Plan Review Details - Permit 12020533
Plan Review Stops For Permit 12020533
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-07 Cont ID  
Sent By jwitmer Date 2012-06-07 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2012-06-07 Time 11:30 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-27 Cont ID  
Sent By jwitmer Date 2012-02-27 Time 11:41 Rev Time 0.00
Received By jwitmer Date 2012-02-27 Time 11:13 Sent To  
Notes
2012-02-27 11:31:02 
 BUILDING PLAN REVIEW
 PERMIT:12020533/ 11110025
 ADD: 777 S FLAGLER DR # 800
 CONT: HOLT LEE
 TEL: (561) 373-3902
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) BUILDING PROVISO FOUND ON SHEET I-3 HAS BEEN
 IGNORED. PLEASE PROVIDE ADDITIONAL INFORMATION WHERE
 THE 20% ADDITIONAL FUNDS (26,717.00 WILL BE SPENT IN
 CREATING AN CODE COMPLIANT ACCESSIBLE SPACE BY FRAMING
 INSPECTION. THERE WERE TWO AREAS CIRCLED ON THE ISSUED
 SET OF PLANS WHERE THERE WERE CODE ACCESSIBLITY ISSUES
 WITH THE EXISTING LAYOUT. THERE WERE ADDITIONAL AREAS
 WHERE THERE WERE ACCESSIBILITY ISSUES, IT IS UP TO THE
 CONTRACTOR AND DESIGNER TO DECIDE WHERE THE 20%
 ADDITIONAL FUNDS ARE TO BE SPENT IN
 CREATING A CODE COMPLIANT SPACE. PLEASE NOTE WHEN
 EITHER THE 20% OF THE FUNDS WERE SPENT OR IF THE TENANT
 SPACE HAS BECOME CODE COMPLIANT FOR ACCESSIBLITY BEFORE
 REACHING THE TWENTY PERCENT THEN NO MORE FUNDS NEED TO
 BE SPENT.
  
  
 THE ORIGINAL PROVISO LISTED BELOW:
 BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR
 TO INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND
 THE ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS
 REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
 PLEASE SEE HIGHLIGHTED AREAS ON SHEET 1-3 ARE EXISTING
 NON-CODE COMPLIANT (FBC-B 11-4.13.6) DOORS.
 2007/09 EXST. BLDG. CODE LEVEL II ALTERATIONS SECTION
 706.1. A BUILDING, FACILITY, OR ELEMENT THAT IS
 ALTERED SHALL COMPLY WITH CHAPTER 11 OF THE FLORIDA
 BUILDING CODE, BUILDING .
  
 2007/09 FBC-B 11-4.1.6(2) (2) ALTERATIONS TO AN AREA
 CONTAINING A PRIMARY FUNCTION.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST EXCEEDS 20
 PERCENT OF THE COST OF THE ALTERATION TO THE PRIMARY
 FUNCTION AREA.
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT
 IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE
 THE GREATEST ACCESS, IN THE FOLLOWING ORDER:
 (I) AN ACCESSIBLE ENTRANCE;
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
 (IV) ACCESSIBLE TELEPHONES;
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
 PLEASE PROVIDE ADDITIONAL INFORMATION WHERE THE 20%
 ADDITIONAL FUNDS WILL BE SPENT IN CREATING AN CODE
 COMPLIANT ACCESSIBLE
 SPACE BY FRAMING INSPECTION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-02-28 Cont ID  
Sent By rlecky Date 2012-02-28 Time 15:46 Rev Time 0.00
Received By rlecky Date 2012-02-28 Time 15:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-06-14 Cont ID  
Sent By rferguso Date 2012-06-14 Time 15:53 Rev Time 0.00
Received By rferguso Date 2012-06-14 Time 15:53 Sent To  
Notes
2012-06-14 16:00:25777 SOUTH FLAGLER DR. STE. 800
 PERMIT #12020533
  
 PLANS REVIEWED BY FIRE ***APPROVED*** (DD)
 FILED OUT FRONT FOR P/U IN BIN (H).

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-02-27 Cont ID  
Sent By wjolin Date 2012-02-27 Time 15:04 Rev Time 0.00
Received By wjolin Date 2012-02-27 Time 14:43 Sent To  
Notes
2012-02-27 15:04:41THERE ARE FOUR REVISION DELTAS (1,2,3 & 6) IN THE
 TITLEBLOCK AND NO DESCRIPTION AS TO WHAT HAS BEEN
 CHANGED.
  
 REVISION CLOUDS AND CHANGES FOR DELTAS 2 AND 3 CANNOT
 BE FOUND ON THE PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-14 Cont ID  
Sent By rferguso Date 2012-06-14 Time 15:53 Rev Time 0.00
Received By rferguso Date 2012-06-01 Time 17:49 Sent To  
Notes
2012-06-01 17:49:36SENT TO J. WITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-28 Cont ID  
Sent By rlecky Date 2012-02-28 Time 15:46 Rev Time 0.00
Received By rlecky Date 2012-02-23 Time 18:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-02-28 Cont ID  
Sent By lwagner Date 2012-02-28 Time 13:45 Rev Time 0.00
Received By lwagner Date 2012-02-28 Time 10:11 Sent To  
Notes
2012-02-28 13:27:31***PROVISO***
 917.3.2 RELIEF VENT. WHERE THE HORIZONTAL
 BRANCH IS LOCATED MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, THE
 HORIZONTAL BRANCH SHALL BE PROVIDED WITH
 A RELIEF VENT THAT SHALL CONNECT TO A VENT
 STACK OR STACK VENT, OR EXTEND OUTDOORS TO
 THE OPEN AIR.
  