Plan Review Details - Permit 12030334
Plan Review Stops For Permit 12030334
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-08-01 Cont ID  
Sent By jwitmer Date 2012-08-01 Time 14:02 Rev Time 0.00
Received By jwitmer Date 2012-08-01 Time 12:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-07-05 Cont ID  
Sent By jwitmer Date 2012-07-05 Time 12:37 Rev Time 0.00
Received By jwitmer Date 2012-07-05 Time 12:36 Sent To  
Notes
2012-07-05 12:37:37BUILDING PLAN REVIEW
 PERMIT: 12030334
 ADD: 2275 PALM BEACH LAKES BLVD
 SHILOH FAMILY WORSHIP CENTER - PHASE II
 CONT: CUTTING EDGE BUILDING SYSTEMS, INC
 TEL: (561)282-8265
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 ACTION: DENIED
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THE THIRD SUBMITTAL THE NEW SHEETS HAVE NOT BEEN
 INSERTED INTO THE PLANS, AS REVIEWED NOT COMPLETE SETS
 OF PLANS.
  
 1) COMPLIED.
  
 2) COMPLIED. PLANS INDICATE THIS TENANT SPECE TO BE
 FIRE SPRINKLERED FIRE SPRINKLER LAYOUT IS INDICATED ON
 A2.0 WITH NEW FIRE SPRINKLER NOTE SHOP DRAWINGS TO
 FOLLOW WITH HYDROLIC CALCULATIONS.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) PROVISO: SHEET A6.0 & A6.1 INDICATES CLOUDS AS PART
 OF A ISOLATED CEILING DESIGN WITHIN THE ASSEMBLY
 OCCUPANCY. PLEASE PROVIDE DETAILS ON WHAT TYPE OF
 MATERIALS THIS SYSTEM IS COMPOSED OF, HOW IT IS TO BE
 HUNG, AND TO WHAT THE CLOUD SYSTEM IS TO BE ATTACHED?
 ADDITIONAL INFORMATION IS REQUIRED? 106.1.2. SHOP
 DRAWINGS WILL BE REQUIRED TO BE REVIEWED BY THE
 DESIGNER OF RECORD BEFORE SUBMITTING THEM TO THE
 BUILDING DEPARTMENT.
  
