Plan Review Details - Permit 12020414
Plan Review Stops For Permit 12020414
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2012-05-31 Cont ID  
Sent By jwitmer Date 2012-05-31 Time 08:44 Rev Time 0.00
Received By jwitmer Date 2012-05-31 Time 08:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-03-28 Cont ID  
Sent By jwitmer Date 2012-03-28 Time 16:59 Rev Time 0.00
Received By jwitmer Date 2012-03-27 Time 08:45 Sent To  
Notes
2012-03-28 16:49:11BUILDING PLAN REVIEW
 PERMIT: 12020414
 ADD: 4801 DREHER TRAIL N
 CONT: TBD
 TEL: (561)###-####
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 BUILDING TYPE III-B
 FULLY SPRINKLERED
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1)THE PRESSURES FOUND IN THE STRUCTURAL SHEETS ARE
 CORRECT, THESE ITEMS, PRODUCT APPROVALS CAN BE REVIEWED
 UNDER A REVISION WITH ASSOCIATED REVIEW AND FEES OR
 ONCE A CONTRACTOR HAS BEEN PICKED THEY COME IN AT THAT
 TIME. NOTE PERMITS THAT ARE READY FOR ISSUANCE AND THE
 CONTRACTOR BRINGS IN THE PRODUCT APPROVALS FOR A FIRST
 REVIEW MAY DELAY THE ISSUANCE OF THE PERMIT .
 FBC-B 1609 COMPONENTS & CLADDING, FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR GLAZED DOORS, OVERHEAD GARAGE STYLE &
 ROOF HATCH TYPE DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES ROOFING NOA
 10-0125.05 SEE DECK LIMITATION # 2 DECK SPANS EVERY 5
 FT. NOTE THE ROOF HATCH CAN BE TIED TO THE ROOFING
 PERMIT FOR SUBMITTAL PURPOSES.
 (G) PRE-ENGINEERED A/C STANDS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-05 Cont ID  
Sent By jwitmer Date 2012-03-05 Time 16:29 Rev Time 0.00
Received By jwitmer Date 2012-02-24 Time 12:18 Sent To  
Notes
2012-03-08 11:20:29BUILDING PLAN REVIEW
 PERMIT: 12020414
 ADD: 4801 DREHER TRAIL N
 CONT: TBD
 TEL: (561)###-####
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 BUILDING TYPE III-B
 FULLY SPRINKLERED
  
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-101 INDICATES DETAILS ON SHEET A-151
 1A) SHEET A-151 DETAIL # 1 INDICATES THE USE OF A
 PRE-MANUFACTURED ALUMINUM RAMP AND HANDRAIL NO DETAILS
 ARE PROVIDED FOR STRENGTH AN OR ACCESSIBILITY
 REQUIREMENTS
  
 1B) SHEET A-151 DETAIL 02 INDICATES A CONCRETE RAMP AND
 HANDRAIL THE PLANS DO NOT PROVIDE ENOUGH INFORMATION
 FOR THE ACCESSIBLE RAMP NOR STAIRS.
  
 1C) SHEET A-101 INDICATES A DETAIL 01/A151 WHICH REFERS
 TO DETAIL # 11/A-613. THE PLANS ARE NOT CLEAR AS TO IF
 THE HORIZONTAL AND VERTICAL CANOPY PIECES ARE TO BE
 SOLID OR DOES THE MATERIAL ALLOW WIND THROUGH THE
 MATERIAL. S-102 DOES INDICATE WITH NOTE 6 HIGHER
 PRESSURES FOR THIS CANOPY SECTION.
  
 2) SHEET A-101 THIS LOCATION IS IN A A-7 FLOOD ZONE,
 THE MINIMUM FINISH FLOOR OF 12.5?. THE FINISH FLOOR OF
 THE EXISTING BUILDING AND ADDITION IS INDICATED WELL
 ABOVE THIS HEIGHT BUT THE
 NEW EMERGENCY GENERATOR AND PAD AS WELL AS HV/AC
 EQUIPMENT PAD HEIGHTS ARE NOT PROVIDED. THESE EQUIPMENT
 PADS HAVE TO BE AT LEAST THE BASE FLOOD ELEVATION OF
 12.5 ? NGVD.
  
 3) LS-100 HEADING BUILDING SEPARATION INDICATES THE
 BUILDING SEPARATION WALLS FIRE WALLS TO BE 3HOUR RATED
 WALLS AS WELL AS LS-201, LS-202 & LS-203 WITH 2 HOUR
 OPENING PROTECTIVE?S.
  
 3A) PLEASE REVIEW 2007/09 FBC-B TABLE 705.4 FOOTNOTE C.
 FOR THE PURPOSES OF DETERMINING HEIGHT AND AREA IN
 ACCORDANCE WITH TABLE 503, FIRE WALLS DIVIDING
 BUILDINGS INTO SEPARATE BUILDINGS SHALL PROVIDE A
 4-HOUR FIRE-RESISTANCE RATING.
  
