Plan Review Details - Permit 12020584
Plan Review Stops For Permit 12020584
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-07 Cont ID  
Sent By rlecky Date 2012-03-07 Time 11:30 Rev Time 0.00
Received By rlecky Date 2012-03-07 Time 11:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-02-28 Cont ID  
Sent By rlecky Date 2012-02-28 Time 10:57 Rev Time 0.00
Received By rlecky Date 2012-02-28 Time 10:28 Sent To  
Notes
2012-02-28 10:58:5412020584
 1300 8TH STREET
 ELECTRIC SERVICE REPAIR
  
 THE ELECTRICAL RISER PLAN NEEDS TO SHOW THE MAIN
 DISCONNECT SIZE, THE GROUNDING SYSTEM AND THE SERVICE
 CONDUCTOR SIZE. INDICATE THE SIZE OF THE EXISTING PANEL
 BOARD. AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE
 MAIN SERVICE GROUND NEC 250.94, NEC 215.5
  
 ROBERT LECKY
 ELECTRIC PLAN REVIEWER
 [email protected]
 561-805-6718
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-07 Cont ID  
Sent By rlecky Date 2012-03-07 Time 11:30 Rev Time 0.00
Received By rlecky Date 2012-03-07 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-28 Cont ID  
Sent By rlecky Date 2012-02-28 Time 10:59 Rev Time 0.00
Received By rlecky Date 2012-02-24 Time 16:10 Sent To  
Notes
2012-02-24 16:11:2602/24/2012 INCOMING SENT TO ELEC BOX <$5K. JW