Plan Review Details - Permit 12030240
Plan Review Stops For Permit 12030240
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-07-26 Cont ID  
Sent By jwitmer Date 2012-07-26 Time 09:01 Rev Time 0.00
Received By jwitmer Date 2012-07-23 Time 10:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-16 Cont ID  
Sent By jwitmer Date 2012-03-20 Time 16:40 Rev Time 0.00
Received By jwitmer Date 2012-03-20 Time 16:42 Sent To  
Notes
2012-04-02 15:05:59BUILDING PLAN REVIEW
 PERMIT: 12030240
 ADD: 6701 N JOG RD
 CONT: LEBOLO CONSTRUCTION
 TEL: (561)541-0191
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE BUILDING CODE SUMMARY SHEET 720-A5-100 INDICATES
 THIS BUILDING IS TO BE FIRE SPRINKLERED, THE INDEX
 SHEET 720-G0-002 DOES NOT INDICATE ANY FIRE SPRINKLER
 PLANS FOR THE BUILDING ITSELF. 2007/09 FBC-B MINIMUM
 PLAN REVIEW CRITERIA FOR BUILDINGS 106.3.5.1.1(5) FIRE
 SUPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE
 SPRINKLERS .
  
 2) 109.3.7(1) SPECIAL INSPECTOR IS REQUIRED FOR ALL
 TYPE I OR TPYE II BUILDINGS . FBC* 109.3.7 RESIDENT
 INSPECTOR. SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO KEN CONRAD , DIRECTOR OF THE RESIDENT
 (SPECIAL) INSPECTOR PROGRAM. A RESIDENT INSPECTOR
 PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO ONE OR
 MORE OF THE FOLLOWING: - BUILDINGS/ADDITIONS OF TYPE I
 OR II CONSTRUCTION. CONTACT KEN CONRAD AT (561)
 805-6666.
  
 3) THE PLANS DO PROVIDE THE MINIMUM SAFE BEARING VALUE
 FOR THE SOIL TO BE 4,000 PSF (SHEET 720-S3-101), NO
 SOILS REPORT INDICATING HOW TO OBTAIN THE MINIMUM SAFE
 BEARING FOR THIS BUILDING. 2007/09 FBC-B 1802.6
 REPORTS.
  
 4) A SEPERATE PERMIT APPLICATION REVIEW AND ASSOCIATED
 FEES SHOULD BE MADE FOR THE FUEL STATION FOUND ON SHEET
 720-S4-101. PLEASE PROVIDE ADDITIONAL INFORMATION AS TO
 WHAT TYPE OF TANK WILL BE INSTALLED. PLEASE REVIEW
 2007/09 FBC-B 414.6. OUTDOOR STORAGE, DISPENSING AND
 USE. THE OUTDOOR STORAGE , DISPENSING AND USE OF
 HAZARDOUS MATERIALS SHALL BE IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
 5) SHEET 720-S6-000. THIS STRUCTURAL SHEET INDICATES
 THE BUILDING DESIGN TO THE:
 2007/09 FBC-B ASCE 7-05
 140 MPH WIND ZONE
 1.15 IMPORTANCE FACTOR
 PLEASE PROVIDE WHY THE LOWER ROOF HAS A FACTORY-MUTUAL
 FM-105 WIND RATING M-1 TO M-3 & M-5 TO M-9 AAND THE
 UPPER ROOF A FACTORY-MUTUAL FM-120 WIND RATING FROM M-3
 TO M-5?
 IT WOULD APPEAR THIS TO BE ANOTHER WIND DESIGN FROM
 ASCE 7-05? ADDITIONAL INFORMATION IS REQUIRED.
  
 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS, TRANSLUCENT WALL PANELS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 8) THE CODE SUMMARY / LIFESAFETY SHEET INDICATES PART
 OF THE BUILDING AS A S-2 OCCUPANCY, PLEASE PREOVIDE
 WHAT TYPES OF ITEMS WILL BE STORED IN THE WAREHOUSE
 PORTION AND WHAT WOULD BE STORED INTHE INSULATED
 STORAGE AREA? AND AT WHAT AMOUNTS?
  
 9) THE LIFE SAFETY SHEET DOES NOT INDICATE ANY EGRESS
 PATHS IN THE WAREHOUSE AREA NOR ANY EMERGENCY LIGHTING,
 2007/09 FBC TABLE 1006 INDICATES AAN EXCEPTION THAT IS
 WHEN THIS IS ONLY DAYLIGHT OPERATIONS, WILL THIS
 FACILITY BE OCCUPIED AT NIGHT?
  
 10) PRE-ENGINEERED EQUIPMENT MEZZANINE, FOUND ON SHEET
 720-A3-104 WILL NEED TO PROVIDE MANUFACTURERS
 SPECIFICATION ON THE FRAMING SYSTEM, FLOORING SYSTEM,
 STAIR/ LADDER AND GUARDRAIL SYSTEM AS WELL AS THE SAFE
 ALLOWABLE FLOOR LOADING OF THE MEZZANINE. FBC-B
 110.4.2.
  
 11) SHEET 720-A1-101 INDICATES EXTERIOR BOTTLE STORAGE,
 PLEASE PROVIDE THE TYPES OF GASSSES, THE SIZE OF THE
 CONTAINERS, IN CUBIC FT. 2007/09 FBC-B 2007/09 FBC-B
 414.6. OUTDOOR STORAGE, DISPENSING AND USE. THE OUTDOOR
 STORAGE , DISPENSING AND USE OF HAZARDOUS MATERIALS
 SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-07-05 Cont ID  
Sent By rlecky Date 2012-07-05 Time 10:44 Rev Time 0.00
Received By rlecky Date 2012-07-05 Time 09:11 Sent To  
Notes
2012-07-05 10:08:28SEE THE RESPONSE LETTER FROM THE ENGINEER WHICH
 CONTAINS ADDITIONAL INFORMATION AND CLARIFICATION ON
 THE PREVIOUS ELECTRIC REVIEW COMMENTS. RL
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-04-10 Cont ID  
Sent By rlecky Date 2012-04-10 Time 17:53 Rev Time 0.00
Received By rlecky Date 2012-03-30 Time 15:59 Sent To  
Notes
2012-04-10 17:55:0012030240
 6701 N. JOG ROAD
 SWA WAREHOUSE
  
 E3-001
 VERIFY THE 112 ? KVA TRANSFORMERS OR LARGER ARE LOCATED
 WITHIN FIRE-RESISTANT ROOMS WITH A ONE HOUR FIRE RATING
 OR COMPLY WITH THE NEC EXCEPTIONS. NEC 450.21 (B)
 PROVIDE A GROUNDED CONDUCTOR WHICH MAY BE BROUGHT TO
 THE SERVICE EQUIPMENT AT THE MAINTENANCE BUILDING AND
 THE VISITOR?S CENTER. NEC 250.24 (C)
 IF A HIGH IMPEDANCE GROUNDING SYSTEM IS TO BE UTILIZED
 A DETAIL IS REQUIRED. NEC 250.36
 A GFCI GENERAL PURPOSE RECEPTACLE IS REQUIRED AT AN
 ACCESSIBLE LOCATION FOR THE SERVICE OF HEATING, AIR
 CONDITIONING, AND REFRIGERATION EQUIPMENT. NEC 210.63
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING CODE 711.1
 CLARIFY HOW THE TRANSFER FROM NORMAL POWER TO EMERGENCY
 POWER WILL BE MANAGED. CLARIFY HOW THE GROUNDING AND
 BONDING BETWEEN THE TWO SYSTEMS WILL BE HANDLED
 INCLUDING THE MAIN BONDING JUMPER TO THE GROUNDED
 CONDUCTOR. NEC 215.5. 250
 E7-002
 PROVIDE DETAIL FOR BONDING METAL PULL BOX COVERS. NEC
 314.30(D)
 PROVIDE PULL BOX DIMENSIONS. NEC 314
 E4-101
 ALL RECEPTACLES LOCATED OUTDOORS IN BATHROOMS OR WITH
 IN SIX FEET OF A SINK MUST BE GFCI PROTECTED. NEC 210.8
 PROVIDE A DETAIL WHICH ILLUSTRATES THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED AS REQUIRED FOR THE ELECTRICAL EQUIPMENT AND
 PANEL BOARDS. NEC 110.26, 240.24, 408.17
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT WHICH INCLUDES THE SPECIFIC WORDING REGARDING
 THE SIZE AND TYPE OF HAZARDS. NEC 110.22, 110.16
 E4-103
 PROVIDE DIMENSIONS FOR THE DUCT BANK. NEC 310.16
 PROVIDE ELECTRICAL DETAIL FOR FUELING STATION WIRING
 METHODS. NEC 215.5
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, LIGHTNING PROTECTION, NURSE CALL, VOICE
 AND DATA.
 A SEPARATE PERMIT AND PLANS WITH WIND LOAD ENGINEERING
 FOR POLES, BASES AND FIXTURES IS REQUIRED.
  