 3B) OPENING PROTECTIVES2007/09 FBC-B TABLE 715.4
 REQUIRES EITHER A 3 HOUR RATED FIRE DOOR AND FIRE
 SHUTTER ASSEMBLY. PLEASE NOTE THAT 715.3 DOES ALLOW FOR
 715.3 ALTERNATIVE METHODS FOR DETERMINING FIRE
 PROTECTION RATINGS. BASED ON THE FIRE EXPOSURE AND
 ACCEPTANCE CRITERIA SPECIFIED IN NFPA 252 OR NFPA 257.
 THE REQUIRED FIRE RESISTANCE OF AN OPENING PROTECTIVE
 SHALL BE PERMITTED TO BE ESTABLISHED BY ANY OF THE
 FOLLOWING METHODS OR PROCEDURES:
 1. DESIGNS DOCUMENTED IN APPROVED SOURCES.
 2. CALCULATIONS PERFORMED IN AN APPROVED MANNER.
 3B) 3. ENGINEERING ANALYSIS BASED ON A COMPARISON OF
 OPENING PROTECTIVE DESIGNS HAVING FIRE-PROTECTION
 RATINGS AS DETERMINED BY THE TEST PROCEDURES SET FORTH
 IN NFPA 252 OR NFPA 257.
 3B) 4. ALTERNATIVE PROTECTION METHODS AS ALLOWED BY
 SECTION 104.11.
  
 4) SHEET LS-201, LS-202 & LS-203 ALL SHOW THE NEW DECK
 AND ADA MODULAR RAMP AS PART OF THE MEANS OF EGRESS BUT
 THE PLANS DO NOT PROVIDE COMPLIANCE WITH THE EXIT
 DISCHARGE LEADING TO A PUBLIC WAY. FBC-B 1024.1.
 11-4.1.3(8)(II).
  
 5) SHEET A-650 INDICATES WALL TYPES BUT NOTE # 3
 INDICATES REFER TO LIFE SAFETY PLANS FOR LOCATION AND
 FULL EXTENT OF FIRE AND SMOKE RATED ASSEMBLIES. COMMENT
 # 3 DEALS WITH THE 4 HR RATED FIRE WALL THAT SEPARATES
 THE TWO BUILDINGS BUT THE PLANS DO NOT PROVIDE FOR FIRE
 RATING FOR THE FIRST FOUR FEET PAST WHERE THE EXTERIOR
 WALL INTERSECTS, SEE FBC-B 705.5.1.
  
 6A) SHEET LS-201, LS-202 & LS-203 DOES NOT PROVIDE FOR
 ANY RATINGS OF OTHER WALLS. FBC-B TABLE 508.2 FOR
 STORAGE ROOMS WITH FULLY SPRINKLERED BUILDINGS STILL
 REQUIRE THE WALLS TO BE A SMOKE PARTITION SEE FBC- B
 508.2.2.1.
 THE PARTITIONS SHALL EXTEND FROM THE FLOOR TO THE
 UNDERSIDE OF THE FIRE-RESISTANCE-RATED FLOOR/CEILING
 ASSEMBLY OR FIRE-RESISTANCE-RATED ROOF/CEILING ASSEMBLY
 ABOVE OR TO THE UNDERSIDE OF THE FLOOR OR ROOF
 SHEATHING, OR SUB DECK ABOVE.
  
 6B) SHEET A-251 DETAILS 03, 08 & 10 ARE ALL DETAILS
 INDICATING CUT SECTIONS THROUGH THE 4 HOUR FIRE RATED
 WALL, PLEASE PROVIDE AN ASSEMBLY RATING FOR SUCH WALL.
 SHEET A-611 DETAIL # 4
 DEPICTS TWO SEPARATE WALL DETAILS DETAIL FOUND ON A-451
 DETAIL # 5 DOES SHOW ROOF HEIGHTS AT TWO DIFFERENT
 HEIGHTS. PLEASE PROVIDE WALL RATING OF PARAPET WALL.
 705.6.1.
  
 7) STRUCTURAL SHEET S-2.1122 INDICATES THE USE OF
 EPICORE ER2R NOTE # 2 INDICATES 18 GAGE STEEL SUPPORTED
 BY CSTELLATED CELLULAR BEAMS. THE ESR-2047 REPORT ON
 THIS SYSTEM PROVIDES
 TABLES AND SPANS FOR THIS SYSTEM BEING USED WITH A
 POURED 4 INCH CONCRETE DECK SYSTEM. THE DETAIL SHEETS
 A-613 INDICATE THE USE OF ONLY RIGID FOAM AND A BUILT
 UP SYSTEM. HOW FAR CAN THIS STEEL DECKING SPAN WITHOUT
 A CONCRETE DECK, NOTE ROOFING PRODUCT APPROVALS MAY
 HAVE SPAN LIMITATIONS ( SPACING CENTER TO CENTER).
 ADDITIONAL INFORMATION REQUIRED. 106.1.2.
  
 8) PLEASE PROVIDE SOILS REPORTS BY NORARSE & ASSOCIATES
 DATED 12/07/2011, FBC-B 1802.6.
  
