| 2012-03-21 16:34:22 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 12030044 |
| | ADD: 4847 FRED GLADSTONE |
| | CONT: THE WHITING TURNER CO. |
| | TEL: (954)776-0800 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) PLEASE PROVIDE (3) SURVEY INDICATING WHAT FLOOD |
| | ZONE THIS NEW BUILDING WILL BE LOCATED. WPB ADMIN. |
| | 106.3.5.1. |
| | |
| | 1B) THERE ARE SEPARATE BUILDINGS AND FEATURES THAT ARE |
| | PART OF THIS PERMIT SET OF PLANS. SEPARATE ADDRESSES, |
| | PERMITS (PERMIT APPLICATIONS) AND ASSOCIATED FEES WILL |
| | BE REQUIRED FOR RECORD KEEPING PURPOSES (INSPECTIONS). |
| | |
| | 2) PLEASE PROVIDE (3) ORIGINAL SOILS REPORTS 2007/09 |
| | FBC-B1802.6. |
| | |
| | 3) THIS BUILDING QUALIFIES FOR A SPECIAL RESIDENT |
| | INSPECTOR 109.3.7 WPB ADMIN.: |
| | A) TYPE II CONSTRUCTION |
| | B) FOR BUILDINGS WITH AN AREA GREATER THAN 20,000 |
| | SQUARE FEET |
| | C) FOR BUILDINGS GREATER THAN 2 STORIES IN HEIGHT |
| | FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 4 SHEET A101, LIFE SAFETY SHEET G-101 AND A002 |
| | PARTITION TYPES DO NOT MATCH UP: |
| | |
| | 4A) STAIR # 3 OR ROOM # S103 WALL TAG TYPE F01 NO FIRE |
| | RATING VERSES G-101. FBC-B 1020.1. |
| | |
| | 4B) STAIR # 3 WALL TAG MISSING, RATING FBC-B 1020.1. |
| | |
| | 4C) STAIR # 3 SEE DETAIL # 1/ A451, WRONG PLAN UP |
| | LOADED, A551. |
| | |
| | 4D) WALL TAG TYPE F01 IS INDICATED DRYWALL ON ONE SIDE, |
| | SEE |
| | FL. BOAF INFORMAL INTERPRETATIONS 6341 REQUIRING |
| | DRYWALL ON BOTH SIDES OF THE WALL. |
| | |
| | 4E) COMMON STATEMENT FOR ALL FLOORS!!! SHEET A101 |
| | VERSES G-101, LIFE SAFETY SHEETS INDICATE THE CORRIDOR |
| | WALLS TO BE SMOKE PARTITIONS AS REQUIRED BY SECTION |
| | 2007/09 FBC-B 407.3 SMOKE PARTITIONS IN ACCORDANCE WITH |
| | SECTION 710 SMOKE PARTITIONS. |
| | PLEASE SEE BOAF INFORMAL INTERPRETATION # 6341. |
| | PLEASE PROVIDE ON SHEET A002 A HEADING TYPE FOR SMOKE |
| | PARTITIONS AND SMOKE BARRIER WALLS AS IS PROVIDED FOR |
| | FIRE RATED WALLS, ON THIS IDENTIFY WALL RATINGS. |
| | COMMON STATEMENT FOR ALL FLOORS!!! SHEET A101 VERSES |
| | G-101, LIFE SAFETY SHEETS INDICATE THE CORRIDOR WALLS |
| | TO BE SMOKE PARTITIONS AS REQUIRED BY SECTION 2007/09 |
| | FBC-B 407.3 SMOKE PARTITIONS IN ACCORDANCE WITH SECTION |
| | 710 SMOKE PARTITIONS. PLEASE PROVIDE ON SHEET A002 A |
| | HEADING TYPE FOR SMOKE PARTITIONS AND SMOKE BARRIER |
| | WALLS AS IS PROVIDED FOR FIRE RATED WALLS, ON THIS |
| | IDENTIFY WALL RATINGS. |
| | |
| | |
| | 4F) FIRE/ SMOKE PARTITIONS INSPECT 2007/09 FBC-B |
| | 420.3.10.21 WHERE IT IS NOT POSSIBLE TO INSPECT |
| | FIRE/SMOKE PARTITIONS BECAUSE OF THE FIRE-TESTED |
| | MEMBRANE, FIRE-RATED ACCESS PANELS SHALL BE INSTALLED |
| | ADJACENT TO EACH SIDE OF THE SMOKE PARTITIONS AT |
| | INTERVALS NOT EXCEEDING 30 FEET (9.00 M) AND IN SUCH |
| | LOCATIONS AS NECESSARY TO VIEW ALL SURFACES OF THE |
| | PARTITION. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, |
| | SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING. SUCH IDENTIFICATION SHALL BE ABOVE ANY |
| | DECORATIVE CEILING AND IN CONCEALED SPACES. SUGGESTED |
| | WORDING FOR A FIRE/SMOKE PARTITION IS AS FOLLOWS: "FIRE |
| | AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| | |
| | |
| | 4G) THIS WILL BE A COMMON STATEMENT FOR ALL SLEEPING |
| | UNITS FOR ALL COMPARTMENTS ON ALL FLOORS, THIS SHEET |
| | NOR IF SHEETS INDICATE HOW MANY OCCUPANTS ARE IN A ROOM |
| | NOR IS THERE A FURNITURE LAYOUT THAT WILL ALLOW FOR |
| | CODE COMPLIANCE FOR SECTION 403.2.2 & 403.2.3 FOR UNIT |
| | TYPES A-E. |
| | |
| | 4H) SMOKE COMPARTMENT/ SMOKE BARRIER FBC-B 407.4 WALL |
| | MISSING 1 HOUR FIRE RATING ON THIS SHEET AND A002, WALL |
| | TYPE A01 MISSING 1 HOUR FIRE RATING. SEE G-101. |
| | |
| | 4I) COMMON TO ALL FLOORS. ELEVATOR SHAFT WALLS SHALL BE |
| | CONSTRUCTED IN ACCORDANCE WITH FBC-B 706.5. |
| | |
| | 4J) COMMON TO ALL FLOORS VERTICAL EXIT STAIRWELL. |
| | MISSING WALL IDENTIFICATION TAG. |
| | G-101 INDICATES A TWO HOUR FIRE RATING. FBC-B 1020.1. |
| | |
| | 4K) STAIRWELL S101 EXIT DOES NOT DISCHARGE AT THE |
| | EXTERIOR OF THE BUILDING. IT ALSO DOES NOT MEET THE |
| | REQUIREMENTS OF A VESTIBULE FBC 1024.1. WALL RATINGS? |
| | |
| | 4L) ROOM 166, DOOR # 166 PLEASE NOTE THAT ON SHEET THE |
| | DOOR SCHEDULE THE HARDWARE IS NOT SPECIFIED, FBC-B |
| | 420.3.3.8 LOCKABLE DOOR IS REQUIRED. |
| | |
| | |
| | |
| | |
| | 4M) ROOM 166 WALL TAG M03 DETAIL IS MISSING ON SHEET |
| | A002. G-101 INDICATES THIS WALL IS PART OF THE SMOKE |
| | PARTITION REQUIREMENTS FOR CORRIDOR. FBC 407.3/ 710. |
| | |
| | 4N COMMENT COMMEND TO ALL FLOORS. 2007/09 FBC-B |
| | 420.3.2.6 DOORS TO RESIDENT TOILET ROOMS SHALL BE SIDE |
| | HINGED. PLEASE ALSO NOTE THE HARDWARE SCHEDULE DOES NOT |
| | INDICATE TYPE OF HARDWARE THAT WOULD MEET THE |
| | ACCESSIBILITY CODE 11-4.13.9. |
| | |
| | 4O) COMMENT COMMON TO ALL FLOORS. 2007/09 FBC-B |
| | 420.3.2.7 EACH RESIDENT SHALL HAVE A WARDROBE, LOCKER |
| | OR CLOSET FOR EACH RESIDENT. |
| | |
| | |
| | 4P) THIS COMMENT IS FOR ALL DINING AREAS FOR ALL |
| | FLOORS. PLEASE PROVIDE THE SQUARE FOOT AREA OF EACH |
| | DINING AREA AND THE AMOUNT OF RESIDENTS TO BE SERVED. |
| | 2007/09 FBC ?B 420.3.4.1. |
| | |
| | 4Q) PLANS DO NOT INDICATE COMPLIANCE WITH 2007/09 FBC-B |
| | 420.3.4.4 A BARBER/BEAUTY ROOM SHALL BE PROVIDED WITH |
| | FACILITIES AND EQUIPMENT FOR RESIDENT HAIR CARE AND |
| | GROOMING. THE AREA OF THE ROOM SHALL BE A MINIMUM OF |
| | 200 SQUARE FEET (18.58 M2) WITH THE LEAST DIMENSION OF |
| | 12 FEET (3.66 M). |
| | |
| | 4R) ROOM 130C SOILED UTILITY 2 OF THE WALL |
| | IDENTIFICATION TAGS ARE A01 PLEASE REVIEW G-101 |
| | REFERENCING A 1-HOUR WALL RATING. FBC-B 420.3.3.6/ SEE |
| | REQUIREMENTS FROM NFPA 101 HAZARDOUS AREAS LIFE SAFETY |
| | CODE ADOPTED BY THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 4S) COMMENT COMMON TO ALL FLOORS. PROVIDE COMPLIANCE |
| | WITH: |
| | 2007/09 FBC-B 420.3.3.13 STORAGE ALCOVE SPACE FOR A |
| | MINIMUM OF ONE WHEELCHAIR AND ONE STRETCHER SHALL BE |
| | PROVIDED IN AN AREA LOCATED AWAY FROM NORMAL TRAFFIC. |
| | |
| | 4T) STAIRWELL # 2 WALL IDENTIFICATION TAG INDICATES |
| | TYPE F, STEEL STUD WALL PLANS APPEAR TO BE A BLOCK WALL |
| | PLEASE PROVIDE WALL TYPE AND COMPLIANCE WITH FBC-B |
| | 1020.1. |
| | |
| | 4U) WINDOW HAZARDOUS LOCATION FBC-B 2406.3 (5) 5. |
| | GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, |
| | WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS. |
| | GLAZING IN ANY PORTION OF A BUILDING WALL ENCLOSING |
| | THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE |
| | GLAZING IS LESS THAN 60 INCHES (1524 MM) ABOVE A |
| | STANDING SURFACE. |
| | |
| | 4V) ROOM 172 A DOOR MAY REQUIRE 12" LATCH SIDE OF DOOR |
| | IN HALLWAY. NOTE DOOR SCHEDULE DOES NOT INDICATE |
| | HARDWARE. |
| | IF DOOR IS EQUIPPED WITH BOTH A DOOR CLOSER AND LATCH A |
| | CLEARANCE OF 112 INCHES IS REQUIRED. |
| | |
| | 5) SHEET A-104 : |
| | |
| | 5A) THE AREA OF THE GYMNASIUM IS APPROX 5340 SQ FT. |
| | SHEET G-0011 CODE SUMMARY DOES NOT PROVIDE THE SQUARE |
| | FOOTAGE PER FLOOR BUT IS INDICATING THE AREA INCREASE |
| | ALLOWED PER STORY IS 47,264. G101 DOES PROVIDE THE AREA |
| | OF THE THREE SMOKE COMPARTMENTS, TOTALING TO 36,565 |
| | SQUARE FEET. THE AREA OF THE GYM IS OVER 10% OF THE |
| | FLOOR AREA (ACCESSORY OCCUPANCIES 508.3.1.) ACCESSORY |
| | OCCUPANCIES SHALL BE CLASSIFIED IN ACCORDANCE WITH |
| | SECTION 302.1. GYMNASIUMS ARE CLASSIFIED AS AN A-3 |
| | OCCUPANCY FBC-B TABLE 508.3.3 WOULD REQUIRE 1 HOUR |
| | SEPARATION BETWEEN THE I-2 OCCUPANCY AND THE A-3 |
| | GYMNASIUM WITH OPENING PROTECTION IN ACCORDANCE WITH |
| | FBC-B TABLE 715.4. |
| | |
| | 5B) FL BC-B 11-6.1(3) LONG-TERM CARE FACILITIES AND |
| | NURSING HOMES. AT LEAST 50 PERCENT OF PATIENT BEDROOMS |
| | AND TOILETS, AND ALL PUBLIC USE AND COMMON USE AREAS |
| | ARE REQUIRED TO BE DESIGNED AND CONSTRUCTED TO BE |
| | ACCESSIBLE. |
| | IT APPEARS THAT THE BATHROOM 196A IS NOT ACCESSIBLE. |
| | |
| | 5C) STORAGE ROOM 194A, LINEN STORAGE 190C, HOUSE |
| | KEEPING 194B & SOILED LINEN ROOM 190B DO NOT INDICATE |
| | ANY SMOKE AND OR FIRE RATINGS . |
| | |
| | 5D) THERE IS AN UNIDENTIFIED AREA THAT APPEARS TO BE A |
| | RECEPTION COUNTER, ADDITIONAL INFORMATION IS REQUIRED, |
| | 106.1.2/ 420.3.6.2. |
| | |
| | 6) SHEET G102: |
| | |
| | 6A) SMOKE COMPARTMENT WALL THAT SEPARATES COMPARTMENTS |
| | A/ B. WALL TYPE A01 & F01 BOTH ARE INDICATED AS NONE |
| | FIRE RATED. SMOKE COMPARTMENT WALLS REQUIRED BY 407.4 |
| | SHALL BE IN ACCORDANCE WITH 709, 709.3 REQUIRES A 1 |
| | HOUR SEPARATION CONTINUOUS FROM OUTSIDE OF WALL TO |
| | OUTSIDE OF WALL. |
| | |
| | 6B) SATELLITE MAINTENANCE ROOM THE DOOR IS 45 MINUTE |
| | FIRE RATED BUT THE WALL DESIGNATION TAG A)! NO FIRE |
| | RATING. SEE G102 1 HR FIRE RATED. |
| | |
| | 6C) CENTRAL STORAGE: G102 INDICATES THESE WALLS ALSO 1 |
| | HOUR FIRE RATED WALLS. |
| | |
| | 6D) ELEVATOR SHAFT WALL TAG DESIGNATION (F01) AS WELL |
| | AS STAIRWELL (STAIR # 1) WALLS 2 HRS IF FOUR STORIES OR |
| | MORE. FBC-B 1020.1. |
| | |
| | 6E) SOILED UTILITY ROOM # 230C G102 INDICATES THE 1 |
| | HOUR FIRE RATED WALLS FBC-B 420.3.3.6 NFPA 101 |
| | CLASSIFIES AS HAZARDOUS LOCATION . |
| | |
| | 6F) COMMON COMMENT TO ALL FLOORS. ROOM # 230A CART |
| | STORAGE, PLEASE PROVIDE ADDITIONAL INFORMATION, IT |
| | APPEARS THIS AREA MAY BE USED FOR LAUNDRY / LINEN CART |
| | STORAGE IF SO PLEASE PROVIDE DOCUMENTATION FOR A |
| | CLOSED-CART SYSTEM THAT WOULD BE IN COMPLIANCE WITH THE |
| | FLORIDA FIRE PREVENTION CODE, FBC-B 420.3.3.11. |
| | |
| | 6G) WALL TYPE D01 ON G102 THIS WALL IS DESIGNATED AS A |
| | SMOKE PARTITION, PLEASE INDICATE COMPLIANCE WITH 710. |
| | |
| | 7) SHEET G103: |
| | |
| | 7A) MISSING INFORMATION ON WALL DESIGNATION TAG. SMOKE |
| | COMPARTMENT WALL/ SMOKE BARRIER FBC-B 709 1 HOUR RATING |
| | FROM OUTSIDE WALL TO OUTSIDE WALL. |
| | |
| | 7B) SMOKE COMPARTMENT WALL THAT SEPARATES COMPARTMENTS |
| | A/ B. WALL TYPE A01 & F01 BOTH ARE INDICATED AS NONE |
| | FIRE RATED. SMOKE COMPARTMENT WALLS REQUIRED BY 407.4 |
| | SHALL BE IN ACCORDANCE WITH 709, 709.3 REQUIRES A 1 |
| | HOUR SEPARATION CONTINUOUS FROM OUTSIDE OF WALL TO |
| | OUTSIDE OF WALL. |
| | |
| | 8) SHEET A106 ROOF PLAN: EIGHT ROOF DRAINS ARE MISSING |
| | A EMERGENCY ROOF DRAIN. THE OVERFLOW SCUPPERS THAT ARE |
| | SHOWN (6) ARE LOCATED SOMEWHERE BETWEEN 2?- 4? ABOVE |
| | THE EDGE OF THE INSULATED ROOF. 1503.4.3 OVERFLOW |
| | SCUPPERS ARE DESIGNED TO BE USED WITH SCUPPERS WHERE |
| | THE ROOF SLOPES TO THE SCUPPERS, AND IF THE SCUPPERS |
| | ARE BLOCKED THEN THE OVERFLOW SCUPPERS WILL ONLY POND |
| | 2-4 INCHES. WITH THE ROOF HAVING ??/ 12? OR 1? PER |
| | 4?-0? AND THE ROOF DRAIN TO THE OVER FLOW SCUPPER IS 32 |
| | FEET AWAY THE PONDING WOULD BE 8-10 INCHES DEEP. |
| | |
| | 9) SHEET S-6.6 WIND LOAD SCHEDULE INDICATES PRESSURES |
| | BUT NOT THE WIND DESIGN CRITERIA: 1609.6.2 WIND DESIGN |
| | PROCEDURES |
| | 9.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| | 9.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION1609.5. |
| | 9.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. NOTE THIS FACILITY HAS A |
| | BUILDING CATEGORY III, HEALTH CARE FACILITIES WITH A |
| | CAPACITY OF 50OR MORE RESIDENT PATIENTS BUT NOT HAVING |
| | SURGERY OR EMERGENCY TREATMENT FACILITIES. |
| | 9.4 A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) EXPOSURE C |
| | 9.5 POSITIVE & NEGATIVE PRESSURES FOR BOTH DOOR & |
| | WINDOW OPENINGS FOR SIZE OF OPENINGS, ROOF PRESSURES |
| | FOR FLAT ROOF AS WELL AS SLOPED ROOF 7 TO 27 DEGREES . |
| | 9.6 MEAN ROOF HEIGHT- THE AVERAGE OF THE ROOF EAVE |
| | HEIGHT AND THE HEIGHT TO THE HIGHEST POINT ON THE ROOF |
| | SURFACE, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR ROOF |
| | ANGLE OF LESS THAN OR EQUAL TO 10 DEGREES (0.18 RAD). |
| | |
| | 10) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 11) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, SOLID & GLAZED, ROLL UP OR |
| | COILING OVERHEAD DOORS AND OR INCLUDING ROOF HATCHES. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E SKYLIGHTS |
| | (F) PRE-ENGINEERED A/C STANDS |
| | |
| | 12) FBC-B 1609.1.2 PROTECTION OF OPENINGS. LARGE IMPACT |
| | RESISTANT GLAZING TO A HEIGHT OF 30'-0" OR : |
| | 420.4.2.5.2 PERMANENTLY ATTACHED PROTECTIVE SYSTEMS |
| | SUCH AS SHUTTERS AND BAFFLING SHALL BE DESIGNED TO MEET |
| | THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE DEBRIS |
| | IMPACT REQUIREMENTS AS SPECIFIED BY SECTIONS 1626.2 |
| | THROUGH 1626.4. |
| | |
| | 420.4.2.5.3 REMOVABLE PROTECTIVE SYSTEMS DESIGNED TO |
| | INTRICATELY FIT WITH THE WALL/WINDOW SYSTEM OF THE |
| | FACILITY AND STORED ON SITE AT THE FACILITY AND THAT |
| | MEET THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE |
| | DEBRIS IMPACT REQUIREMENTS SPECIFIED BY SECTIONS 1626.2 |
| | THROUGH 1626.4 MAY BE USED TO PROTECT THE EXTERIOR |
| | UNITS. |
| | |
| | PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR |
| | WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13 |
| | RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES |
| | WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE |
| | SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT |
| | MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE |
| | THAT COMPLETE INSTALLATION OR SECURING IS DONE |
| | SUFFICIENTLY IN ADVANCE OF THE HURRICANE? |
| | |
| | IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE |
| | GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, |
| | SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING, |
| | CHAPTER 1, |
| | ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY |
| | OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE |
| | BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR |
| | ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION |
| | OF EXISTING BUILDINGS. |
| | |
| | IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR |
| | MULTI-STORY BUILDINGS, OR MULTIPLE |
| | ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST |
| | BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS |
| | FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY |
| | SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION |
| | OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE |
| | SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH |
| | COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND |
| | THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. |
| | PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN |
| | TWELVE (12) HOURS OR LESS OF THE |
| | OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES |
| | OF A HURRICANE WATCH. |
| | |
| | PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| | ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE |
| | MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| | REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN |
| | QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| | DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| | UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| | MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| | BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| | SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| | |
| | IN LEAU OF LARGE MISSILE IMPACT RATED WINDOWS, STORM |
| | SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/ |
| | 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT |
| | PROTECTION. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |