Plan Review Details - Permit 12020587
Plan Review Stops For Permit 12020587
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-04-16 Cont ID  
Sent By jwitmer Date 2012-04-16 Time 13:28 Rev Time 0.00
Received By jwitmer Date 2012-04-16 Time 13:00 Sent To  
Notes
2012-04-16 13:32:54BUILDING PLAN REVIEW
 PERMIT: 12020587
 ADD: 400 EXECUTIVE CENTRE DR # 110
 CONT: SCIENTIFIC CONSTRUCTION GROUP
 TEL: (786)587-9728
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1) RECEPTION DOOR TO COMPLY WITH 2007/09 FBC-B
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS, 18 INCHES AT
 LATCH SIDE OF DOOR FOR MANEUVERING CLEARENCES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-12 Cont ID  
Sent By jwitmer Date 2012-03-12 Time 13:46 Rev Time 0.00
Received By jwitmer Date 2012-03-12 Time 13:39 Sent To  
Notes
2012-03-12 13:54:06BUILDING PLAN REVIEW
 PERMIT: 12020587
 ADD: 400 EXECUTIVE CENTRE DR # 110
 CONT: SCIENTIFIC CONSTRUCTION GROUP
 TEL: (786)587-9728
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1STREVIEW
 ACTION: DENIED
  
 1) SHEET A1 INDICATES DOOR TYPE "B"& DOOR TYPE "C",
 BOTH ARE INDICATED TO BE A 30 INCH OPENING.2007/09
 FBC-B SECTION 11-4.13.5 CLEAR WIDTH- DOORWAYS SHALL
 HAVE A MINIMUM CLEAR OPENING OF 32 INCHES (813 MM) WITH
 THE DOOR OPEN 90 DEGREES, MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE OPPOSITE STOP .
  
 THE PERMIT APPLICATION INDICATES THE CONTRACT VALUE TO
 BE $25,000.00, AN ADDITIONAL $5,000.00 OR 20% IN FUNDS
 WILL NEED TO BE INDICATED WHERE THESE FUNDS WILL BE
 USED IN UPGRADING THIS UNIT TO BE CLOSER TO ACCESSIBIE
 IN CODE COMPLIANCE. . FBC-B 11-4.1.6(2) ALTERATIONS TO
 AN AREA CONTAINING A PRIMARY FUNCTION.
 IN ADDITION TO THE REQUIREMENTS OF SECTION 11-4.1.6(1),
 AN ALTERATION THAT AFFECTS OR COULD AFFECT THE
 USABILITY OF OR ACCESS TO AN AREA CONTAINING A PRIMARY
 FUNCTION SHALL BE MADE SO AS TO ENSURE THAT, TO THE
 MAXIMUM EXTENT FEASIBLE, THE PATH OF TRAVEL TO THE
 ALTERED AREA AND THE RESTROOMS, TELEPHONES, AND
 DRINKING FOUNTAINS SERVING THE ALTERED AREA, ARE
 READILY ACCESSIBLE TO AND USABLE BY INDIVIDUALS WITH
 DISABILITIES, UNLESS SUCH ALTERATIONS ARE
 DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN TERMS
 OF COST AND SCOPE.
  
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION
 TO THE PRIMARY FUNCTION AREA.
  
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (I) AN ACCESSIBLE ENTRANCE;
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
  
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
  
 (IV) ACCESSIBLE TELEPHONES;
  
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
  
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
 PLEASE PROVIDE DOCUMENTATION WHICH DOORS WILL BE
 ALTERED TO CREATE A 32 INCH CLEAR OPENING AND USING UP
 THE 20% FUNDS FOR CODE COMPLIANCE.
  
  
 2) THE PLANS DO NOT PROVIDE THE ONE HOUR TENANT
 SEPERATION REQUIRED BY FBC-B 708.1.
  
 3) PLEASE PROVIDE COMPLIANCE WITH: FBC-B 712.6 FIRE
 WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS
 AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE
 PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH
 IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING
 AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND
 SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL
 OPENINGS."
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-04-09 Cont ID  
Sent By rlecky Date 2012-04-09 Time 12:59 Rev Time 0.00
Received By rlecky Date 2012-04-09 Time 12:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-02-29 Cont ID  
Sent By rlecky Date 2012-02-29 Time 14:05 Rev Time 0.00
Received By rlecky Date 2012-02-29 Time 13:45 Sent To  
Notes
2012-02-29 14:06:4612020587
 400 EXECUTIVE CENTER DR.
 RENOVATION SUITE #110
  
 REVISE THE ELECTRICAL PLAN TO INCLUDE THE REQUIREMENTS
 FOR WIRING IN PATIENT CARE AREAS OF ALL EXAM AND
 TREATMENT ROOMS. NEC 517.10
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING CODE 711.1
 PROVIDE A LIGHTING DENSITY CALCULATIONS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 PROVIDE EMERGENCY EGRESS LIGHTING. FBC 1006.1
 RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS MUST BE
 GFCI PROTECTED. NEC 210.8
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-04-12 Cont ID  
Sent By wjolin Date 2012-04-12 Time 15:23 Rev Time 0.00
Received By wjolin Date 2012-04-12 Time 15:10 Sent To  
Notes
2012-04-12 15:23:09400 EXECUTIVE CENTER DRIVE - SUITE #110
 PERMIT #12020587
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL PREVIOUS PLAN REVIEW COMMENTS (FIRE) HAVE BEEN
 ADDRESSED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-02-28 Cont ID  
Sent By wjolin Date 2012-02-28 Time 11:54 Rev Time 0.00
Received By wjolin Date 2012-02-28 Time 11:21 Sent To  
Notes
2012-02-28 11:54:15400 EXECUTIVE CENTER DRIVE - SUITE #110
 PERMIT #12020587
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED AREAS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 DESIGN DOCUMENTS NEED TO INCLUDE THE SCOPE OF WORK FOR
 THE MODIFICATION OF THE EXISTING FIRE SPRINKLER AND
 FIRE ALARM SYSTEM. AT MINIMUM, PROVIDE FIRE ALARM
 INITIATING/NOTIFICATION APPLIANCE LOCATIONS AND
 INDICATE THE SPRINKLER HAZARD CLASSIFICATION WITH
 DESIGN DENSITY. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED DESIGN
 DOCUMENTS) FOR A SUB-PERMIT. SEPARATE PLANS AND PERMITS
 ARE REQUIRED FOR THE INSTALLATION OR MODIFICATION OF
 THE FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FIRE RATED WALLS SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE/SMOKE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PLANS DO NOT INDICATE A FIRE RATED SEPARATION BETWEEN
 ADJACENT TENANT. INDICATE THE OCCUPANY OF THE ADJACENT
 TENANT.
  
 EXIT SIGNS ARE DIRECTING OCCUPANTS TO PASS THROUGH
 DOCTOR'S OFFICES.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-17 Cont ID  
Sent By hmoser Date 2012-04-17 Time 10:18 Rev Time 0.00
Received By hmoser Date 2012-04-05 Time 17:45 Sent To  
Notes
2012-04-05 17:48:15B--20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-28 Cont ID  
Sent By hmoser Date 2012-03-28 Time 09:53 Rev Time 0.00
Received By hmoser Date 2012-02-27 Time 10:41 Sent To  
Notes
2012-02-27 10:41:48INCOMING SENT TO B14. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-04-17 Cont ID  
Sent By hmoser Date 2012-04-17 Time 10:18 Rev Time 0.00
Received By hmoser Date 2012-04-17 Time 10:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-03-28 Cont ID  
Sent By hmoser Date 2012-03-28 Time 09:53 Rev Time 0.00
Received By hmoser Date 2012-03-27 Time 14:44 Sent To  
Notes
2012-03-28 09:53:02PLANS DENIED
 1) PROVIDE A COMPLETE SET OF MECHANICAL PLANS.SECTION
 106.1.1 FBC 2007
 2) PROVIDE LOCATION OF MECHANICAL EQUIPMENT ON THE
 PLANS. SECTION 106.1.1
 3) PROVIDE MECHANICAL CONTRACTOR SIGNATURE ON THE
 APPLICATION.
 4) REFER TO SECTION 13-409.AB.3.3 DAMPER SHUTOFF
 CONTROL'S FLORIDA ENERGY CODE.
 5) REFER TO FLORIDA STATUTES CHAPTER 471 ENGINEERING
 407.003 QUALIFICATION FOR PRACTICE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-04-17 Cont ID  
Sent By lwagner Date 2012-04-17 Time 07:59 Rev Time 0.00
Received By lwagner Date 2012-04-16 Time 14:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-03-05 Cont ID  
Sent By lwagner Date 2012-03-05 Time 09:30 Rev Time 0.00
Received By lwagner Date 2012-03-05 Time 08:12 Sent To  
Notes
2012-03-05 09:29:14FBC PLUMBING REVIEW #1
 DENIED:
  
 1. 403.1 MINIMUM PLUMBING FACILITIES - IF NOT ALREADY
 EXISTING, ONE DRINKING FOUNTAIN WILL BE REQUIRED.
  
 2. THE PLAN SHOWS EXISTING RESTROOMS THAT DO NOT APPEAR
 TO BE ACCESSIBLE:
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION
 TO THE PRIMARY FUNCTION AREA.
  
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (I) AN ACCESSIBLE ENTRANCE;
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
  
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
  
 (IV) ACCESSIBLE TELEPHONES;
  
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
  
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2012-03-28 Cont ID  
Sent By lfranco Date 2012-03-28 Time 11:28 Rev Time 0.00
Received By hmoser Date 2012-03-28 Time 11:28 Sent To  
Notes
2012-03-28 11:28:56PER LINDA NOT REQUIRED.