| Plan Review Stops For Permit 12020503 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2012-04-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-04-24 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-04-24 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2012-04-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-04-11 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-04-11 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2012-04-11 11:19:53 | BUILDING PLAN REVIEW | | | PERMIT: 12020503 | | | ADD: 515 N FLAGLER P-100 | | | CONT: CUTTING EDGE BUILDING | | | TEL: (561)282-8265 | | | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) LIFE SAFETY SHEET LS-1: | | | 1A) COMPLIED. | | | | | | 1B) 2ND REQUEST! THE CODE RESEARCH INDICATES THIS PLANS | | | TO BE A BUSINESS OCCUPANCY, PLEASE SEE 303.1 A-3 | | | GYMNASIUM WITHOUT SPECTATOR SEATING, IT APPEARS THIS | | | MAY BE A CHANGE OF OCCUPANCY WHICH WOULD BE REVIEWED | | | UNDER THE EXISTING BUILDING CODE 901.3.1 SECTION 912 OF | | | THE EXISTING BUILDING CODE WOULD APPLY. | | | | | | 1C)2ND REQUEST! WITH THE A-3 OCCUPANCY THE OCCUPANT | | | LOAD WILL CHANGE PLEASE SEE FBC-B TABLE 1004.1.1 | | | EXERCISE ROOMS/ GYMASIUMS WITH EQUIPMENT 50 GROSS AND | | | ROOMS WITHOUT EQUIPMENT 15 GROSS PLEASE MAKE THE | | | REQUIRED OCCUPANT LOAD ADJUSTMENTS. | | | RESPONSE INDICATES THAT THE SPACE WAS REDUCED TO 4934 | | | SQ FT AN OCCUPANT LOAD OF 49. WHEN THERE IS A FRACTION | | | ON AN OCCUPANT YOU ROUND UP NOT DOWN, MAKING THE | | | OCCUPANT LOAD OF 50 UNDER A BUSINESS OCCUPANCY. | | | | | | BOAF INFORMAL INTERPRETATION 5484 HAS A SIMILAR | | | ARGUEMENT DECLARING A BUSINESS OCCUPANCY BUT THEY WERE | | | CORRECT IN THE BUSINESS OCCUPANCY CLASSIFICATION BUT | | | THEY ALSO USED THE CORRECT OCCUPANT LOADING FROM TABLE | | | 1004.1.1. IN YOUR CASE THE GYM (WITH EQUIPMENT) PORTION | | | SHOULD BE TAKEN AT | | | 50 GROSS AND THE AEROBATICS AT 15 GROSS. THIS COUNT | | | WILL WELL PUT THE GYM ABOVE THE 50 OCCUPANT LOAD TO | | | DECLARE THIS AN A-3 ASSEMBLY OCCUPANCY. | | | | | | BOAF INFORMAL INTERPRETATION 5662 PROVIDES A BIT OF | | | HISTORY WHY THE FIGURES STATED ABOVE COME FROM, TO | | | ALIGN THE FLORIDA BUILDING CODE WITH THE FLORIDA FIRE | | | PREVENTION CODE, NFPA 101, TABLE 7.3.1.2. THE FFPC | | | SUB-DIVIDES EVERCISE ROOMS INTO THE TWO CATEGORIES WITH | | | AND WITHOUT EQUIPMENT. THE BASE CODE (IBC) SPECIFIES AN | | | OLF OF 50 SQ FT GROSS PER PERSON. | | | | | | 1D) COMPLIED. | | | | | | 2) COMPLIED. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-03-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-03-12 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-03-12 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2012-03-12 11:51:49 | BUILDING PLAN REVIEW | | | PERMIT: 12020503 | | | ADD: 515 N FLAGLER P-100 | | | CONT: CUTTING EDGE BUILDING | | | TEL: (561)282-8265 | | | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) LIFE SAFETY SHEET LS-1: | | | 1A) PLANS FAIL TO IDENTIFY THE TENANT SEPERATION WALL | | | RATING.2007/09 FBC-B 106.3.5.1.1(4) / FBC-B 708.1 | | | TENANT SEPERATION WALLS, 1 HOUR RATING. | | | | | | 1B) THE CODE RESEARCH INDICATES THIS PLANS TO BE A | | | BUSINESS OCCUPANCY, PLEASE SEE 303.1 A-3 GYMNASIUM | | | WITHOUT SPECTATOR SEATING, IT APPEARS THIS MAY BE A | | | CHANGE OF OCCUPANCY WHICH WOULD BE REVIEWED UNDER THE | | | EXISTING BUILDING CODE 901.3.1 SECTION 912 OF THE | | | EXISTING BUILDING CODE WOULD APPLY. | | | | | | 1C) WITH THE A-3 OCCUPANCY THE OCCUPANT LOAD WILL | | | CHANGE PLEASE SEE FBC-B TABLE 1004.1.1 EXERCISE ROOMS/ | | | GYMASIUMS WITH EQUIPMENT 50 GROSS AND ROOMS WITHOUT | | | EQUIPMENT 15 GROSS PLEASE MAKE THE REQUIRED OCCUPANT | | | LOAD ADJUSTMENTS. | | | | | | 1D) WITHIN THE TENANT SPACE IT APPEARS THAT A VERTICAL | | | EXIT (EXIT STAIRS) ARE LOCATED, IS THIS A 1 HOUR RATING | | | OR TWO HOUR RATING? IS THIS TENANT SPACE A NEWLY | | | CREATED SPACE? | | | DO WE STILL HAVE A CODE COMPLIANT EXITING FOR THE FIRST | | | FLOOR SINCE THE OCCUPANTS ON THE REMAINDER OF THE FIST | | | FLOOR MAY NOT BE ABLE TO USE THIS STAIR? | | | | | | 2) SHEET A-2.0 DETAILS 20 & 21 BOTH INDICATE THE | | | ACCESSIBLE WATER CLOSET AT 1'-5" FROM THE SIDE WALL. | | | 2007/ 09 FBC-B 11-4.16.2 WATER CLOSETS SHALL COMPLY | | | WITH FIGURE 11-28 WHICH SHOWS THE WATER CLOSET CENTERED | | | AT 18 INCHES FROM THE SIDE WALL. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-04-09 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-04-09 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-04-09 |