 9) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10)THE PRESSURES FOUND IN THE STRUCTURAL SHEETS ARE
 CORRECT, THESE ITEMS, PRODUCT APPROVALS CAN BE REVIEWED
 UNDER A REVISION WITH ASSOCIATED REVIEW AND FEES OR
 ONCE A CONTRACTOR HAS BEEN PICKED THEY COME IN AT THAT
 TIME. NOTE PERMITS THAT ARE READY FOR ISSUANCE AND THE
 CONTRACTOR BRINGS IN THE PRODUCT APPROVALS FOR A FIRST
 REVIEW MAY DELAY THE ISSUANCE OF THE PERMIT .
 FBC-B 1609 COMPONENTS & CLADDING, FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS GLAZED EXT DOORS, METAL EXT,
 OVERHEAD GARAGE STYLE & ROOF HATCH TYPE DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES ROOFING NOA
 10-0125.05 SEE DECK LIMITATION # 2 DECK SPANS EVERY 5
 FT.
 (G) PRE-ENGINEERED A/C STANDS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-27 Cont ID  
Sent By rlecky Date 2012-03-27 Time 12:14 Rev Time 0.00
Received By rlecky Date 2012-03-21 Time 12:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-03-05 Cont ID  
Sent By rlecky Date 2012-03-05 Time 14:46 Rev Time 0.00
Received By rlecky Date 2012-03-01 Time 12:41 Sent To  
Notes
2012-03-05 14:48:30PANEL SCHEDULE WIRE AND CONDUIT SIZES DO NOT MATCH THE
 LOADS. NEC 215.5
 GFCI PROTECTION IS REQUIRED FOR THE ELECTRIC DRINKING
 FOUNTAIN. NEC 422.52
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
 PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE
 REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL
 ROOMS. NEC 110.22, 110.16
 PROVIDE DETAIL FOR THE ELECTRIC EQUIPMENT ROOM SHOWING
 SAFETY CLEARANCES. NEC 110.26
 A SEPARATE PERMIT AND PLANS WITH WIND LOAD ENGINEERING
 IS REQUIRED FOR SITE LIGHTING.
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR SECURITY,
 VOICE, DATA AND FIRE ALARM SYSTEMS.
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2012-03-09 Cont ID  
Sent By mgonzale Date 2012-03-09 Time   Rev Time 0.25
Received By mgonzale Date 2012-03-09 Time   Sent To  
Notes
2012-03-09 17:40:07PROJECT HAS SUBMITED TO ENGINEERING DIRECTLY 02/16/2012

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-04-09 Cont ID  
Sent By wjolin Date 2012-04-09 Time 09:25 Rev Time 0.00
Received By wjolin Date 2012-04-09 Time 08:38 Sent To  
Notes
2012-04-09 08:38:494801 DREHER TRAIL NORTH
 PERMIT #12020414
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS-100: UPDATE THE CODE LIST TO REFERENCE THE
 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 DEMOLITION: TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED AREAS. ALL OTHER
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 DEMOLITION: WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING AND APPROVED BY
 THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH
 DIXIE HIGHWAY.
  
 SHEET A-101: PROVIDE FIRE LANE SIGNAGE FOR EXISTING
 DROP-OFF LANE. FIRE LANES SHALL BE MARKED WITH
 FREESTANDING SIGNS READING, "FIRE LANE - NO PARKING BY
 ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18"
 WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL BE A
 MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE
 SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW
 AND BE SPACED A MAXIMUM OF 60 FEET APART.
  
 SHEET A-201: PROVIDE A 1-HOUR FIRE/SMOKE BARRIER FOR
 THE RECEIVING/STORAGE ROOM #105 PER SECTION 12.7.5.2 OF
 NFPA 101. PROTECT ALL OPENINGS AND PENETRATIONS.
  
 GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 GENERAL: FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: POST "NO SMOKING" SIGNS IN ALL EXHIBIT ROOMS.
  
 GENERAL: AN EMERGENCY PLAN SHALL BE DEVELOPED AND
 APPROVED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY.
  
 FIRE ALARM: A CERTIFICATE OF COMPLETION AND A THIRD
 PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE
 SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM
 INSPECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-03-01 Cont ID  
Sent By wjolin Date 2012-03-01 Time 15:18 Rev Time 0.00
Received By wjolin Date 2012-02-29 Time 11:59 Sent To  
Notes
2012-02-29 12:47:114801 DREHER TRAIL NORTH
 PERMIT #12020414
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS-100: UPDATE THE CODE LIST TO REFERENCE THE
 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 DEMOLITION: TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED AREAS. ALL OTHER
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 DEMOLITION: WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING AND APPROVED BY
 THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH
 DIXIE HIGHWAY.
  
 SHEET A-101: PROVIDE FIRE LANE SIGNAGE FOR EXISTING
 DROP-OFF LANE. FIRE LANES SHALL BE MARKED WITH
 FREESTANDING SIGNS READING, "FIRE LANE - NO PARKING BY
 ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18"
 WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL BE A
 MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE
 SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW
 AND BE SPACED A MAXIMUM OF 60 FEET APART.
  
 SHEET A-201: PROVIDE A 1-HOUR FIRE/SMOKE BARRIER FOR
 THE RECEIVING/STORAGE ROOM #105 PER SECTION 12.7.5.2 OF
 NFPA 101. PROTECT ALL OPENINGS AND PENETRATIONS.
  
 GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 GENERAL: FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: POST "NO SMOKING" SIGNS IN ALL EXHIBIT ROOMS.
  
 GENERAL: AN EMERGENCY PLAN SHALL BE DEVELOPED AND
 APPROVED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY.
  
 SHEET F-002: PROVIDE LOCKABLE KNOX CAPS ON FIRE
 DEPARTMENT CONNECTION.
  
 FIRE ALARM: A CERTIFICATE OF COMPLETION AND A THIRD
 PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE
 SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM
 INSPECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-06-18 Cont ID  
Sent By rregueir Date 2012-06-06 Time 10:04 Rev Time 0.00
Received By rregueir Date 2012-05-01 Time 10:05 Sent To  
Notes
2012-05-02 10:05:44NEEDS ZONING ONLY. ASSIGNED TO JROACH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-26 Cont ID  
Sent By shill Date 2012-04-26 Time 17:33 Rev Time 0.00
Received By shill Date 2012-03-20 Time 11:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-21 Cont ID  
Sent By rregueir Date 2012-03-13 Time 11:00 Rev Time 0.00
Received By rregueir Date 2012-02-24 Time 11:34 Sent To  
Notes
2012-02-24 11:34:42**DIGITAL** SEE PROJECTDOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-03-21 Cont ID  
Sent By rregueir Date 2012-03-21 Time 11:00 Rev Time 0.00
Received By rregueir Date 2012-03-21 Time 11:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-03-09 Cont ID  
Sent By rregueir Date 2012-03-09 Time 11:09 Rev Time 0.00
Received By rregueir Date 2012-03-09 Time 10:48 Sent To  
Notes
2012-03-09 11:09:00REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-201: INTAKE FOR OAU-1 IS LESS THAN 10 FEET
 FROM THE LOADING DOCK AREA. MECHANICAL OUTDOOR AIR
 INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FEET
 HORIZONTALLY FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT
 SOURCE, SUCH AS STREETS, ALLEYS, PARKING LOTS AND
 LOADING DOCKS IN ACCORDANCE WITH FBC-M 401.4. SEE
 DRAWING MARK-UP IN PROJECTDOX FOR EXACT LOCATION.
  
 2. PAGE M-201: EF-T IS SHOWN WITH A CAPACITY OF 1500
 CFM AND DISCHARGING THROUGH AN 18X18 ROOF EXHAUST HOOD
 WHICH IS SHOWN WITH A CAPACITY OF 250 CFM. PLEASE
 COORDINATE EXHAUST FAN AND ROOF HOOD RATINGS TO ASSURE
 PROPER VENTILATION RATES ARE PROVIDED IN ACCORDANCE
 WITH FBC-M TABLE 403.3. SEE DRAWING MARK-UP IN
 PROJECTDOX FOR EXACT LOCATION.
  
 3. PROVIDE EVNTILATION CALCULATIONS FOR ALL NEWLY
 CONSTRUCTED AND RENOVATED SPACES SHOWING OCCUPANCY
 CLASSIFICATIOPN, OCCUPANT LOAD AND VENTILATION RATES IN
 ACCORDANCE WITH FBC-M SECTION 403.
  
 4. PROVIDE PRODUCT APPROVALS FOR ALL OUTSIDE LOUVERS
 PER FAC RULE 9N-3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-03-05 Cont ID  
Sent By lwagner Date 2012-03-05 Time 11:22 Rev Time 0.00
Received By lwagner Date 2012-03-02 Time 14:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2012-06-27 Cont ID  
Sent By rregueir Date 2012-06-27 Time 14:00 Rev Time 0.00
Received By rregueir Date 2012-06-27 Time 14:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2012-06-22 Time   Rev Time 0.00
Received By   Date 2012-06-22 Time   Sent To  
Notes
2012-06-22 16:17:10RECEIVED PEDDS SIGNATURE PAGE FOR 42 PAGES SIGNED BY
 PETER GILSTAD.
 LACKING PEDDS SIGNATURE PAGES FOR MEP, CIVIL, AND
 LANDSCAPE PAGES TOTALLING 57 PAGES.
 CALLED PETER AND ASKED HIM TO NOTIFY OTHER DESIGN
 PROFESSIONALS THAT PERMIT CAN NOT BE ISSUED WITHOUT ALL
 PAGES.

Review Stop Z ZONING
Rev No 4 Status P Date 2012-06-06 Cont ID  
Sent By jroach Date 2012-06-06 Time 23:20 Rev Time 0.00
Received By jroach Date 2012-06-06 Time 23:20 Sent To  
Notes
2012-06-06 23:20:51ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.06.2012
 PERMIT NO.: 12020414
 ADDRESS: 4801 DREHER TRAIL NORTH
 CONTRACTOR/CONTACT: PETER GILSTAD
 TELEPHONE NO.: 561.655.2423
 SCOPE OF REVIEW: ADDITION TO EXISTING SCIENCE MUSEUM.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. ALL NECESSARY APPROVALS TO ACCOMMODATE ANY DRAINAGE
 THAT MAY BE REQUIRED OUTSIDE OF THE LEASE AREA SHALL BE
 OBTAINED.
  
 2. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT APPLICATION AND SHALL BE ACCOMPANIED BY A
 CERTIFIED COST ESTIMATE.
  
