Plan Review Details - Permit 12020426
Plan Review Stops For Permit 12020426
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-03-01 Cont ID  
Sent By jgomez Date 2012-03-01 Time 11:10 Rev Time 0.00
Received By jgomez Date 2012-03-01 Time 11:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-02-27 Cont ID  
Sent By jgomez Date 2012-02-27 Time 11:58 Rev Time 0.00
Received By jgomez Date 2012-02-27 Time 11:58 Sent To  
Notes
2012-02-27 12:04:31RE-ROOF BUILDING REVIEW THIRD REVIEW COMMENTS.
  
 1- ENGINEER TO REVISE RAS 117 CALCULATIONS. NAIL
 ENHANCING FASTENING FOR ROOF ZONE #2 SUBMITTED IS THE
 SAME AS FOR ROOF ZONE #1. THIS NAIL ENHANCING DOESN'T
 MEET THE CALCULATED DESIGN PRESSURES. REVISE AS
 REQUIRED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-02-23 Cont ID  
Sent By jgomez Date 2012-02-23 Time 09:42 Rev Time 0.00
Received By jgomez Date 2012-02-23 Time 09:16 Sent To  
Notes
2012-02-23 09:48:34RE-ROOF SECOND REVIEW COMMENTS:
  
 1- ENGINEER TO REVISE RAS 117 CALCULATIONS. NEED TO
 REFER TO NEW MANUFACTURER'S NOA APPROVED ASSEMBLY TO BE
 INSTALLED. INFORMATION SUBMITTED DOESN'T MATCH SELECTED
 ASSEMBLY. REVISE SPECIFIC MATERIALS TO BE USED, REVISE
 FASTENER SPACING AND RAS 117 CALCULATIONS AS REQUIRED.
 ALSO, SECOND PAGE IS REFERRING TO THE GAF NOA. NOA
 SUBMITTED IS FOR A POLYGLASS PRODUCT. REVISE AS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-21 Cont ID  
Sent By jgomez Date 2012-02-21 Time 10:39 Rev Time 0.00
Received By jgomez Date 2012-02-21 Time 10:16 Sent To  
Notes
2012-02-21 10:43:32RESIDENTIAL (R3) RE-ROOF COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ENGINEER TO REVISE RAS 117 CALCULATIONS. NEED TO
 REFER TO POLYGLASS NOA. PLEASE PROVIDE 2 SIGNED AND
 SEALED COPIES.
  
 2- POLYGLASS NOA 08-0226.06 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. PLEASE SUBMIT 2 COPIES OF NOA 11-0425.07,
 WHICH IS THE ONE THAT SUPERSEDES THE OLD NOA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2012-03-01 Cont ID  
Sent By jgomez Date 2012-03-01 Time 11:08 Rev Time 0.00
Received By jgomez Date 2012-03-01 Time 11:05 Sent To  
Notes
2012-03-01 11:11:18ENTERED TWICE BY MISTAKE. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-03-01 Cont ID  
Sent By jgomez Date 2012-03-01 Time 11:04 Rev Time 0.00
Received By jgomez Date 2012-03-01 Time 11:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-02-27 Cont ID  
Sent By jgomez Date 2012-02-27 Time 12:23 Rev Time 0.00
Received By jgomez Date 2012-02-27 Time 12:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-23 Cont ID  
Sent By jgomez Date 2012-02-23 Time 09:48 Rev Time 0.00
Received By jgomez Date 2012-02-23 Time 09:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-21 Cont ID  
Sent By jgomez Date 2012-02-21 Time 10:17 Rev Time 0.00
Received By jgomez Date 2012-02-21 Time 10:17 Sent To  
Notes
***NONE***