Time |
12:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-03-01 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-03-01 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-03-01 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2012-04-27 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-04-27 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-04-27 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2012-04-27 12:48:28 | 515 NORTH FLAGLER DRIVE - SUITE #P100 | | | PERMIT #12020503 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | REPEAT COMMENT: SHEET FA1.1 (FIRE ALARM NOTIFICATION | | | APPLIANCE LAYOUT) WAS NOT SUBMITTED. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2012-04-10 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-04-10 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-04-10 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2012-04-10 15:11:14 | 515 NORTH FLAGLER DRIVE - SUITE #P100 | | | PERMIT #12020503 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PER NFPA 101, THE OCCUPANT LOAD IS CALCULATED BASED | | | UPON THE USE (ASSEMBLY: EXERCISE W/ AND W/O EQUIPMENT) | | | OF THE SPACE AND NOT THE OCCUPANCY CLASSIFICATION | | | (BUSINESS). | | | | | | REPEAT COMMENT:THE OCCUPANT LOAD FACTOR FOR EXERCISE | | | ROOMS WITH EQUIPMENT SHOULD BE 50 SQ.FT. PER PERSON AND | | | 15 SQ.FT. PER PERSON FOR EXERCISE ROOMS WITHOUT | | | EQUIPMENT PER TABLE 7.3.1.2 OF NFPA 101. | | | | | | REPEAT COMMENT: THE BUILDING IS FUNCTIONING AS A | | | MULTIUSE OCCUPANCY. INDICATE IF THE BUILDING IS | | | DESIGNED FOR MIXED USE (NON-SEPARATED) OR SEPARATED USE | | | PER SECTION 6.1.14.2.1 OF NFPA 101 FLORIDA EDITION | | | 2009. SEPARATED USE WILL REQUIRE A 1-HOUR FIRE BARRIER | | | BETWEEN THE ASSEMBLY OCCUPANCY AND THE BUSINESS | | | OCCUPANCY PER TABLE 6.1.14.4.1(B). | | | | | | REPEAT COMMENT: EVERY ASSEMBLY OCCUPANCY ROOM NOT | | | HAVING FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE | | | ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT | | | FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE | | | NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM. | | | | | | REPEAT COMMENT: FOR AN ASSEMBLY OCCUPANCY WITH AN | | | OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE | | | SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. | | | NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT | | | BE RELEASED BY THE PANIC HARDWARE. | | | | | | REPEAT COMMENT: PROVIDE THE NEW FIRE ALARM NOTIFICATION | | | APPLIANCE LAYOUT. **NOTE - FA1.1 WAS NOT SUBMITTED** | | | | | | SHEET P1.1: PIPING APPEARS TO BE ROUTED THROUGH THE | | | FIRE RATED EXIT PASSAGEWAY OF THE STAIR. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2012-02-27 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-02-27 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-02-27 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2012-02-27 13:53:28 | 515 NORTH FLAGLER DRIVE - SUITE #P100 | | | PERMIT #12020503 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | THE OCCUPANCY OF THE PROJECT APPEARS TO BE AN ASSEMBLY | | | OCCUPANCY IN LIEU OF A BUSINESS OCCUPANCY.THE OCCUPANT | | | LOAD FACTOR FOR EXERCISE ROOMS WITH EQUIPMENT SHOULD BE | | | 50 SQ.FT. PER PERSON AND 15 SQ.FT. PER PERSON FOR | | | EXERCISE ROOMS WITHOUT EQUIPMENT PER TABLE 7.3.1.2 OF | | | NFPA 101. | | | | | | THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. | | | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE | | | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 | | | OF NFPA 101 FLORIDA EDITION 2006. SEPARATED USE WILL | | | REQUIRE A 1-HOUR FIRE BARRIER BETWEEN THE ASSEMBLY | | | OCCUPANCY AND THE BUSINESS OCCUPANCY PER TABLE | | | 6.1.14.4.1(B). | | | | | | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS | | | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A | | | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. | | | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF | | | OCCUPANTS PERMITTED FOR EACH ROOM. | | | | | | FOR AN ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OF 100 | | | OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON | | | DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR | | | LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE | | | PANIC HARDWARE. | | | | | | FIRE-RATED WALLS SHALL BE PERMANENTLY IDENTIFIED WITH | | | SIGNS OR STENCILING READING FIRE/SMOKE BARRIER?PROTECT | | | ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN | | | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE | | | SPACED NOT MORE THAN 15 FEET ON CENTER. | | | | | | SHEET D1.0: EXISTING STAIR APPEARS TO DISCHARGE INTO | | | FITNESS CENTER. | | | | | | SHEET E2.1: PROVIDE THE NEW FIRE ALARM NOTIFICATION | | | APPLIANCE LAYOUT. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2012-05-02 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-05-02 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-04-18 |
Time |
16:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-04-12 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-04-12 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-04-02 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2012-04-04 11:04:53 | SENT TO B16 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-03-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-03-12 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-02-22 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2012-04-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-04-24 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-04-24 |
Time |
11:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2012-04-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-04-11 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-04-11 |
Time |
11:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2012-03-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-03-12 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-03-12 |
Time |
13:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2012-05-02 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-05-02 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-05-02 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2012-04-12 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-04-12 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-04-12 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2012-04-12 13:56:41 | PLUMBING IS OK PENDING OCCUPANCY TYPE. SEE BUILDING AND | | | FIRE COMMENTS, AND BELOW: | | | | | | PLUMBING IS OK BASED UPON PLUMBING TABLE 403.1 - | | | GYMNASIUMS - 1 PER 65 FEMALE - 3 WATER CLOSETS WOULD BE | | | GOOD FOR UP TO 195. HOWEVER, PER THIS TABLE, ONE | | | SERVICE SINK WOULD BE REQUIRED. A USABLE SERVICE SINK | | | LOCATED ON THE SAME LEVEL WOULD BE ACCEPTABLE. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2012-03-09 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-03-09 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-02-29 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2012-02-29 15:04:22 | ***PROVISO*** | | | PLUMBING IS OK BASED UPON PLUMBING TABLE 403.1 - | | | GYMNASIUMS - 1 PER 65 FEMALE - 3 WATER CLOSETS WOULD BE | | | GOOD FOR UP TO 195. HOWEVER, PER THIS TABLE, ONE | | | SERVICE SINK WOULD BE REQUIRED. A USABLE SERVICE SINK | | | LOCATED ON THE SAME LEVEL WOULD BE ACCEPTABLE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2012-04-06 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2012-04-06 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2012-04-06 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2012-04-06 09:46:23 | MINOR PD AMENDMENT APPROVED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2012-03-02 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2012-03-02 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2012-03-02 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2012-03-02 16:16:26 | THE NORTHBRIDGE CENTER IS A DOWNTOWN PLANNED | | | DEVELOPMENT. PLEASE PROVIDE INFORMATION TO CONFIRM THE | | | LOCATION OF A GYM ON THE FIRST FLOOR OF THE PAVILLION | | | BUILDING IS PERMITTED BY THE PD. IF THE USE IS NOT | | | CURRENTLY PERMITTED AT THE PROPOSED LOCATION A PD | | | AMENDMENT WILL BE REQUIRED BEFORE A BUILDING PERMIT MAY | | | BE ISSUED. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439 |
|
|