Plan Review Details - Permit 12030357
Plan Review Stops For Permit 12030357
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-03-16 Cont ID  
Sent By ddaniels Date 2012-03-16 Time 12:31 Rev Time 0.00
Received By ddaniels Date 2012-03-16 Time 12:31 Sent To M
Notes
2012-03-16 12:33:2403/16/2012 PLANS REVIEWED BY FIRE **APPROVED**
  
 1.) A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG
 THE EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A
 MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE
 DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR
 AND SHALL CLEARLY IDENTIFY THE HAZARD PROTECTED PER FBC
 904.11.1.
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-21 Cont ID  
Sent By hmoser Date 2012-03-21 Time 09:18 Rev Time 0.00
Received By hmoser Date 2012-03-14 Time 15:32 Sent To  
Notes
2012-03-15 15:32:50IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-03-21 Cont ID  
Sent By hmoser Date 2012-03-21 Time 09:18 Rev Time 0.00
Received By hmoser Date 2012-03-21 Time 09:18 Sent To  
Notes
***NONE***