 3. ALL LANDSCAPE AREAS SHALL BE IRRIGATED. IRRIGATION
 PLANS SHALL BE SUBMITTED UNDER A SEPARATE PERMIT
 APPLICATION AND SHALL CONFORM TO THE REQUIREMENTS OF
 ARTICLE XIV OF THE CITY'S ZLDRS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 3 Status F Date 2012-05-11 Cont ID  
Sent By jroach Date 2012-05-11 Time 10:52 Rev Time 0.00
Received By jroach Date 2012-05-11 Time 10:52 Sent To  
Notes
2012-05-11 10:52:37ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.11.2012
 PERMIT NO.: 12020414
 ADDRESS: 4801 DREHER TRAIL NORTH
 CONTRACTOR/CONTACT: PETER GILSTAD
 TELEPHONE NO.: 561.655.2423
 SCOPE OF REVIEW: ADDITION TO EXISTING SCIENCE MUSEUM.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS.
  
 1. PLEASE PROVIDE A DETAIL FOR ALL NEW FENCING THAT IS
 BEING PROPOSED (CHAIN LINK AND WOOD). THE PLANS AND/OR
 DETAIL SHALL CLEARLY INDICATE THE HEIGHTS OF ALL
 FENCES. NO DETAIL REFERENCES WERE FOUND?ARE YOU USING
 THE DETAILS SHOWN ON SHEET A-152?
  
 2. THE SITE AND LANDSCAPE PLANS SHALL CONTAIN THE
 FOLLOWING:
 A. LOCATION, HEIGHT AND INTENSITY OF ALL OUTDOOR
 ILLUMINATION. PLEASE NOTE THAT SHEET A-101 DOES NOT
 MATCH THE ELECTRICAL SITE PLAN, AND NO LIGHTING IS
 SHOWN ON THE SITE/LANDSCAPE PLANS.
  
 3. PURSUANT TO SECTION 94-444, THE EXISTING A/C AREA,
 SOUTH OF THE EXISTING BUILDING, SHALL BE SCREENED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. SHRUBS OR HEDGES SHALL BE
 PLANTED AROUND THE PERIMETER OF THE ENCLOSURE AT 2-FOOT
 INTERVALS. PLEASE NOTE THAT AS THE PROJECT EXCEEDS 50
 PERCENT OF THE VALUE OF THE EXISTING STRUCTURE, THE
 SITE SHALL BE BROUGHT INTO COMPLIANCE WITH ARTICLE XIV
 OF THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS), INCLUDING SCREENING OF MECHANICAL EQUIPMENT.
  
 4. LANDSCAPE PLAN SHALL PROVIDE A TABULATION TABLE
 INDICATING COMPLIANCE WITH ARTICLE XIV OF THE ZLDRS.
 A. A MINIMUM OF 30 POINTS SHALL BE PROVIDED IN
 ACCORDANCE WITH THE XERISCAPE REQUIREMENTS OF SECTION
 94-442(G) OF THE CITY'S ZLDRS. NO XERISCAPE TABLE WAS
 SHOWN.
  
 5. PLEASE PROVIDE THE PERCENTAGE OF THE EXISTING AND
 PROPOSED BUILDING FOUNDATIONS THAT ARE PLANTED WITH
 SHRUBS/HEDGES.
  
 6. FINAL ORDER FOR ZBA CASE NO. 3258 REQUIRED THE
 FOLLOWING ITEMS PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT:
 A. ALL NECESSARY APPROVALS TO ACCOMMODATE ANY DRAINAGE
 THAT MAY BE REQUIRED OUTSIDE OF THE LEASE AREA.
  
 7. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT APPLICATION AND SHALL BE ACCOMPANIED BY A
 CERTIFIED COST ESTIMATE.
  
 8. ALL LANDSCAPE AREAS SHALL BE IRRIGATED. IRRIGATION
 PLANS SHALL BE SUBMITTED UNDER A SEPARATE PERMIT
 APPLICATION AND SHALL CONFORM TO THE REQUIREMENTS OF
 ARTICLE XIV OF THE CITY'S ZLDRS.
  
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 2 Status F Date 2012-04-25 Cont ID  
Sent By jroach Date 2012-04-25 Time 14:30 Rev Time 0.00
Received By jroach Date 2012-04-03 Time 11:05 Sent To  
Notes
2012-04-25 14:31:06ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.25.2012
 PERMIT NO.: 12020414
 ADDRESS: 4801 DREHER TRAIL NORTH
 CONTRACTOR/CONTACT: PETER GILSTAD
 TELEPHONE NO.: 561.655.2423
 SCOPE OF REVIEW: ADDITION TO EXISTING SCIENCE MUSEUM.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS. PLEASE NOTE THAT THE NUMBER OF THE
 COMMENTS REMAINS FROM THE PREVIOUS PLANS REVIEW, AND
 ADDITIONAL COMMENTS/INFORMATION IS SHOWN IN ALL CAPS.
  
 1. PURSUANT TO SECTION 94-444(B) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS), GENERATORS
 AND OTHER MECHANICAL EQUIPMENT (I.E. HVAC, ETC.) SHALL
 BE COMPLETELY SCREENED FROM VIEW. SCREENING SHALL BE
 CONSTRUCTED OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD AND
 STEEL. SHRUBS OR HEDGES SHALL BE PLANTED AROUND THE
 PERIMETER OF THE ENCLOSURE AT 2-FOOT INTERVALS. THE
 PLANS REFERENCE A SLAT DETAIL, AND IT IS UNCLEAR ON THE
 PLANS WHAT IS WOOD FENCE VS. CHAIN LINK FENCE, ETC.
 PLEASE NOTE THAT FENCING SURROUNDING MECHANICAL
 EQUIPMENT SHALL NOT CONSIST OF CHAIN LINK FENCING WITH
 SLATS; IT SHALL BE A PERMANENT OPAQUE FENCE (I.E. WOOD,
 PVC, ETC.).
  
