2012-04-06 10:03:52BUILDING PLAN REVIEW
 PERMIT: 12030295
 ADD: 300 NORTHPOINT PKWY # 305
 CONT: TRILLIUM CONSTRUCTION, INC
 TEL: (561)283-5121
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A100 & A120 INDICATE ROOM # 119 AS A TRAINING
 ROOM THAT HAS AN OCCUPANT LOAD OF 87 ( 1292/15= 87),
 PLEASE REVIEW 2007/09 FBC-B 1008.1.2 DOORS SHALL SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE SERVING AN
 OCCUPANT LOAD OF 50 OR MORE PERSONS.
  
 2) SHEET A100 & A120 ROOM # 119 IS INDICATED WITH A 1
 HR FIRE PARTITION NEITHER OF DOORS 18 OR 19 INDICATE
 ANY FIRE RATING ON THE DOOR SCHEDULE A100. 2007/09
 FBC-B TABLE 715.4
  
 3) SHEET A100 & A120 THE DOOR LEADING FROM OFFICE TO
 WAREHOUSE (DOOR # 8) IN A 1 HOUR RATED FIRE WALL DOES
 NOT INDICATE ANY RATING, PLEASE REVIEW 2007/09 FBC-B
 TABLE 715.4.
  
 4) SHEET A100 & A120 STORAGE ROOM #118 HAS TWO WALLS 1
 HR ATED BECAUSE OF THE ADJOINING OCCUPANCY
 CLASSIFICATIONS THE OTHER 2 WALLS ARE DESIGNATED AS A
 TYPE (2) WALL. DETAIL # 2 SHEET A600 INDICATES THIS
 WALL STOPS 6 INCHES ABOVE THE CEILING. PLEASE REVIEW
 2007/09 FBC-B TABLE 508.2 INCIDENTAL USE AREAS (STORAGE
 > 100 SQ FT). PLEASE SEE 508.2.2.1 CONSTRUCTION. WHERE
 TABLE 508.2 PERMITS AN AUTOMATIC FIRE-EXTINGUISHING
 SYSTEM WITHOUT A FIRE BARRIER, THE INCIDENTAL USE AREA
 SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING
 BY CONSTRUCTION CAPABLE OF RESISTING THE PASSAGE OF
 SMOKE. THE PARTITIONS SHALL EXTEND FROM THE FLOOR TO
 THE UNDERSIDE OF THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING ASSEMBLY OR FIRE-RESISTANCE-RATED
 ROOF/CEILING ASSEMBLY ABOVE OR TO THE UNDERSIDE OF THE
 FLOOR OR ROOF SHEATHING, OR SUB DECK ABOVE.
 SMOKE PARTITIONS 710.
 710.4 CONTINUITY. SMOKE PARTITIONS SHALL EXTEND FROM
 THE TOP OF THE FOUNDATION OR FLOOR BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, DECK OR SLAB
 ABOVE OR TO THE UNDERSIDE OF THE CEILING ABOVE WHERE
 THE CEILING MEMBRANE IS CONSTRUCTED TO LIMIT THE
 TRANSFER OF SMOKE.
  
 5) 2007/09 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-04-30 Cont ID  
Sent By rlecky Date 2012-04-30 Time 15:08 Rev Time 0.00
Received By rlecky Date 2012-04-30 Time 15:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-03-26 Cont ID  
Sent By rlecky Date 2012-03-26 Time 15:57 Rev Time 0.00
Received By rlecky Date 2012-03-26 Time 15:40 Sent To  
Notes
2012-03-26 15:57:35REDLINED IN EXAM ROOM FOR NEC 517 WIRING METHOD. RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-04-19 Cont ID  
Sent By wjolin Date 2012-04-19 Time 12:27 Rev Time 0.00
Received By wjolin Date 2012-04-19 Time 10:26 Sent To  
Notes
2012-04-19 10:39:09300 NORTHPOINT PARKWAY - SUITE #305
 PERMIT #12030295
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DOOR #13: DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, HALLWAY OR
 LANDING UNOBSTRUCTED AND SHALL PROJECT NOT MORE THAN
 7-INCHES INTO THE REQUIRED WIDTH OF THE EGRESS PATH
 WHEN FULLY OPEN.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-02 Cont ID  
Sent By wjolin Date 2012-04-02 Time 13:25 Rev Time 0.00
Received By wjolin Date 2012-04-02 Time 12:14 Sent To  
Notes
2012-04-02 13:24:34300 NORTHPOINT PARKWAY - SUITE #305
 PERMIT #12030295
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES SUITE #305 AND THE
 DRAWINGS INDICATE SUITE #300. PLEASE COORDINATE.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 FIRE-RATED WALLS/PARTITIONS SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SHEET A100 - DOOR #18 IS REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHEN SERVING AN OCCUPANT
 LOAD OF MORE THAN 50 PERSONS (1350 SQ.FT. / 15 SQ.FT. =
 90 PERSONS).
  
 SHEET A100 - EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING
 FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM
 POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM
 THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET M2.1 - PROVIDE FIRE DAMPERS FOR DUCTWORK
 PENETRATING FIRE RATED WALL OF TRAINING ROOM.
  
 SHEET FA2.1- PROVIDE FIRE ALARM NOTIFICATION APPLIANCE
 IN BEREAVEMENT LOBBY.
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 SHEET FS2.1 - ESTABLISHES BRADLY BROWN AS THE ENGINEER
 OF RECORD FOR THE FIRE SPRINKLER SYSTEM; THEREFORE,
 FIRE SPRINKLER SHOP DRAWINGS PRODUCED BY THE CONTRACTOR
 SHOULD NOT BE SIGNED/SEALED PER FS 633.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-01 Cont ID  
Sent By hmoser Date 2012-05-01 Time 12:43 Rev Time 0.00
Received By hmoser Date 2012-04-10 Time 10:22 Sent To  
Notes
2012-04-10 10:58:51C14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-06 Cont ID  
Sent By hmoser Date 2012-04-06 Time 10:43 Rev Time 0.00
Received By hmoser Date 2012-03-13 Time 15:41 Sent To  
Notes
2012-03-19 15:30:51SENT TO C14 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-05-01 Cont ID  
Sent By hmoser Date 2012-05-01 Time 12:43 Rev Time 0.00
Received By hmoser Date 2012-05-01 Time 12:30 Sent To  
Notes
2012-05-01 12:42:48PROVISO
 1) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER
 CONTROLS ( FOR FRESH AIR)
 2007 FLORIDA ENERGY CODE
 2) REFER TO SECTION 301.12 WIND RESISTANCE 2007 FBC (M)
 . WOOD SLEEPERS
 ON THE ROOF FOR CONDENSATE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-04-06 Cont ID  
Sent By hmoser Date 2012-04-06 Time 10:42 Rev Time 0.00
Received By hmoser Date 2012-04-06 Time 09:24 Sent To  
Notes
2012-04-06 10:42:34PLANS DENIED
 1) REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC (M)
 PAGE M2-1 ON PLANS TRAINING ROOM.
 2) TIPICAL ROOFTOP A/C UNIT DETAIL PAGE M7.1 OF PLANS
 SHOW DUCT DETECTOR IN RETURN AIR. DUCT DETECTOR MUST
 BE IN SUPPLY . PER SECTION 606.2.1 SUPPLY AIR SYSTEM.
 2007 FBC (M)
 3) REFER TO SECTION 606.3 INSTALLATION AND 606.4.1
 SUPERVISION.
 2007 FBC (M)
 4) REFER TO SECTION 601.4 BALANCED RETURN AIR. 2007 FBC
 (M)
 5) REFER TO SECTION 13-409.AB.3.3 SHUTOFF CONTROL'S
 2007 ENERGY CODE.
 6) RETURN AIR GRILLE SCHEDULE PAGE M6.1 AND RETURN AIR
 ON PAGE M2-1
 DO NOT MATCH.
 7) PROVIDE A DETAIL BY THE ENGINEER ON THE CURB TIE
 DOWN TO THE ROOF.
 PER SECTION 301.12 WIND RESISTANCE 2007 FBC (M)
 8) REFER TO SECTION 301.12 WIND RESISTANCE REFERRING TO
 WOOD SLEEPERS
 FOR CONDENSATE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-03-27 Cont ID  
Sent By lwagner Date 2012-03-27 Time 09:23 Rev Time 0.00
Received By lwagner Date 2012-03-27 Time 08:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-03-26 Cont ID  
Sent By eschneid Date 2012-03-26 Time 10:06 Rev Time 0.50
Received By eschneid Date 2012-03-26 Time 10:06 Sent To  
Notes
2012-03-26 12:50:47INTERIOR WORK VALUED AT LESS THAN 50% OF STRUCTURE. THE