Plan Review Details - Permit 12030002
Plan Review Stops For Permit 12030002
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-03-01 Cont ID  
Sent By jgomez Date 2012-03-01 Time 16:33 Rev Time 0.00
Received By jgomez Date 2012-03-01 Time 16:33 Sent To  
Notes
2012-03-01 16:35:56TALKED TO PHILIP. HE SAID HE WILL INSTALL GAF ASSEMBLY
 ON PAGE 8 OF GAF NOA 08-0303.10.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-01 Cont ID  
Sent By jgomez Date 2012-03-01 Time 11:19 Rev Time 0.00
Received By jgomez Date 2012-03-01 Time 11:19 Sent To  
Notes
2012-03-01 11:31:38RE-ROOF REVISION BUILDING REVIEW COMMENTS.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PLEASE PROVIDE FIELD WITHDRAWAL RESISTANCE TEST (TAS
 105) AND RAS 117 CALCULATIONS AS REQUIRED BY
 LIGHTWEIGHT INSULATING CONCRETE SYSTEM LIMITATION #1 ON
 LAST PAGE OF NOA 11-0415.11 SUBMITTED.
 PROVIDE 2 SIGNED AND SEALED COPIES OF EACH.
  
 ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO
 TAKE INTO CONSIDERATION THAT PER 2009 REVISIONS, THIS
 BUILDING IS LOCATED ON EXPOSURE "C".
  
 2- SELECTED APPROVED ASSEMBLY ON SHEET 8 OF NOA
 11-0415.11 SUBMITTED IS GOOD FOR -52.5PSF. NEED TO
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON LAST
 PAGE OF NOA TO MEET THE DESIGN PRESSRUES OF SEC. 1609
 FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-01 Cont ID  
Sent By jgomez Date 2012-03-01 Time 16:33 Rev Time 0.00
Received By jgomez Date 2012-03-01 Time 16:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-01 Cont ID  
Sent By jgomez Date 2012-03-01 Time 11:37 Rev Time 0.00
Received By jgomez Date 2012-03-01 Time 11:37 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved