Plan Review Details - Permit 12030294
Plan Review Stops For Permit 12030294
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2012-11-01 Cont ID  
Sent By jnguyen Date 2012-11-01 Time 12:25 Rev Time 0.00
Received By jnguyen Date 2012-10-30 Time 10:50 Sent To  
Notes
2012-11-01 08:48:06THIS PARCEL HAS A PRIMARY ADDRESS AT 425 24TH ST FOR
 THE THE EAST BUILDING & A SECONDARY ADDRESS AT 2401
 SPRUCE AVE FOR THE WEST BUILDING. I NEEDED
 CLARIFICATION ON WHAT THE ADDRESSING ISSUE WAS? LUIS
 MARTINEZ INFORMED ME THAT THIS PERMIT WAS INITIALLY
 REFERENCED TO THE WRONG ADDRESS AT 2401 SPRUCE AVE &
 JUST NEEDED TO BE LINKED TO CORRECT ONE AT 425 24TH ST.
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 PUBLIC UTILITIES DEPARTMENT
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-12-21 Cont ID  
Sent By jwitmer Date 2012-12-21 Time 09:41 Rev Time 0.00
Received By jwitmer Date 2012-12-21 Time 08:41 Sent To  
Notes
2012-12-21 09:48:41STAMP NEW SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-11-20 Cont ID  
Sent By jwitmer Date 2012-11-20 Time 10:47 Rev Time 0.00
Received By jwitmer Date 2012-11-20 Time 10:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-10-02 Cont ID  
Sent By jwitmer Date 2012-10-02 Time 12:08 Rev Time 0.00
Received By jwitmer Date 2012-10-01 Time 16:30 Sent To  
Notes
2012-10-02 12:08:01BUILDING PLAN REVIEW
 PERMIT: 12030294
 ADD: 425 24TH ST
 CONT: CLEAR SPAN
 TEL: (561)252-9028
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 APPLICATION DATE 3/13/2012
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 (1) SET OF PLANS FOR REVIEW.
 1ST REVIEW
 ACTION: DENIED
  
 1) SP-1 PROJECT SUMMARY INDICATES THESE PLANS WERE
 DESIGNED TO THE 2004 FBC. THE PLANS WILL NEED TO BE
 UPDATED TO BE DESIGNED UNDER THE 2007/ 09 SUPPLEMENTS
 FLORIDA BUILDING CODE- BUILDING, & 2007 / 09
 SUPPLEMENTS FLORIDA EXISTING BUILDING CODE.
  
 2) SP-1 WIND DESIGN CRITERIA PLANS ARE CURRENTLY
 DESIGNED TO THE 2004 FBC-B. THE PLANS WILL NEED THE
 WIND DESIGN TO COMPLY UNDER THE FBC-B 2007
 SECTION 1609.1.1 WIND LOADS ON EVERY BUILDING OR
 STRUCTURE SHALL BE DETERMINED IN ACCORDANCE WITH
 CHAPTER 6 OF ASCE 7-05.
  
 3) THROUGHOUT THE PLANS THERE IS REFRENECES TO THE 2004
 FBC PLEASE UPDATE ALL CODE REFERENECES TO THE 2007 FBC.
  
 4) SHEEET A-13 DOOR SCHEDULE;
 4A) DOOR # 100 IS INDICATED IN A 2 HR OCCUPANCY
 SEPERATION WALL 2007 FBC-B TABLE 715.4 REQUIRES A 1 1/2
 HR OPENING PROTECTION.
  
 5) LIFE SAFETY PLAN INDICATES EXIT ACCESS TRAVEL AS 200
 FT FOR OCCUPANCY A PLEASE REVIEW 2007 FBC-B TABLE
 1016.1 FOR ASSEMBLY OCCUPANCY, 250 FT.
  
 6) LIFE SAFETY PLAN, CORRIDOR 100 & 105 WILL REQUIRE
 THE FIRE RATED DOORS TO BE IN PLACE 127-130 & 135- 137
 TO BE ABLE TO MAINTAIN A FIRE RATED CORRIDOR, PLANS DO
 NOT INDICATE HOW TO MAINTAIN THE 45 MINUTE OPENING
 PROTECTIVES WHEN NOT PART OF SCOPE OF WORK? 2007 FBC-B
 TABLE 715.4.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-12-12 Cont ID  
Sent By rlecky Date 2012-12-12 Time 10:51 Rev Time 0.00
Received By rlecky Date 2012-12-12 Time 10:24 Sent To  
Notes
2012-12-12 10:51:1112030294
 2401 SPRUCE AVENUE
 COMMERCIAL RENOVATION
  
 THE FOLLOWING ITEMS HAVE BEEN NOTED AS A PROVISO ON THE
 PLANS.
  
 VERIFY THE LIGHTING DENSITY IS COMPLIANT WITH THE 2007
 FLORIDA BUILDING ENERGY CODE REQUIREMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION AS APPROPRIATE TO
 THE DESIGN. 2005 NEC 110.22, 110.16
  
 PROVIDE A SUMMARY LOAD CALCULATION. 2005 NEC 215.2
  
 PROVIDE A FEEDER AND CONDUIT SCHEDULE FOR PANEL "AD".
 2005 NEC 215.5
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA AND
 FIRE ALARM SYSTEMS.
  
 PLEASE CALL IF FURTHER CLARIFICATION IS NEEDED.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-11-26 Cont ID  
Sent By rlecky Date 2012-11-26 Time 12:55 Rev Time 0.00
Received By rlecky Date 2012-11-26 Time 12:07 Sent To  
Notes
2012-11-26 12:57:32THE FOLLOWING ELECTRICAL REVIEW COMMENTS FROM 10/1/12
 WERE NOT ADDRESSED IN THE REVISION SUBMITTED.
  
 12030294
 2401 SPRUCE AVENUE
 COMMERCIAL RENOVATION
  
 PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW
 COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY VERIFYING COMPLIANCE
 WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC EC 505.5.3
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION AS APPROPRIATE TO
 THE DESIGN. 2005 NEC 110.22, 110.16
  
 PROVIDE A SUMMARY LOAD CALCULATION. 2005 NEC 215.2
  
 PROVIDE A FEEDER AND CONDUIT SCHEDULE FOR PANEL "AD".
 2005 NEC 215.5
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA AND
 FIRE ALARM SYSTEMS.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-10-01 Cont ID  
Sent By rlecky Date 2012-10-01 Time 10:54 Rev Time 0.00
Received By rlecky Date 2012-10-01 Time 09:59 Sent To  
Notes
2012-10-01 10:55:4312030294
 2401 SPRUCE AVENUE
 COMMERCIAL RENOVATION
  
 PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW
 COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY VERIFYING COMPLIANCE
 WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC EC 505.5.3
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION AS APPROPRIATE TO
 THE DESIGN. 2005 NEC 110.22, 110.16
  
 PROVIDE A SUMMARY LOAD CALCULATION. 2005 NEC 215.2
  
 PROVIDE A FEEDER AND CONDUIT SCHEDULE FOR PANEL "AD".
 2005 NEC 215.5
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA AND
 FIRE ALARM SYSTEMS.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-01-04 Cont ID  
Sent By W JOLIN Date 2013-01-04 Time 09:08 Rev Time 0.00
Received By wjolin Date 2013-01-04 Time 08:53 Sent To  
Notes
2013-01-04 09:03:53425 24TH STREET
 PERMIT #12030294
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE ALARM: PROVIDE VISUAL NOTIFICATION APPLIANCE IN
 ALL PUBLIC AND COMMON USE SPACES.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-11-20 Cont ID  
Sent By wjolin Date 2012-11-20 Time 12:20 Rev Time 0.00
Received By wjolin Date 2012-11-20 Time 11:38 Sent To  
Notes
2012-11-20 12:02:40425 24TH STREET
 PERMIT #12030294
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 CONFIRM ALL EXISTING EXTERIOR EXIT DOORS ARE EQUIPPED
 WITH PANIC HARDWARE.
  
 PART OF THE ASSEMBLY OCCUPANCY APPEARS TO EXIT THROUGH
 THE BUSINESS OCCUPANCY. WHERE EXIT ACCESS FROM AN
 OCCUPANCY TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE
 OCCUPANCY SHALL BE TREATED AS A MIXED OCCUPANCY PER
 NFPA 101 SECTION 6.1.14.1.2.
  
 NO INFORMATION PROVIDED FOR PHASE III. WILL THIS BE
 EMPTY SHELL SPACE OR STORAGE DURING PHASE I AND II?
 WHAT IS THE OCCUPANT LOAD FOR PHASE III?
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. FOR ISSUANCE OF A GENERAL BUILDING
 PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING
 CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 FIRE ALARM: PROVIDE VISUAL NOTIFICATION APPLIANCE IN
 ALL PUBLIC AND COMMON USE SPACES.
  
 FIRE ALARM: PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES AS NEW ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM
 NOTIFICATION BY VISIBLE SIGNALS AND VOICE
 ANNOUNCEMENTS. REFERENCE SECTION 12.3.4.3.3 OF FLORIDA
 FIRE PREVENTION CODE ? NFPA 101
  
 FIRE ALARM: PROVIDE A PRE-RECORDED FIRE ALARM
 EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS
 BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT,
 AND EXIT THE BUILDING IMMEDIATELY.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-10-04 Cont ID  
Sent By wjolin Date 2012-10-04 Time 13:39 Rev Time 0.00
Received By wjolin Date 2012-10-04 Time 12:46 Sent To  
Notes
2012-10-04 13:39:35425 24TH STREET (2401 SPRUCE AVENUE)
 PERMIT #12030294
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NONE OF THE ARCHITECTURAL PLANS ARE SEALED BY THE
 ARCHITECT.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION AND CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 CONFIRM ALL EXISTING EXTERIOR EXIT DOORS ARE EQUIPPED
 WITH PANIC HARDWARE.
  
 EXPLAIN THE NOTE, "DOOR TO BE FIXED AND SEALED."
  
 PART OF THE ASSEMBLY OCCUPANCY APPEARS TO EXIT THROUGH
 THE BUSINESS OCCUPANCY. WHERE EXIT ACCESS FROM AN
 OCCUPANCY TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE
 OCCUPANCY SHALL BE TREATED AS A MIXED OCCUPANCY PER
 NFPA 101 SECTION 6.1.14.1.2.
  
 SEVERAL ASSEMBLY ROOMS ARE CALCULATED USING AN OCCUPANT
 LOAD FACTOR OF 15 SQ.FT. PER PERSON; HOWEVER, THERE
 DOES NOT APPEAR TO BE ANY TABLES/CHAIRS IN THESE
 LOCATIONS. AN OCCUPANT LOAD FACTOR OF 7 SQ.FT. PER
 PERSON MAY BE MORE APPROPRIATE.
  
 INDICATE WHY THE CLASSROOMS (108/112), CONFERENCE ROOM
 (113) AND BREAK AREA ARE CALCULATED WITH AN OCCUPANT
 LOAD FACTOR OF 20 SQ.FT. PER PERSON.
  
 NO INFORMATION PROVIDED FOR PHASE III. WILL THIS BE
 EMPTY SHELL SPACE OR STORAGE DURING PHASE I AND II?
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. FOR ISSUANCE OF A GENERAL BUILDING
 PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING
 CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 EACH FIRE-RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-01-04 Cont ID  
Sent By wjolin Date 2013-01-04 Time 09:08 Rev Time 0.00
Received By wjolin Date 2012-12-19 Time 09:06 Sent To  
Notes
2012-12-20 09:05:20C06

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-11 Cont ID  
Sent By lmartine Date 2012-12-11 Time 13:55 Rev Time 0.00
Received By lmartine Date 2012-11-02 Time 11:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-26 Cont ID  
Sent By shill Date 2012-10-26 Time 16:46 Rev Time 0.00
Received By shill Date 2012-09-19 Time 13:54 Sent To  
Notes
2012-09-21 13:58:28C--5

