Plan Review Details - Permit 12020552
Plan Review Stops For Permit 12020552
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-02-27 Cont ID  
Sent By wjolin Date 2012-02-27 Time 10:45 Rev Time 0.00
Received By wjolin Date 2012-02-27 Time 09:59 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-11 Cont ID  
Sent By hmoser Date 2012-04-11 Time 15:14 Rev Time 0.00
Received By hmoser Date 2012-03-19 Time 14:40 Sent To  
Notes
2012-03-19 14:41:08SENT TO HAROLD'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-12 Cont ID  
Sent By hmoser Date 2012-03-12 Time 12:26 Rev Time 0.00
Received By hmoser Date 2012-02-23 Time 16:12 Sent To  
Notes
2012-02-23 16:13:06TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-04-11 Cont ID  
Sent By hmoser Date 2012-04-11 Time 15:11 Rev Time 0.00
Received By hmoser Date 2012-04-11 Time 15:11 Sent To  
Notes
2012-04-11 15:13:05PASS PROVISO
 REFER TO SECTION 308 CLEARANCE REDUCTION 2007 FBC (M)
 HM.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-04-04 Cont ID  
Sent By hmoser Date 2012-04-04 Time 12:26 Rev Time 0.00
Received By hmoser Date 2012-03-20 Time 08:47 Sent To Z
Notes
2012-04-04 12:29:34PLANS DENIED
 REFER TO SECTION 308 CLEARANCE REDUCTION 2007 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-03-12 Cont ID  
Sent By hmoser Date 2012-03-12 Time 12:17 Rev Time 0.00
Received By hmoser Date 2012-03-12 Time 11:08 Sent To  
Notes
2012-03-12 12:26:45PLANS DENIED
 1) DETAILS ON EXHAUST AND SUPPLY DO NOT MATCH NOTES
 PAGE # 1 OF PLANS.
 2) PROVIDE ROD SIZE ON THE PLANS SUPPLY AIR CURB TO
 UNISTRUT.PAGE 1 OF PLANS
 3) PAGE 1 OF PLANS SHOW JOIST PAGE 3 SHOWS RAFTERS.
 4) PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS ON
 WRAP ON TOP OF HOOD .
 5) REFER TO SECTION 304.10 GUARDS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-04-06 Cont ID  
Sent By fmittner Date 2012-04-06 Time 15:11 Rev Time 0.00
Received By fmittner Date 2012-04-05 Time 11:59 Sent To  
Notes
2012-04-05 11:59:11GIVEN TO FM