 6. PLEASE PROVIDE A DETAIL FOR ALL NEW FENCING THAT IS
 BEING PROPOSED (CHAIN LINK AND WOOD). THE PLANS AND/OR
 DETAIL SHALL CLEARLY INDICATE THE HEIGHTS OF ALL
 FENCES. PLANS ARE UNCLEAR. SHEET SP-1 REFERENCES SHEET
 A-157, WHICH IS INCORRECT.
  
 10. A DETAILED AND ACCURATE SITE PLAN SHALL BE
 PROVIDED. SHEET A-101 DOES NOT PROVIDE ENOUGH
 INFORMATION TO DETERMINE COMPLIANCE WITH THE CITY'S
 ZLDRS. THE SITE PLAN SHALL CONTAIN THE FOLLOWING:
 I. LOCATION, HEIGHT AND INTENSITY OF ALL OUTDOOR
 ILLUMINATION. PLEASE NOTE THAT SHEET A-101 DOES NOT
 MATCH THE ELECTRICAL SITE PLAN, AND NO LIGHTING IS
 SHOWN ON THE SITE/LANDSCAPE PLANS.
  
 11. PURSUANT TO SECTION 94-444, THE EXISTING A/C AREA,
 SOUTH OF THE EXISTING BUILDING, SHALL BE SCREENED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. SHRUBS OR HEDGES SHALL BE
 PLANTED AROUND THE PERIMETER OF THE ENCLOSURE AT 2-FOOT
 INTERVALS. PLEASE NOTE THAT AS THE PROJECT EXCEEDS 50
 PERCENT OF THE VALUE OF THE EXISTING STRUCTURE, THE
 SITE SHALL BE BROUGHT INTO COMPLIANCE WITH ARTICLE XIV
 OF THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS), INCLUDING SCREENING OF MECHANICAL EQUIPMENT.
  
 12. THE SITE PLAN ON SHEET A-101 DOES NOT MATCH THE
 CIVIL OR LANDSCAPE DRAWINGS WITH REGARD TO THE PROPOSE
 IMPROVEMENTS. SOME EXAMPLES INCLUDE, BUT ARE NOT
 LIMITED TO:
 A. CIVIL PLANS INDICATE THAT ONE OF THE OF THE EXISTING
 ALUMINUM BUILDING SOUTH OF THE EXISTING BUILDING IS
 BEING REMOVED; HOWEVER, THE SITE PLAN ON SHEET A-101
 SHOWS ALL EXISTING BUILDINGS TO REMAIN. THIS BUILDING
 ALSO I NOT SHOWN ON THE SURVEY?IS IT PROPOSED? IF SO,
 ALL CALCULATIONS SHALL INCLUDE THIS AS ADDITIONAL
 SQUARE FOOTAGE AND PARKING, ETC. WILL NEED TO BE
 ACCOUNTED FOR.
  
 13. THE LANDSCAPE PLAN DOES NOT MATCH THE CIVIL PLANS.
 SOME EXAMPLES INCLUDE, BUT ARE NOT LIMITED TO:
 A. CIVIL PLANS INDICATE THAT ONE OF THE OF THE EXISTING
 ALUMINUM BUILDING SOUTH OF THE EXISTING BUILDING IS
 BEING REMOVED; HOWEVER, THE LANDSCAPE PLAN ON SHEET LP1
 SHOWS ALL EXISTING BUILDINGS TO REMAIN. SEE COMMENT
 #12A.
  
 14. ADDITIONAL AREAS OF CONFLICT BETWEEN THE PLANS
 INCLUDE, BUT ARE NOT LIMITED TO:
 F. LANDSCAPE PLANS DO NOT SHOW ANY SIDEWALK, ETC.
 LEADING TO THE EASTERN-MOST ALUMINUM PORTABLE BUILDING
 AND THE SITE PLAN IS UNCLEAR.
  
 ALL PLANS NEED TO BE CONSISTENT AND REFLECT THE SAME
 SCOPE OF WORK. THERE ARE NUMEROUS INCONSISTENCIES
 BETWEEN THE SITE PLAN, LANDSCAPE PLAN, CIVIL PLANS,
 ETC.
  
 17. PURSUANT TO SECTION 94-443(C)(3) OF THE CITY'S
 ZLDRS, INTERMEDIATE ISLANDS SHALL CONTAIN A SHADE OR
 FLOWERING TREE. NO PLANTINGS ARE SHOWN IN THE ISLANDS
 NEAR THE COVERED ENTRY ON WEST SIDE OF EXISTING
 BUILDING. IT HAS BEEN DISCUSSED THAT THE SOUTHERN MOST
 PARKING SPACE IN THIS ROW COULD BE REMOVED TO
 ACCOMMODATE A SUFFICIENT LANDSCAPE ISLAND, OR PLANTING
 ARES NEED TO BE CUT INTO THE EXISTING CONCRETE LOCATED
 IN FRONT OF THE ENTRY.
  
