012-03-16 Time 12:35 Rev Time 0.00
Received By jgomez Date 2012-03-16 Time 11:54 Sent To  
Notes
2012-03-16 13:25:40RE-ROOF BUILDING REVIEW COMMENTS.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE MOISTURE TESTING RESULTS AS REQUIRED BY RAS
 109 (SEE SURFACE PREPARATION REQUIREMENTS ON SELECTED
 APPROVED ASSEMBLY) AND RECOVER SYSTEM LIMITATION #1 ON
 NOA 09-0610.06 SUBMITTED.
  
 2- PROVIDE UPLIFT RESISTANCE TEST RESULTS AS REQUIRED
 BY TAS 124 AND RECOVER SYSTEM LIMITATION #2 ON NOA
 09-0610.06 SUBMITTED.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) OF PROTECTED
 ROOF COATING AS REQUIRED PROTECTIVE COATING APPLICATION
 ON SELECTED APPROVED ASSEMBLY OF NOA 09-0610.06
 SUBMITTED.
  
 4- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY (PAGE 4 OR
 PAGE 5) OF NOA SUBMITTED IS GOING TO BE INSTALLED. SEC.
 106.1.1 OF CITY AMENDMENTS TO FBC.
  
 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTES. THIS SCOPE OF WORK IS
 NOT REFERENCED IN THE MASTER PERMIT 12030342.
  
 ***NOTE; FOR YOUR INFORMATION:
 A) ROOF WASHING IS NOT PERMITTED.
 B) CONTRACTOR REQUIRED TO MAINTAIN JOB LOG IN
 COMPLIANCE WITH RAS 109.
 C) ANY ROOF EQUIPMENT REMOVAL REQUIRES SEPARATE PERMIT.
 D) ANY RETROFIT ROOF DRAINS REQUIRE PLUMBING REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-16 Cont ID  
Sent By jgomez Date 2012-03-16 Time 11:36 Rev Time 0.00
Received By jgomez Date 2012-03-16 Time 11:36 Sent To  
Notes
***NONE***