 6) THIRD REVIEW, NEW COMMENT, THE NEW A1.0 SHEET IS
 MISSING WALL TAGS FOR WALLS THAT WERE CHANGED AS PART
 OF THIS REVISION, EXAMPLE STORAGE ROOM WALLS HAVE THE
 SAME HASH MARKING AS THE COMMON WALL TO THE RESTROOMS,
 THIS WALL DOES NOT REQUIRE THE DRYWALL TO CONTINUE TO
 THE DECK ABOVE, WHERE AS THE STORAGE ROOM CONSIDERED A
 INCIDENTAL USE AREA AND CONSSTRUCTION TO MEET THE
 REQUIREMENT OF 508.2.2.1 AND CAPABLE OF RESITNG PASSAGE
 OF SMOKE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-05-23 Cont ID  
Sent By jwitmer Date 2012-05-23 Time 14:41 Rev Time 0.00
Received By jwitmer Date 2012-05-23 Time 12:48 Sent To  
Notes
2012-05-23 15:00:09BUILDING PLAN REVIEW
 PERMIT: 12030334
 ADD: 2275 PALM BEACH LAKES BLVD
 SHILOH FAMILY WORSHIP CENTER - PHASE II
 CONT: CUTTING EDGE BUILDING SYSTEMS, INC
 TEL: (561)282-8265
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) NEITHER G1.0 NOR THE LS1.0 SHEET INDICATE:
 2A-F) COMPLIED.
 2G) LS1.0 NOTES INDICATES A LIMIT OF 299 OCCUPANTS,
 PLEASE REVIEW PLANS INDICATE 302 SEATS AND AN OCCUPANT
 LOAD WITH THE OCCUPANTS IN A/V CONTROLS & PROJECTION
 ROOM.
 THE OTHER ISSUE THAT WOULD STILL REQUIRE FIRE
 SPRINKLERS WOULD BE 2007 FBC-B 903.2.1.3 EXCEPTION # 2,
 CAN'T BE PART OF A MIXED OCCUPANCY. PLEASE REVIEW
 SECTION 508.3.1 ACCESSORY OCCUPANCIES THE AGGREGATE
 ACCESSORY OCCUPANCIES SHALL NOT BE MORE THAN 10% OF THE
 AREA OF THE STORY IN WHICH THEY ARE LOCATED.
 2H) LS1.0 PLEASE REVIEW FBC-B 907.2.1 FOR ASSEMBLY
 AREAS WITH OCCUPANT LOADS OF 300 OR GREATER.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) PROVISO: SHEET A6.0 & A6.1 INDICATES CLOUDS AS PART
 OF A ISOLATED CEILING DESIGN WITHIN THE ASSEMBLY
 OCCUPANCY. PLEASE PROVIDE DETAILS ON WHAT TYPE OF
 MATERIALS THIS SYSTEM IS COMPOSED OF, HOW IT IS TO BE
 HUNG, AND TO WHAT THE CLOUD SYSTEM IS TO BE ATTACHED?
 ADDITIONAL INFORMATION IS REQUIRED? 106.1.2. SHOP
 DRAWINGS WILL BE REQUIRED TO BE REVIEWED BY THE
 DESIGNER OF RECORD BEFORE SUBMITTING THEM TO THE
 BUILDING DEPARTMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-03 Cont ID  
Sent By jwitmer Date 2012-04-03 Time 13:40 Rev Time 0.00
Received By jwitmer Date 2012-04-03 Time 12:01 Sent To  
Notes
2012-04-03 13:39:53BUILDING PLAN REVIEW
 PERMIT: 12030334
 ADD: 2275 PALM BEACH LAKES BLVD
 SHILOH FAMILY WORSHIP CENTER - PHASE II
 CONT: CUTTING EDGE BUILDING SYSTEMS, INC
 TEL: (561)282-8265
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED ON MARCH 14/2012 ARE TO BE REVIEWED
 UNDER THE 2007/09 FBC. PLANS SUBMITTED ON OR AFTER
 MARCH 15TH/ 2012 ARE TO BE REVIEWED UNDER THE 2010 FBC.
 SHEET G1.0 GOVERNING CODES INDICATE ALL CONSTRUCTION
 WORK, ACTIVITIES & ALTERATIONS SHALL COMPLY WITH THE
 2007 FBC, 2010 EXISTING BUILDING CODE. CODE DESIGNS CAN
 NOT BE MIXED BETWEEN THE EDITIONS OF CODES.
  
 2) NEITHER G1.0 NOR THE LS1.0 SHEET INDICATE:
 2A) MINIMUM BUILDING TYPE
 2B) IS THIS BUILDING FIRE SPRINKLERED? NEITHER G1.0 NOR
 LS1.0 INDICATE FIRE SPRINKLERS, FOR THIS REVIEW IT WILL
 BE CONSIDERED NON-SPRIKLERED
 2C) UNDER THE 2007/ 09 EXISTING BUILDING CODE THE
 DESIGNER WILL NEED TO PICK A COMPLIANCE METHOD. 2007/09
 EXIST BLDG CODE 101.5.
 2D) IS THIS A CHANGE IN OCCUPANCY FOR THIS SPACE? IF SO
 CHAPTER 9 OF THE EXIST BLDG CODE WILL APPLY. 2007/09
 EXIST BLDG CODE 901.3.1 PARTIAL CHANGE IN OCCUPANCY,
 SECTION 912 SHALL APPLY.
 2E) LS1.0 SHEET INDICATES ADJACENT TENANT SPACES ON
 BOTH SIDES OF THIS TENANT SPACE, THE PLANS INDICATE A
 ONE HOUR TENANT SEPERATION WALL, PLEASE REVIEW 2007/09
 FBC-B TABLE 508.3.3 OCCUPANCY SEPERATION FOR EITHER
 BUSINESS OR MERCANTILE WITH THIS A3 OCCUPANCY REQUIRES
 A 2 HOUR OCCUPANCY SEPERATION WALL. PLEASE NOTE THAT
 THE BUSINESS OCCUPANCY THAT TIES TO THIS TENANTCY WOULD
 ALSO REQUIRE A 2 HOUR FIRE RATED WALL WITH 1 1/2 HOUR
 OPENING PROTECTIVES FBC-B TABLE 715.4. SEE NOTE # 5 ON
 SHEET A1.0 FOR A 2 HOUR WALL.
 2F) LS1.0 SHEET DOES NOT INDICATE ANY FIRE RATED
 CORRIDORS, PLEASE REVIEW 2007/09 FBC-B TABLE 1017.1THAT
 REQUIRES 1 HOUR FIRE RATED CORRIDORS WITH OR WITHOUT
 FIRE SPRINKLERS ALSO UPDATE THE DOOR SCHEDULE FOUND ON
 SHEET A7.0.
 2G) LS1.0 NOTE # 2 INDICATES A LIMIT OF 299 OCCUPANTS,
 PLEASE REVIEW PLANS INDICATE 306 SEATS AND AN OCCUPANT
 LOAD OF 21 FOR THE STAGE WHICH TOTALS 327 OCCUPANTS,
 WHY THE LIMITING FACTOR TO 299? THE 2007 FBC-B
 903.2.1.3 DOES REQUIRE FIRE SPRINKLERS FOR OCCUPANT
 LOADS 300 OR GREATER.
 2H) LS1.0 PLEASE REVIEW FBC-B 907.2.1 FOR ASSEMBLY
 AREAS WITH OCCUPANT LOADS OF 300 OR GREATER.
  
 3) SHEET A1.0:
 3A) WALL TYPE F IS FOUND AT ALL STORAGE ROOMS WHICH IF
 OVER 100 SQ FT WILL REQUIRE A 1 HOUR FIRE RATING TO
 EXTEND UP TO THE UNDER SIDE OF THE ROOF DECK FBC-B
 508.2.2.1.
 3B) WALL TYPE B CORRIDOR WALLS WILL ALSO NEED TO BE
 UPDATED TO A 1 HOUR FIRE RATED WALL PER FBC-B 708.1(
 4).
  
 4) 2007/09 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 5) SHEET A2.0 INDICATES UNDER SIDE OF CLOUDS PLEASE
 PROVIDE DETAILS ON WHAT TYPE OF MATERIALS THIS SYSTEM
 IS COMPOSED OF, HOW IT IS TO BE HUNG, AND TO WHAT THE
 CLOUD SYSTEM IS TO BE ATTACHED? ADDITIONAL INFORMATION
 IS REQUIRED? 106.1.2.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-05-08 Cont ID  
Sent By rlecky Date 2012-05-08 Time 09:53 Rev Time 0.00
Received By rlecky Date 2012-05-08 Time 09:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-03-20 Cont ID  
Sent By rlecky Date 2012-03-20 Time 10:06 Rev Time 0.00
Received By rlecky Date 2012-03-19 Time 14:47 Sent To  
Notes
2012-03-20 10:07:5012030334
 2275 PALM BEACH LAKES BLVD.
 SANCTUARY AND CLASSROOMS
 GROUP A3
  
 VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING
 RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND
 CURRENT THAT IS AVAILABLE. NEC 110.9
 FEEDER CONDUCTORS TO NEW PANELBOARDS, OVERCURRENT
 DEVICES AND MAIN LUGS APPEAR TO BE MISMATCHED. LOCATE
 ALL PANEL BOARDS ON THE PLAN SHOWING ALL SAFETY
 CLEARANCES. NEC 310.16, 110.26
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 CLARIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 SPACE CONTROL FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS
 13-415 ABC.1.3
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR
 SECURITY, VOICE, DATA AND FIRE ALARM SYSTEMS.
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2012-07-30 Cont ID  
Sent By rferguso Date 2012-07-30 Time 11:42 Rev Time 0.00
Received By rferguso Date 2012-07-30 Time 11:42 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2012-06-30 Cont ID  
Sent By wjolin Date 2012-06-30 Time 18:48 Rev Time 0.00
Received By wjolin Date 2012-06-30 Time 18:27 Sent To  
Notes
2012-06-30 18:48:352275 PALM BEACH LAKES BOULEVARD
 PERMIT #12030334
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: ENGINEERED FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 TO OBTAIN A GENERAL BUILDING PERMIT, BY STATE LAW AND
 THE FLORIDA BUILDING CODE, WHEN A FIRE SPRINKLER SYSTEM
 IS TO BE INSTALLED OR MODIFIED, PURSUANT TO FS 553.79,
 FIRE PROTECTION DESIGN DOCUMENTS SHALL BE PREPARED BY A
 QUALIFIED ENGINEER AND SUBMITTED TO THE AUTHORITY
 HAVING JURISDICTION. ALL DESIGN DOCUMENTS SUBMITTED FOR
 THIS PURPOSE SHALL PROVIDE A SCOPE OF WORK FOR THE
 SPRINKLER CONTRACTOR AND SHALL COMPLY WITH FBPE RULES
 OF RESPONSIBILITY CHAPTER 61G15-32. PER 61G15-32 FAC,
 BASIC ENGINEERING REQUIREMENTS FOR PLANS SHALL INCLUDE:
 WATER SUPPLY INFORMATION, SUPPRESSION SYSTEM TYPE,
 HAZARD CLASSIFICATION, APPLICABLE CODES AND STANDARDS
 WITH APPROPRIATE YEAR/EDITION, STRUCTURAL INFORMATION
 AND STRUCTURAL OPENINGS, ALARMS, ACTIVATION CONTROLS,
 AND INTERFACES WITH OTHER SYSTEMS. CONTRACTOR SHOP
 DRAWINGS ARE REQUIRED TO OBTAIN A FIRE SPRINKLER
 PERMIT. SHOP DRAWINGS SHALL CONFORM TO THE DESIGN
 REQUIREMENTS OF THE ENGINEER OF RECORD DESIGN
 DOCUMENTS. SHOP DRAWINGS SHALL NOT BE SEALED BY AN
 ENGINEER.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-05-21 Cont ID  
Sent By wjolin Date 2012-05-21 Time 13:38 Rev Time 0.00
Received By wjolin Date 2012-05-21 Time 11:40 Sent To  
Notes
2012-05-21 13:38:342275 PALM BEACH LAKES BOULEVARD
 PERMIT #12030334
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS1.0: THE KNOX-BOX SHOWN AS "LB" INCORRECTLY
 INDICATES THE AUTHORITY HAVING JURISDICATION AS PALM
 BEACH COUNTY FIRE RESCUE.
  
 SHEET A1.0: KNOX-BOX IS INCORRECTLY IDENTIFIED BY
 CONSTRUCTION NOTE #23 (SHOULD BE #24).
  
 SHEET A 7.2: COULD NOT LOCATE TACTILE SIGNAGE FOR EXIT
 DOORS.
  
 SHEET A7.0: DOOR #9 DOES NOT INDICATE A FIRE RESISTANCE
 RATING.
  
 SHEET A7.0: SINGLE DOOR AT MAIN ENTRANCE IS INDICATED
 AS DOOR #7; THE SCHEDULE INDICATES DOOR #7 AS A STORAGE
 ROOM DOOR.
  
 SHEET A7.0: FIRE RATED DOORS ON STORAGE ROOMS NEED TO
 BE EQUIPPED WITH DOOR CLOSERS.
  
 SHEET A1.0 & SHEET A6.1: STAIRS TO PLATFORM ARE NOT
 SHOWN ON SHEET A1.0. THE RAISED PLATFORM IS INDICATED
 AS AN ELEVATION OF 3'-6". PROVIDE STAIR GUARDS
 RESISTING 4-INCH SPHERE AND A PERIMETER GUARDRAIL FOR
 THE UPPER PLATFORM.
  
 NOTE: ENGINEERED FIRE ALARM PLANS NOT RESUBMITTED:
 REPEAT COMMENT: PER LOCAL AHJ POLICY, DUCT SMOKE
 DETECTORS SHALL INITIATE A GENERAL FIRE ALARM
 CONDITION.
  
 REPEAT COMMENT: PROVIDE A PRE-RECORDED FIRE ALARM
 EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS
 BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT,
 AND EXIT THE BUILDING IMMEDIATELY.
  
 REPEAT COMMENT: A CERTIFICATE OF COMPLETION AND A THIRD
 PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE
 SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM
 INSPECTION.
  