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-12-21 Cont ID  
Sent By H MOSER Date 2012-12-21 Time 11:32 Rev Time 0.00
Received By tgordon Date 2012-12-21 Time 10:37 Sent To  
Notes
2012-12-21 11:33:062007 FBC.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-12-12 Cont ID  
Sent By lmartine Date 2012-12-11 Time 13:25 Rev Time 0.00
Received By lmartine Date 2012-12-11 Time 13:25 Sent To  
Notes
2012-12-11 13:38:17*** DENIED ***
 1) PLAN M-1 SHOWS 5 LOCATIONS WERE DUCTS ARE
 PENETRATING 1 HR. FIRE RATED
 WALLS WITH NO FIRE DAMPERS, PLEASE REVISE MECH. PLAN TO
 COMPLY WITH 2007 FBC/M (B) 607.5.3.
 2) OUTDOOR AIR CALCULATIONS ON PLAN M-1 APPEAR TO BE
 INCORRECT, SEE 2007
 FBC/M 403.3 AND TABLE 403.3 OR SEE 403.3.2. PLEASE
 SUBMIT REVISED
 OUTDOOR AIR CAL'S. WITH CALCULATIONS FOR REVIEW BEFORE
 INSPECTION.
 **MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD INC.)
 **FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-10-22 Cont ID  
Sent By hmoser Date 2012-10-22 Time 14:41 Rev Time 0.00
Received By hmoser Date 2012-10-22 Time 13:03 Sent To  
Notes
2012-10-22 14:40:53PLANS DENIED
 1) SHOW RATED WALLS ON MECHANICAL PLANS
 PER SECTION 107 FBC AND 607.5.1 FIRE WALLS
 2) PROVIDE DETAILS ON CONDENSER STAND TO ROOF TIE DOWN
 AND CONDENSER TO STAND TIE DOWN.PER SECTION 301.12
 WIND RESISTANCE 2010 FBC (M)
 3) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3 FBC
 (M)
 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-12-27 Cont ID  
Sent By L WAGNER Date 2012-12-27 Time 14:29 Rev Time 0.00
Received By lwagner Date 2012-12-27 Time 14:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2012-11-20 Cont ID  
Sent By lwagner Date 2012-11-20 Time 09:07 Rev Time 0.00
Received By lwagner Date 2012-11-15 Time 09:09 Sent To  
Notes
2012-11-15 11:19:12NO PLUMBING DRAWINGS WERE FOUND WITH THIS SET OF PLANS.
 PER RAR
 SEPARATE PLUMBING APPLICATION, PLAN, REVIEW, AND PERMIT
 WILL BE REQUIRED.
  
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-10-03 Cont ID  
Sent By lwagner Date 2012-10-03 Time 13:45 Rev Time 0.00
Received By lwagner Date 2012-10-03 Time 12:26 Sent To  
Notes
2012-10-03 13:45:28FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET A-1.1: PER P-403.7 A UNISEX RESTROOM IS
 REQUIRED.
  
 2. SHEET A-10 PLEASE SHOW THE GRAB BARS IN THE REQUIRED
 AMBULITORY STALLS:
 FBC 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE
 PROVIDED, THEN AT LEAST ONE SHALL BE A STANDARD TOILET
 STALL COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE
 STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING
 WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES
 (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING
 DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D)
 AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16.
  
 3. NO PLUMBING DRAWINGS WERE FOUND WITH THIS SET OF
 PLANS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 3 Status P Date 2013-01-03 Cont ID  
Sent By ESCHNEID Date 2013-01-03 Time 09:45 Rev Time 3.00
Received By eschneid Date 2013-01-03 Time 09:45 Sent To  
Notes
2013-01-03 16:46:41PASSED W/PROVISOS
  
 1) A DUMPSTER IS REQUIRED FOR THIS SITE. THE CURRENT
 PLANS NO LONGER SHOW A DUMPSTER ON-SITE. PRIOR TO FINAL
 INSPECT 1) PROVIDE DUMPSTER ON-SITE OR 2) INSTALL A NEW
 ALLEY COMPACTOR.
  
 2) NO GLARE ALLOWED ONTO 25TH STREET. THE LIGHTING
 SHALL INCLUDE SHIELDING TO PREVENT GLARE INTO THE 25TH
 STREET RIGHT-OF-WAY
  
 3) THE MINI SPLIT ?CU-1? SHALL BE PAINTED TO MATCH THE
 COLOR OF THE BUILDING.
  
 4) THE FOLLOWING SEPARATE PERMITS ARE REQUIRED:
  
 A. PARKING LOT PERMIT, INCLUDING STRIPING.
 B. LANDSCAPE PERMIT.
 C. IRRIGATION PERMIT.
 D. FENCE PERMIT FOR THE GROUND MOUNTED A/C EQUIPMENT
 SCREEN WALL AND GATE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2012-11-30 Cont ID  
Sent By eschenid Date 2012-11-30 Time 13:12 Rev Time 2.00
Received By eschneid Date 2012-11-29 Time 16:39 Sent To  
Notes
2012-11-30 14:03:16FAILED
  
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 1) THE PARKING LOT REQUIRES A SEPARATE PERMIT. PLEASE
 CONSIDER USING THE D CURB INSTEAD OF THE WHEEL STOPS
 AND ALLOWING A TWO (2) FOOT OVERHANG TO PROVIDE SOME
 MORE GREEN AREA ON THE SITE. STAFF ACKNOWLEDGES THAT
 THE PLANS INCLUDE THE D CURB DETAIL, BUT THE SUGGESTION
 IS NOT TO HAVE A WHEEL STOP AND A D CURB, BUT RATHER
 MOVE THE D CURB IN FROM THE END OF THE PARKING SPACE
 AND INSTALL IT IN PLACE OF THE WHEEL STOP SO THAT SOD,
 NOT PAVING, IS OVERHUNG BY THE CAR. IF THE OWNER WISHES
 TO CONSTRUCT THE PARKING LOT WITH THE WHEEL STOP AND
 THE CURB AT EACH PARKING SPACE, THEN THE PLANS
 SUBMITTED AS PART OF THE PARKING LOT PERMIT WILL BE
 REVIEWED AS SUCH.
  
 2) THE LANDSCAPE REQUIRES A SEPARATE LANDSCAPE PERMIT.
  
 3) REPEAT COMMENT - THE SITE NO LONGER SHOWS A DUMPSTER
 ON-SITE. PLEASE PROVIDE WRITTEN VERIFICATION FROM THE
 SANITATION DEPARTMENT THAT NO DUMPSTER IS REQUIRED.
  
 4) REPEAT COMMENT - PROVIDE VERIFICATION THAT THE
 LIGHTING WILL INCLUDE SHIELDING TO PREVENT GLARE INTO
 THE 25TH STREET RIGHT-OF-WAY.
  
 5) REPEAT COMMENT - THE SITE PLAN DOES NOT SHOW THE
 PROVISION OF A/C EQUIPMENT, YET THE MECHANICAL AND
 ELECTRIC PLANS SHOW GROUND MOUNTED CONDENSING UNITS.
 ADDITIONALLY, THERE APPEARS TO BE A MINI SPLIT UNIT
 THAT IS LABELED AS CU-1 ON THE EAST SIDE OF THE
 BUILDING WHICH IS NOT SHOWN ON THE ELEVATIONS AND
 APPEARS TO IMPEDE THE ADA PARKING AISLE. THE NMUD
 REGULATIONS REQUIRE THAT MECHANICAL EQUIPMENT BE
 SCREENED FROM VIEW BY LANDSCAPING OR BUILT ELEMENTS
 DESIGN AS AN INTEGRAL PART OF THE BUILDING
 ARCHITECTURE. THIS NEEDS TO BE REFLECTED ON THE PLANS.
  
 6) THE WIDOWS WERE INCLUDED ON AN EARLIER PERMIT THAT
 EXPIRED AND IS NOW BEING REACTIVATED BY THIS PERMIT, SO
 PLEASE INCLUDE SHEET A-3.1 WHICH VERIFIED THAT THE
 GLAZING REQUIREMENTS WERE MET.
  
 7) PLEASE NOTE THAT COMMENTS NO. 1 AND 2., THE
 ADDITIONAL PERMITS, WILL BE INCLUDED AS A CONDITIONAL
 PERMIT IF THEY ARE NOT SUBMITTED PRIOR TO THE
 RESUBMITTAL TO ADDRESS THE OUTSTANDING COMMENTS LISTED
 ABOVE. THE CONDITIONAL PERMIT WOULD NEED TO BE
 SATISFIED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY/CERTIFICATE OF COMPLETION ON THIS PERMIT.
 STAFF HOPES THAT THE REQUIRED PERMITS ARE SUBMITTED
 PRIOR TO THE RESUBMITTAL SO THAT NO CONDITIONAL PERMIT
 IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2012-11-08 15:02:5611/8

Review Stop Z ZONING
Rev No 1 Status F Date 2012-10-11 Cont ID  
Sent By eschneid Date 2012-10-11 Time 09:24 Rev Time 3.00
Received By eschneid Date 2012-10-10 Time 16:11 Sent To  
Notes
2012-10-11 09:25:15FAILED
  
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 1) THE PARKING LOT REQUIRES A SEPARATE PERMIT. PLEASE
 CONSIDER USING THE D CURB INSTEAD OF THE WHEEL STOPS
 AND ALLOWING A TWO (2) FOOT OVERHANG TO PROVIDE SOME
 MORE GREEN AREA ON THE SITE.
  
 2) THE LANDSCAPE REQUIRES A SEPARATE LANDSCAPE PERMIT.
  
 3) THE SITE NO LONGER SHOWS A DUMPSTER ON-SITE. PLEASE
 PROVIDE WRITTEN VERIFICATION FROM THE SANITATION
 DEPARTMENT THAT NO DUMPSTER IS REQUIRED.
  
 4) PROVIDE VERIFICATION THAT THE LIGHTING WILL INCLUDE
 SHIELDING TO PREVENT GLARE INTO THE 25TH STREET
 RIGHT-OF-WAY.
  
 5) THE SITE PLAN DOES NOT SHOW THE PROVISION OF A/C
 EQUIPMENT, YET THE MECHANICAL PLANS SHOW GROUND MOUNTED
 CONDENSING UNITS. THE NMUD REGULATIONS REQUIRE THAT
 MECHANICAL EQUIPMENT BE SCREENED FROM VIEW BY
 LANDSCAPING OR BUILT ELEMENTS DESIGN AS AN INTEGRAL
 PART OF THE BUILDING ARCHITECTURE. THIS NEEDS TO BE
 REFLECTED ON THE PLANS.
  
 6) VERIFICATION BY DETAILS ON THE PLANS SHALL BE
 PROVIDED THAT THE GLAZING ALONG 24TH STREET AND SPRUCE
 AVENUE CONFORMS TO EITHER THE CURRENT NMUD REGULATIONS
 OR THE APPROVED VARIANCE REQUIREMENTS LISTED BELOW
 (SIMILAR COMMENT FOR EXPIRED PERMIT 09070711):
  
 A FORTY ONE (41) PERCENT VARIANCE FROM THE REQUIREMENTS
 OF ARTICLE VII, SECTION 94-213(D)(5) TO CREATE A TOTAL
 CLEAR GLAZED AREA OF FIVE HUNDRED FORTY (540) SQUARE
 FEET [FORTY ONE (41) PERCENT] OF THE BUILDING'S FRONT
 FACADE. THERE WAS A MOTION FOR APPROVAL WITH A FINAL
 VOTE OF FOUR (4) MEMBERS SUPPORTING THE MOTION AND NO
 MEMBERS OPPOSING THE MOTION, WITH THE FOLLOWING
 CONDITION:
 A. TWO (2) ADDITIONAL WINDOWS, WITH EACH BEING BETWEEN
 TWO (2) AND EIGHT (8) FEET ABOVE THE GROUND AND TEN
 (10) FEET WIDE, SHALL BE PLACED IN THE OFFICE SPACE AT
 THE SOUTHEAST SECTION OF THE BUILDING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.