Plan Review Details - Permit 12030280
Plan Review Stops For Permit 12030280
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2012-03-22 Time   Rev Time  
Received By   Date 2012-03-22 Time   Sent To M
Notes
2012-03-22 15:13:4003/22/12
  
 SENT TO MECHANICAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-26 Cont ID  
Sent By hmoser Date 2012-03-26 Time 11:08 Rev Time 0.00
Received By hmoser Date 2012-03-13 Time 15:15 Sent To  
Notes
2012-03-19 15:16:02SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-03-27 Cont ID  
Sent By hmoser Date 2012-03-27 Time 14:34 Rev Time 0.00
Received By hmoser Date 2012-03-27 Time 14:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-03-26 Cont ID  
Sent By hmoser Date 2012-03-26 Time 11:08 Rev Time 0.00
Received By hmoser Date 2012-03-26 Time 09:29 Sent To  
Notes
2012-03-26 11:08:33PLANS DENIED
 1) SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR
 FIRE SUPPRESSION TO HOOD.
 2) CAN NOT READ DETAILS FOR CURB'S TO ROOF TIE DOWN PER
 SECTION 106.1.3 FBC 2007
 3) REFER TO SECTION 506.3.12.1 TERMINATION ABOVE THE
 ROOF. 2007 FBC (M)
 4) REFER TOSECTION506.3.6 GREASE DUCT CLEARANCE 2007
 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]