 REPEAT COMMENT: ASSEMBLY OCCUPANCIES EXCEEDING 300
 PERSONS WILL BE REQUIRED TO BE PROTECTED BY AN
 AUTOMATIC FIRE SPRINKLER SYSTEM.
 ADDITIONAL INFORMATION: SECTION 903.2.1.3 OF THE
 FLORIDA BUILDING CODE WILL STILL REQUIRE AN AUTOMATIC
 SPRINKLER SYSTEM BECAUSE OF THE MIXED OCCUPANCY
 (ASSEMBLY, MERCANTILE, EDUCATION) USAGE. ALSO REFER TO
 SECTION 12.3.5.2 AND SECTION 12.3.5.3 (FLORIDA FIRE
 PREVENTION CODE - NFPA 101) WHEREBY AN AUTOMATIC
 SPRINKLER SYSTEM IS REQUIRED.
  
 REPEAT COMMENT: ENGINEERED FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-03 Cont ID  
Sent By wjolin Date 2012-04-03 Time 15:51 Rev Time 0.00
Received By wjolin Date 2012-04-03 Time 14:02 Sent To  
Notes
2012-04-03 15:51:572275 PALM BEACH LAKES BOULEVARD
 PERMIT #12030334
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE MAIN ENTRANCE DOORS SHALL BE SIZED TO ACCOMMODATE
 1/2 OF THE MAXIMUM OCCUPANT LOAD.
  
 FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS, PANIC OR FIRE EXIT HARDWARE SHALL BE PROVIDED
 ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE. REFER TO DOOR #3, EX1, EX4 ETC.
  
 EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 SHEET A10.1 WAS NOT SUBMITTED.
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 ASSEMBLY OCCUPANCIES EXCEEDING 300 PERSONS WILL BE
 REQUIRED TO BE PROTECTED BY AN AUTOMATIC FIRE SPRINKLER
 SYSTEM.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status P Date 2012-08-02 Cont ID  
Sent By jwitmer Date 2012-08-02 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2012-08-02 Time 13:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-08-01 Cont ID  
Sent By jwitmer Date 2012-08-01 Time 14:02 Rev Time 0.00
Received By jwitmer Date 2012-07-20 Time 15:33 Sent To  
Notes
2012-07-20 12:59:38IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-07-09 Cont ID  
Sent By hmoser Date 2012-07-09 Time 12:17 Rev Time 0.00
Received By hmoser Date 2012-06-12 Time 11:58 Sent To  
Notes
2012-06-12 11:58:28C-25 JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-24 Cont ID  
Sent By hmoser Date 2012-05-24 Time 10:25 Rev Time 0.00
Received By hmoser Date 2012-05-07 Time 15:34 Sent To  
Notes
2012-05-07 15:42:20C--5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-12 Cont ID  
Sent By shill Date 2012-04-12 Time 10:46 Rev Time 0.00
Received By shill Date 2012-03-14 Time 11:45 Sent To  
Notes
2012-03-15 15:26:58C03
2012-03-15 11:46:05C--28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2012-08-02 Cont ID  
Sent By jwitmer Date 2012-08-02 Time 13:50 Rev Time 0.00
Received By jwitmer Date 2012-08-02 Time 13:50 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-07-05 Cont ID  
Sent By jwitmer Date 2012-04-03 Time 12:34 Rev Time 0.00
Received By jwitmer Date 2012-04-03 Time 12:34 Sent To  
Notes
2012-07-05 12:36:15BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-07-09 Cont ID  
Sent By hmoser Date 2012-07-09 Time 12:15 Rev Time 0.00
Received By hmoser Date 2012-07-09 Time 11:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-05-24 Cont ID  
Sent By hmoser Date 2012-05-24 Time 10:24 Rev Time 0.00
Received By hmoser Date 2012-05-24 Time 09:49 Sent To  
Notes
2012-05-24 10:24:45PLANS DENIED
 1) PROVIDE A FULL SET OF MECHANICAL PLANS MISSING
 PAGES M-2, M-3, M-4
 2) REFER TO SECTION 901.1 EXISTING BUILDING CODE
 2007. ALL ROOF TOP UNITS NEED TO COMPLY WITH
 13-409.AB.3.3 SHUTOFF DAMPER CONTROLS.2007
 FLORIDA ENERGY CODE.
 3) REFER TO SECTION 607.5.1 FIRE WALLS 2007
 FBC (M) MISSING A FIRE DAMPER IN 4X9 DUCT ABOVE
 WOMENS BATHROOM.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-07-09 Cont ID  
Sent By hmoser Date 2012-03-21 Time 12:16 Rev Time 0.00
Received By hmoser Date 2012-03-21 Time 14:40 Sent To  
Notes
2012-03-22 11:01:12PLANS DENIED
 1) MISSING FIRE DAMPERS IN STORAGE ROOM 114 C .
 REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC (M)
 2) PROVIDE INFORMATION ON THE 18X14 DUCT GOING IN THE
 BATHROOM.
 IF IT IS A SUPPLY WHAT RTU IS TI COMING FROM.
 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM 2007 FBC
 (M)
 AND SECTION 606.4.1 SUPERVISION NEW AND EXISTING RTU.
 4) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER
 CONTROLS.
 2007 ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-05-16 Cont ID  
Sent By lwagner Date 2012-05-16 Time 10:46 Rev Time 0.00
Received By lwagner Date 2012-05-16 Time 10:08 Sent To  
Notes
2012-05-16 10:47:20CIRCUIT VENT REQUIRED - SEE PLAN

