Plan Review Details - Permit 12030017
Plan Review Stops For Permit 12030017
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-04-16 Cont ID  
Sent By rmcdouga Date 2012-04-16 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2012-04-16 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-13 Cont ID  
Sent By RMCDOUGA Date 2012-03-13 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2012-03-13 Time 10:17 Sent To  
Notes
2012-03-13 16:42:162007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) BASED ON FBC TABLES R301.2(2) AND R301.2(3) FOR AN
 OPENING 10 SQFT OR LESS AND A 30' MEAN ROOF HEIGHT THE
 COMPONENT AND CLADDING PRESSURES ON THE ORIGINAL PLANS
 ARE CORRECT. PLEASE SUBMIT SIGNED AND SEALED
 CALCULATIONS THAT JUSTIFY THE LOWER PRESSURES.
  
 2) THE PRODUCT APPROVAL FOR THE DOUBLE HUNG WINDOW
 SPECIFIES DESIGN PRESSURES OF +55, -65 PSF. THE
 REQUIRED NEGATIVE PRESSURE IN WALL ZONE 5 IS -66.08 PSF
 USING THE TABLES SPECIFIED IN THE PREVIOUS COMMENT.
 PLEASE CORRECT. FBC R301.2.1
  
 3) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED ARE FOR
 A JOHNS-MANVILLE ROOFING PRODUCT (NOA NO 11-0126.01)
 AND THE PRODUCT APPROVAL THAT WAS SUBMITTED IS FOR A
 GAF BUR SYSTEM (NOA NO 07-1219.09). PLEASE SUBMIT THE
 CORRESPONDING PRODUCT APPROVAL. DCA RULE 9N-3 AND FBC
 R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-03-08 Cont ID  
Sent By RMCDOUGA Date 2012-03-08 Time 12:46 Rev Time 0.00
Received By rlecky Date 2012-03-08 Time 12:46 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2012-03-13 Cont ID  
Sent By rmcdouga Date 2012-03-13 Time 16:47 Rev Time 0.00
Received By rmcdouga Date 2012-03-13 Time 16:47 Sent To  
Notes
2012-03-13 16:48:30PREVIOUSLY APPROVED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-16 Cont ID  
Sent By rmcdouga Date 2012-04-16 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2012-04-11 Time 09:45 Sent To  
Notes
2012-04-11 09:46:32GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-13 Cont ID  
Sent By rmcdouga Date 2012-03-13 Time 16:48 Rev Time 0.00
Received By rmcdouga Date 2012-03-05 Time 13:58 Sent To  
Notes
2012-03-05 13:58:42SENT TO R9 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-01-04 Cont ID  
Sent By rmcdouga Date 2013-01-04 Time 08:49 Rev Time 0.00
Received By rmcdouga Date 2013-01-04 Time 08:49 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-03-13 Cont ID  
Sent By RMCDOUGA Date 2012-03-13 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2012-03-13 Time 15:58 Sent To  
Notes
2012-03-13 15:59:35IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-03-13 Cont ID  
Sent By RMCDOUGA Date 2012-03-13 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2012-03-13 Time 15:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-03-02 Cont ID  
Sent By astelly Date 2012-03-02 Time 11:54 Rev Time 0.00
Received By astelly Date 2012-03-02 Time 11:54 Sent To  
Notes
***NONE***