Plan Review Details - Permit 12030344
Plan Review Stops For Permit 12030344
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-04-24 Cont ID  
Sent By jwitmer Date 2012-04-24 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2012-04-24 Time 13:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-03-26 Cont ID  
Sent By jwitmer Date 2012-03-26 Time 10:37 Rev Time 2.20
Received By jwitmer Date 2012-03-26 Time 08:00 Sent To  
Notes
2012-03-26 11:23:12BUILDING PROVISO:
 SHEET A10 SECOND FLOOR PARTIAL FLOOR PLAN
 PLEASE REVIEW PLANS FOR: 2007/09 FBC-B 11-4.13.7
 TWO DOORS IN SERIES. THE MINIMUM SPACE BETWEEN TWO
 HINGED
 OR PIVOTED DOORS IN SERIES SHALL BE 48 INCHES (1219 MM)
 PLUS THE
 WIDTH OF ANY DOOR SWINGING INTO THE SPACE. DOORS IN
 SERIES SHALL
 SWING EITHER IN THE SAME DIRECTION OR AWAY FROM THE
 SPACE BETWEEN
 THE DOORS [SEE FIGURE 26(A)].
 LOCATIONS:
 1) ENTRY AREA LEADING INTO CORRIDOR # 224
 2) ENTRY AREA LEADING INTO LOBBY, ROOM 213
 3) ENTRY DOOR INTO STAIR WELL #1 & 4
 IN THE ABOVE CASES TWO AREAS BUT 3 DOORS IN EACH AREA
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-05-01 Cont ID  
Sent By rlecky Date 2012-05-01 Time 16:28 Rev Time 0.00
Received By rlecky Date 2012-05-01 Time 15:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-03-19 Cont ID  
Sent By rlecky Date 2012-03-19 Time 07:56 Rev Time 0.00
Received By rlecky Date 2012-03-16 Time 11:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-05-02 Cont ID  
Sent By ddaniels Date 2012-05-02 Time 12:47 Rev Time 0.00
Received By ddaniels Date 2012-05-02 Time 11:27 Sent To  
Notes
2012-05-02 11:31:40PLANS REVIEWED BY FIRE ***APPROVED*** WITH PROVISO
  
 1.) ENGINEERED FIRE SPRINKLER CONSTRUCTION DOUCUMENTS
 ARE REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PEERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS
 CAN SUBMIT SHOP DRAWINGS ( CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS ) FOR A SUB-PERMIT.
  
 DERRICK DANIELS
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-04-27 Cont ID  
Sent By wjolin Date 2012-04-27 Time 10:14 Rev Time 0.00
Received By wjolin Date 2012-04-25 Time 15:11 Sent To  
Notes
2012-04-27 10:14:555300 EAST AVENUE
 PERMIT #12030344
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: ENGINEERED FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-03 Cont ID  
Sent By wjolin Date 2012-04-03 Time 13:46 Rev Time 0.00
Received By wjolin Date 2012-04-03 Time 12:17 Sent To  
Notes
2012-04-03 13:46:345300 EAST AVENUE
 PERMIT #12030344
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 TRASH AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY. ALL DEMOLITION AND CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SHEET D1 INDICATES THE BUILDING WILL BE OCCUPIED IN
 SPACES ADJACENT TO CONSTRUCTION/DEMOLITION ACTIVITIES.
 TO ENSURE THE SAFETY OF THE OCCUPANTS, PROVIDE A
 DETAILED CONSTRUCTION/DEMOLITION PHASING PLAN SHOWING
 TEMPORARY SEPARATION WALLS, FUNCTIONING/NON-FUNCTIONING
 EXITS, TRAVEL DISTANCES, EXIT SIGNS, FIRE
 EXTINGUISHERS, ETC.
  
 COULD NOT LOCATE SMOKE DETECTION DEVICES ON SECOND
 FLOOR.
  
 COULD NOT LOCATE EMERGENCY LIGHTING ON SECOND FLOOR.
  
 COULD NOT LOCATE PORTABLE FIRE EXTINGUISHER LOCATIONS
 ON THE SECOND FLOOR.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-01 Cont ID  
Sent By rlecky Date 2012-05-01 Time 15:29 Rev Time 0.00
Received By rlecky Date 2012-04-19 Time 15:02 Sent To  
Notes
2012-04-19 15:03:53INCOMING SENT TO B09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-16 Cont ID  
Sent By shill Date 2012-04-16 Time 09:19 Rev Time 0.00
Received By shill Date 2012-03-14 Time 14:38 Sent To  
Notes
2012-03-15 14:39:39B--5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-04-02 Cont ID  
Sent By hmoser Date 2012-04-02 Time 13:39 Rev Time 0.00
Received By hmoser Date 2012-04-02 Time 12:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-04-11 Cont ID  
Sent By lfranco Date 2012-04-11 Time 09:11 Rev Time 0.25
Received By lfranco Date 2012-04-11 Time 09:11 Sent To  
Notes
2012-04-11 09:20:07PLANNING: PASSED **ZONING REVIEW NOT REQUIRED: INTERIOR
 WORK ONLY AND THE VALUE OF PROPOSED WORK DOES NOT
 EXCEED 50% OF THE IMPROVEMENT VALUE.