 18. LANDSCAPE PLAN SHALL PROVIDE A TABULATION TABLE
 INDICATING COMPLIANCE WITH ARTICLE XIV OF THE ZLDRS.
 THE ENTIRE LEASE AREA SHALL COMPLY WITH ALL OF THE
 PROVISIONS CONTAINED WITHIN ARTICLE XIV. ALL
 CALCULATIONS SHALL BE DONE BASED UPON THE ENTIRE LEASE
 AREA.
 A. ONE SHADE TREE SHALL BE PANTED FOR EVERY 1600 SQUARE
 FEET OPEN SPACE.
 B. ONE FLOWERING TREE SHALL BE PLANTED FOR EVERY 6400
 SQUARE FEET OF OPEN SPACE.
 C. ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET
 OF OPEN SPACE.
 D. A MINIMUM OF 30 POINTS SHALL BE PROVIDED IN
 ACCORDANCE WITH THE XERISCAPE REQUIREMENTS OF SECTION
 94-442(G) OF THE CITY'S ZLDRS.
  
 21. PLEASE ENSURE THAT THE LANDSCAPE PLAN SHOWS THE
 ENTIRE SITE AND THAT ALL CALCULATIONS ARE BASED UPON
 THE ENTIRE LEASE AREA. SEE COMMENT #18.
  
 23. PLEASE PROVIDE THE PERCENTAGE OF THE EXISTING AND
 PROPOSED BUILDING FOUNDATIONS THAT ARE PLANTED WITH
 SHRUBS/HEDGES. SEE COMMENT #18.
  
 27. FINAL ORDER FOR ZBA CASE NO. 3258 REQUIRED THE
 FOLLOWING ITEMS PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT:
 A. ALL NECESSARY APPROVALS TO ACCOMMODATE ANY DRAINAGE
 THAT MAY BE REQUIRED OUTSIDE OF THE LEASE AREA.
  
 29. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT APPLICATION AND SHALL BE ACCOMPANIED BY A
 CERTIFIED COST ESTIMATE.
  
 30. ALL LANDSCAPE AREAS SHALL BE IRRIGATED. IRRIGATION
 PLANS SHALL BE SUBMITTED UNDER A SEPARATE PERMIT
 APPLICATION AND SHALL CONFORM TO THE REQUIREMENTS OF
 ARTICLE XIV OF THE CITY'S ZLDRS.
  
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 1 Status F Date 2012-03-13 Cont ID  
Sent By jroach Date 2012-03-13 Time 14:45 Rev Time 0.00
Received By jroach Date 2012-03-13 Time 14:45 Sent To  
Notes
2012-03-13 14:47:25ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.13.2012
 PERMIT NO.: 12020414
 ADDRESS: 4801 DREHER TRAIL NORTH
 CONTRACTOR/CONTACT: PETER GILSTAD
 TELEPHONE NO.: 561.655.2423
 SCOPE OF REVIEW: ADDITION TO EXISTING SCIENCE MUSEUM.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. SHEET 2 OF 9 ? PAVING AND DRAINAGE PLAN AND SHEET
 LP-1 SHOW THE INSTALLATION OF A GENERATOR PAD IN THE
 SOUTHEAST CORNER OF THE EXISTING BUILDING.
 ADDITIONALLY, A GENERATOR IS SHOWN TO THE EAST OF THE
 PROPOSED ADDITION. PURSUANT TO SECTION 94-444(B) OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS),
 GENERATORS SHALL BE COMPLETELY SCREENED FROM VIEW.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. SHRUBS OR HEDGES SHALL BE
 PLANTED AROUND THE PERIMETER OF THE ENCLOSURE AT 2-FOOT
 INTERVALS.
  
 2. PAVING OF DIRT ROAD TO ACCESS REAR PARKING LOT?
  
 3. ACCORDING THE PLANS, THE DUMPSTER ENCLOSURES ARE
 BEING PLACED IMMEDIATELY WEST OF THE EXISTING STORAGE
 BUILDING, WITH LANDSCAPING BEHIND. WITH THE PROXIMITY
 OF THE ENCLOSURE TO THIS EXISTING BUILDING, WILL CREWS
 BE ABLE TO MAINTAIN THE SHURBS, ETC. BEHIND THE
 ENCLOSURE?
  
 4. PURSUANT TO SECTION 94-444(B) OF THE CITY'S ZLDRS,
 THE ALL MECHANICAL EQUIPMENT IS TO BE SCREENED FROM
 VIEW. HVAC EQUIPMENT, ETC. IS SHOWN TO THE EAST OF THE
 PROPOSED ADDITION NEAR THE LOADING SPACE. SCREENING
 SHALL BE CONSTRUCTED OF BRICK, DECORATIVE CONCRETE,
 OTHER DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD
 AND STEEL. SHRUBS OR HEDGES SHALL BE PLANTED AROUND THE
 PERIMETER OF THE ENCLOSURE AT 2-FOOT INTERVALS.
  
 5. PLEASE PROVIDE A DETAIL OF THE PROPOSED BIKE RACK.
  
 6. PLEASE PROVIDE A DETAIL FOR ALL NEW FENCING THAT IS
 BEING PROPOSED (CHAIN LINK AND WOOD). THE PLANS AND/OR
 DETAIL SHALL CLEARLY INDICATE THE HEIGHTS OF ALL
 FENCES.
  