 ROBERT LECKY, CBO
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2012-08-10 Cont ID  
Sent By mgonzale Date 2012-08-10 Time   Rev Time 1.00
Received By mgonzale Date 2012-08-10 Time   Sent To I
Notes
2012-08-10 06:12:01PROJECT IS UNDER REVIEW WITH ESD.
 PBCHD PERMIT OBTAINED.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2012-07-23 Cont ID  
Sent By mgonzale Date 2012-07-23 Time   Rev Time 0.50
Received By mgonzale Date 2012-07-23 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2012-04-12 Cont ID  
Sent By mgonzale Date 2012-04-12 Time   Rev Time 1.00
Received By mgonzale Date 2012-04-12 Time   Sent To  
Notes
2012-04-12 15:45:53PLEASE ADDRESS PLANNING'S COMMENTS AND ENGINEERING WILL
 SIGN OFF,
 PROJECT WAS REVIEWED UNDER ENGINEERING SITE DEVELOPMENT
 AND IS CURRENTLY UNDER PERMITTING
 WITH PALM BEACH COUNTY HEALTH DEPARTMENT.
  
 PROVIDE LETTER FROM ENGINEER SIGNED AND SEALED THAT
 INCLUDES.
 TOTAL SITE (DEVELOPED UNDER THIS PERMIT)
 TOTAL PERVIOUS AREA
 TOTAL IMPERVIOUS AREA.
 (MAY BE EMAILED TO [email protected])
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-03-27 Cont ID  
Sent By ddaniels Date 2012-03-27 Time 14:05 Rev Time 0.00
Received By ddaniels Date 2012-03-27 Time 14:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2012-08-23 Time   Rev Time 0.00
Received By rregueir Date 2012-06-19 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-10 Cont ID  
Sent By rregueir Date 2012-05-10 Time 11:01 Rev Time 0.00
Received By rregueir Date 2012-03-14 Time 15:42 Sent To  
Notes
2012-03-20 15:42:59DIGITAL PLANS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-05-10 Cont ID  
Sent By rregueir Date 2012-05-10 Time 11:01 Rev Time 0.00
Received By rregueir Date 2012-03-20 Time 15:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-04-12 Cont ID  
Sent By lwagner Date 2012-04-12 Time 11:11 Rev Time 0.00
Received By lwagner Date 2012-03-27 Time 09:43 Sent To  
Notes
2012-04-12 11:13:52HOSE BIBB SHALL HAVE SEPARATE VALVES.
 2 WAY C.O. REQUIRED AT BUILDING SEWER.
 SINK COUNTER 34" AFF FOR BREAK SINK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2012-08-23 Cont ID  
Sent By rregueir Date 2012-08-23 Time 14:43 Rev Time 0.00
Received By rregueir Date 2012-08-23 Time 14:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-07-05 Cont ID  
Sent By eschneid Date 2012-06-26 Time 09:16 Rev Time 2.00
Received By eschneid Date 2012-06-26 Time 09:16 Sent To  
Notes
2012-06-26 10:26:07PASSED W/PROVISOS
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE SITE LIGHTING,
 PARKING STRIPING, LANDSCAPE, SIGNAGE, FENCING, FUEL
 STATION, BICYCLE RACKS AND PHOTOVOLTAIC CARPORTS.
  
 2) THE PARKING, LANDSCAPING AND BICYCLE RACKS SERVING
 THE MAINTENANCE BUILDING SHALL BE INSTALLED AND PASS
 FINAL INSPECTION PRIOR TO THE C.O. OF THE MAINTENANCE
 BUILDING.
  
 3) PRIOR TO THE C.O. FOR THE MAINTENANCE BUILDING, A
 MINOR SITE PLAN AMENMDMENT IS REQUIRED FOR ALL CHANGES
 TO THE MAINTENANCE BUILDING AND THE SURROUNDING AREA.
  
 4) PLEASE NOTE: THE FUEL STATION REQUIRES A SCREEN WALL
 AND LANDSCAPING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-04-04 Cont ID  
Sent By eschneid Date 2012-04-04 Time 16:08 Rev Time 3.00
Received By eschneid Date 2012-04-04 Time 16:08 Sent To  
Notes
2012-04-04 16:10:10FAILED
  
 PLEASE RESPOND IN WRITING.
  
 1) PROVIDE THE FOLLOWING - THE SITE PLAN APPROVAL
 LETTER CONTAINED THE CONDITION THAT PRIOR TO ISSUANCE
 OF THE FIRST BUILDING PERMIT, THE APPLICANT SHALL
 PREPARE A CONSTRUCTION SITE SECURITY AND MANAGEMENT
 PLAN FOR APPROVAL BY THE CITY OF WEST PALM BEACH POLICE
 DEPARTMENT CPTED OFFICIAL.
 A. AFTER SITE CLEARING AND PLACEMENT OF CONSTRUCTION
 TRAILERS, THE DEVELOPER/PROJECT MANAGER SHALL INSTITUTE
 SECURITY MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES
 FOR THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT
 BE LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY, TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING AND OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
 B. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED UNIT
 DEVELOPMENT.
 C. PROPERTY SHALL BE POST "NO TRESPASSING" SIGNS EVERY
 500 FEET AROUND THE PERIMETER OF THE SITE.
  
 2) WHAT EXACTLY IS LIMIT OF WORK? MORE PLANS SITE
 RELATED PLANS WERE SUPPLIED THAN JUST MAINTENANCE
 BUILDING. WHAT PARKING WILL BE INSTALLED AS PART OF
 THIS BUILDING?
  
 3) STAFF REVIEWED THE ENTIRE PLAN SUBMITTAL AND NOTED
 THE FOLLOWING SITE PLAN CHANGES. A SITE PLAN AMENDMENT,
 WHICH CONTAINS ALL CHANGES, WILL BE REQUIRED PRIOR TO
 THE C.O. OF THE FIRST BUILDING ON THE SITE.
 A. THE SIDEWALK ON NORTH AND EAST SIDES OF BUILDING
 HAVE BEEN REMOVED. WHY HAS THE SIDEWALK BEEN REMOVED AS
 THE DOORS STILL REMAIN IN THE SAME LOCATIONS?
 B. THE MAINTENANCE BUILDING ELEVATIONS HAVE CHANGED.
 C. THE VISITOR?S CENTER HAS A DIFFERENT CONFIGURATION.
 D. THE EASTERN ACCESS ROAD HAS A DIFFERENT
 CONFIGURATION.
 E. THE SETTLING BASIN ON WEST SIDE OF ASH MANAGEMENT
 BUILDING HAS DIFFERENT DIMENSIONS.
  
 4) THE EAST ELEVATION (FRONTING JOG) OF THE MAINTENANCE
 BUILDING WAS APPROVED WITH WINDOWS. THE TRANSLUCENT
 WALL PANELS ARE NOT WINDOWS. THE NEW ELEVATIONS HAVE
 REDUCED THE AESTHETICS OF THE EAST ELEVATION AND SHALL
 BE CORRECTED THE APPROVED ELEVATIONS.
  
 5) PROVIDE BIKE RACK DIMENSION ON THE SITE PLAN.
  
 6) THE FUEL STATION REQUIRES A SCREEN WALL AND
 LANDSCAPING.
  
 7) WHAT IS TIMELINE FOR THE LANDSCAPE PLAN SUBMITTAL
 FOR PLANNING REVIEW? THE BUILDINGS WILL NOT GET C.O.S
 WITHOUT LANDSCAPE.
  
 8) SEPARATE PERMITS WILL BE REQUIRED FOR SITE LIGHTING,
 PARKING STRIPING, LANDSCAPE, SIGNAGE, AND FENCING.
  
 9) PLEASE NOTE THAT THE SITE PLAN APPROVAL CONTAINED
 THE FOLLOWING ADDITIONAL CONDITIONS:
  
 1. THE PHOTOVOLTAIC AREAS SHALL BE APPROVED DURING THE
 BUILDING PERMIT PROCESS. THE DESIGN SHALL NOT CREATE
 INTERFERENCE WITH PARKING SPACES OR TREES.
  
 2. SHEET 700-CS-002 "MISCELLANEOUS CIVIL DETAILS"
 CREATED BY CDM, SHALL BE CORRECTED AS FOLLOWS FOR THE
 PERMIT SET SUBMITTED TO THE BUILDING DIVISION AND THE
 ENGINEERING SERVICES DEPARTMENT:
 A. BICYCLE RACK. THE RACK NEEDS TO BE 3 FEET FROM FRONT
 OF THE PAD. THIS IS TO ALLOW MULTIPLE LOCK POINTS
 WITHOUT OVERHANGING THE FRONT OF THE PAD.
 B. PARKING SPACE DETAIL. THE TYPICAL PARKING SPACE
 DETAIL IS INCORRECT. THE REQUIRED 12 INCHES BETWEEN THE
 DOUBLE STRIPES IS NOT SHOWN. PLEASE REFER TO THE
 PARKING STALL DETAIL INCLUDED IN FIGURE XV-2 OF ARTICLE
 XV "PARKING" OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
 C. WHEEL STOP DETAIL. THE WHEEL STOP DETAIL IS
 INCORRECT. THE CITY STANDARD IS SINGLE SIDED IN
 ACCORDANCE WITH SECTION 94-443(C)(5)B AND FIGURE XIV-2
 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS.
 D. VEHICLE OVERHANG. THE TYPICAL PARKING SPACE DETAIL
 SHOWS THE OVERHANG OF TWO (2) FEET PLUS THE CURB WIDTH.
 FIGURE XIV-2 PROVIDES THAT THE ENTIRE OVERHANG BE TWO
 (2) FEET, INCLUDING THE CURB. THE MULCH AREA SHALL BE
 REDUCED AND THE PLANTING AREA INCREASED ACCORDINGLY TO
 MEET THIS STANDARD.
  
 10) THE WHEEL STOPS UNDER THE PHOTOVOLTAIC CARPORT
 SHALL BE VERIFIED AT 2 FEET FROM HEAD OF SPACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
  
  
  