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-04-05 Cont ID  
Sent By lwagner Date 2012-04-05 Time 13:25 Rev Time 0.00
Received By lwagner Date 2012-04-05 Time 08:44 Sent To  
Notes
2012-04-05 11:32:12FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. THE PLUMBING CALCULATIONS ON SHEET G1.0 SHOW 8 WATER
 CLOSETS FOR WOMEN AND 4 FOR MEN. PLEASE CLARIFY OR
 CORRECT THE FOLLOWING:
 1A. SHEET A1.0 AND PLUMBING SHEETS SHOW ONLY 4 WATER
 CLOSETS FOR WOMEN.
 1B. SHEET A1.0 AND PLUMBING SHEETS SHOW 1 WATER CLOSET
 AND 3 URINALS FOR MEN. SECTION 419.2 URINALS SHALL NOT
 BE SUBSTITUTED FOR MORE THAN 67 PERCENT OF THE REQUIRED
 WATER CLOSETS IN ASSEMBLY AND EDUCATIONAL OCCUPANCIES.
 2 WATER CLOSETS AND 2 URINALS WOULD BE REQUIRED.
 1C. 403.7 UNISEX TOILET AND BATHING ROOMS. IN ASSEMBLY
 AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE UNISEX TOILET
 ROOM SHALL BE PROVIDED WHERE AN AGGREGATE OF SIX OR
 MORE MALE AND FEMALE WATER CLOSETS IS REQUIRED.
  
 2. SHEET P-2 HOT WATER WILL BE REQUIRED AT THE JANITOR
 SINK:
 607.1 WHERE REQUIRED. IN OCCUPIED STRUCTURES, HOT WATER
 SHALL BE SUPPLIED TO ALL PLUMBING FIXTURES AND
 EQUIPMENT UTILIZED FOR BATHING, WASHING, CULINARY
 PURPOSES, CLEANSING, LAUNDRY OR BUILDING MAINTENANCE.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 2 Status P Date 2012-06-13 Cont ID  
Sent By lfranco Date 2012-06-13 Time 08:00 Rev Time 0.00
Received By lfranco Date 2012-06-13 Time 08:00 Sent To  
Notes
2012-06-13 08:00:31PLANNING: PASSED **** ZONING REVIEW NOT REQUIRED:
 INTERIOR WORK ONLY AND THE VALUE OF PROPOSED WORK DOES
 NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ****

Review Stop Z ZONING
Rev No 1 Status P Date 2012-04-11 Cont ID  
Sent By lfranco Date 2012-04-11 Time 09:35 Rev Time 0.25
Received By lfranco Date 2012-04-11 Time 09:34 Sent To  
Notes
2012-04-11 09:35:41PLANNING: PASSED **** ZONING REVIEW NOT REQUIRED:
 INTERIOR WORK ONLY AND THE VALUE OF PROPOSED WORK DOES
 NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ****