| Plan Review Stops For Permit 12020682 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2012-05-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-05-01 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-05-01 |
Time |
12:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2012-03-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-03-13 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-03-13 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2012-03-13 10:53:11 | BUILDING PASSED PLANS NOT STAMPED SINCE NEW PLANS WILL | | | BE REQUIRED TO SATISFY PLUMBING COMMENTS. JW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-04-30 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-04-30 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-04-30 |
Time |
08:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-03-01 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-03-01 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-03-01 |
Time |
12:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2012-04-27 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2012-04-27 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2012-04-27 |
Time |
|
Sent To |
|
|
| Notes |
| 2012-04-27 14:51:53 | PLAN IS ACCEPTABLE. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2012-03-28 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2012-03-28 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2012-03-28 |
Time |
|
Sent To |
|
|
| Notes |
| 2012-03-28 12:54:47 | PLAN IS ACCEPTABLE: | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2012-04-27 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2012-04-27 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2012-04-27 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2012-04-27 16:10:11 | SEE APPROVAL SIGNATURE ON PLANS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2012-03-05 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-03-05 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-03-05 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2012-03-05 12:33:54 | 1974 PALM BEACH LAKES BOULEVARD | | | PERMIT #12020682 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO | | | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION | | | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF | | | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-05-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-05-01 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-04-13 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-04-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-03-28 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-02-29 |
Time |
09:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2012-05-01 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-05-01 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-05-01 |
Time |
10:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2012-03-06 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-03-06 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-03-13 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2012-03-06 09:31:30 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. THE NUMBER OF FACILITIES FOR MEN IS REQUIRED TO BE | | | DETERMINED FROM: | | | 403.1.1.2 OCCUPANCY CONTENT CALCULATION. THE OCCUPANCY | | | CONTENT OF A BUILDING, WHICH DETERMINES THE NUMBER OF | | | WATER CLOSETS REQUIRED FOR MEN, SHALL BE CALCULATED | | | USING THE SQUARE FOOTAGE PER PERSON REQUIREMENTS | | | ESTABLISHED BY THE FLORIDA BUILDING CODE, BUILDING. | | | 30 MEN WOULD EQUAL 2 WATER CLOSETS OR 1 WATER CLOSET | | | AND ONE URINAL. | | | | | | 2. PLEASE INCLUDE A PLUMBING RISER DIAGRAM | | | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | PLUMBING | | | 13. PLUMBING RISER | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2012-04-24 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2012-04-24 |
Time |
20:15 |
Rev Time |
0.50 |
| Received By |
lfranco |
Date |
2012-04-24 |
Time |
20:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2012-03-28 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2012-03-28 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2012-03-28 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2012-03-28 15:19:42 | PLANNING: **** FAILED *** | | | | | | | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. PURSUANT TO THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS *"ZLDR"), SECTION 94-443(3)B, AN INTERIOR | | | ISLAND IS REQUIRED FOR EVERY 10 PARKING STALLS. THE | | | PROPOSED 11 SPACES WILL NOT BE ALLOWED WITHOUT AN | | | INTERIOR ISLAND. REVISE PARKING STALLS FOR 10 PARKING | | | STALLS WITH A MINIMUM DIMENSIONS OR A LITTLE BIT LARGER | | | TO FIT INTO THE SPACE AVAILABLE AFTER THE ADA SPACE IS | | | RELOCATED. | | | | | | 3. PROVIDE PARKING STALLS DETAILS ON PLANS THAT HAS | | | BEEN PROVIDED BY ENGINEERING. PLEASE CONTACT ME IF YOU | | | WOULD LIKE A DETAIL EMAILED. | | | | | | LINDA MIA FRANCO, AICP | | | SENIOR PLANNER | | | PLANNING DIVISION | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|