 7. PLEASE PROVIDE A DETAIL OF THE DUMPSTER ENCLOSURE
 DETAIL AND VEGETATION PICK-UP.
  
 8. THE PARKING DETAIL ON SHEET 3 OF 9 ? PAVING AND
 DRAINAGE DETAILS, SHALL CONFORM TO THE MINIMUM
 REQUIREMENTS OF THE CITY'S ZLDRS.
  
 9. A CURRENT AND ACCURATE ALTA SURVEY SHALL BE
 PROVIDED.
  
 10. A DETAILED AND ACCURATE SITE PLAN SHALL BE
 PROVIDED. SHEET A-101 DOES NOT PROVIDE ENOUGH
 INFORMATION TO DETERMINE COMPLIANCE WITH THE CITY'S
 ZLDRS. THE SITE PLAN SHALL CONTAIN THE FOLLOWING:
 A. VICINITY MAP SHOWING THE PROPERTY IN RELATION TO THE
 SURROUNDING AREA.
 B. LOCATION OF PROPOSED/EXISTING EASEMENTS.
 C. THE OUTLINES OF ALL BUILDINGS SHOWING THEIR PROPOSED
 USES, SETBACKS, DIMENSIONS, FLOOR AREA, NUMBER OF
 STORIES, HEIGHT AND POINTS OF ACCESS.
 D. LOCATION AND DIMENSIONS OF ALL PERIMETER TREATMENT
 (SIDEWALKS, FENCES, WALLS, OR BERMS).
 E. LOCATION, HEIGHT AND SIZE OF ALL FREESTANDING SIGNS
 AND OTHER ACCESSORY STRUCTURES.
 F. MEANS OF VEHICULAR AND PEDESTRIAN ACCESS TO AND FROM
 THE SITE.
 G. LAYOUT AND LOCATION OF ALL OFF-STREET PARKING,
 LOADING AND OTHER VEHICULAR USE AREAS, INCLUDING WHERE
 APPLICABLE, THE DISTANCE FROM THE PRINCIPLE USES.
 H. LOCATION OF ALL DISABLED SPACES, RAMPS AND SIGNS.
 I. LOCATION, HEIGHT AND INTENSITY OF ALL OUTDOOR
 ILLUMINATION.
 J. LOCATION OF EXISTING AND PROPOSED FIRE HYDRANTS (OR
 OPERATIONAL EQUIVALENTS) WITHIN 250 FEET OF THE
 PROPOSED STRUCTURE OR STRUCTURES.
 K. LOCATION AND SCREENING OF ALL GARBAGE RECEPTACLES.
 L. STANDARD CITY DETAILS OF PARKING (SMALL CAR,
 HANDICAP SPACE, STANDARD SPACE), HANDICAP RAMPS,
 DRIVEWAYS, DUMPSTERS AND SIGNS.
 M. SUPPLY A DATA TABLE WHICH INDICATES THE FOLLOWING:
 I. EXISTING/PROPOSED LAND USE AND ZONING.
 II. TOTAL ACRES OF THE PROJECT.
 III. TOTAL GROSS BUILDING SQUARE FOOTAGE.
 IV. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING
 COVERAGE & IMPERMEABLE SURFACE.
 V. ACRES AND PERCENT OF WATER BODIES.
 VI. DENSITY AND NUMBER OF DWELLING UNITS (RESIDENTIAL).
 VII. PARKING COMPUTATIONS (PARKING REQUIRED, PROVIDED,
 ETC.)
 VIII. FLOOR AREA RATIO (FAR).
  
 11. PURSUANT TO SECTION 94-444, THE EXISTING A/C AREA,
 SOUTH OF THE EXISTING BUILDING, SHALL BE SCREENED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. SHRUBS OR HEDGES SHALL BE
 PLANTED AROUND THE PERIMETER OF THE ENCLOSURE AT 2-FOOT
 INTERVALS.
  
 12. THE SITE PLAN ON SHEET A-101 DOES NOT MATCH THE
 CIVIL OR LANDSCAPE DRAWINGS WITH REGARD TO THE PROPOSE
 IMPROVEMENTS. SOME EXAMPLES INCLUDE, BUT ARE NOT
 LIMITED TO:
 A. CIVIL PLANS INDICATE THAT ONE OF THE OF THE EXISTING
 ALUMINUM BUILDING SOUTH OF THE EXISTING BUILDING IS
 BEING REMOVED; HOWEVER, THE SITE PLAN ON SHEET A-101
 SHOWS ALL EXISTING BUILDINGS TO REMAIN.
 B. THE PARKING LOT CONFIGURATION, DUMPSTER LOCATIONS,
 SIDEWALK CONFIGURATIONS, ETC. SHOWN ON THE SHEET A-101
 DOES NOT MATCH THAT SHOWN ON THE CIVIL AND LANDSCAPE
 PLANS.
 C. SHEET A-101 INDICATES THAT THE FLAGPOLE IS TO
 REMAIN, WHILE THE CIVIL PLAN INDICATE THAT IT IS BEING
 RELOCATED.
 D. SHEET A-101 SHOWS A NEW COVERED WOOD DECK SOUTH OF
 THE NEW ADDITION WITH RAMP, ETC. THIS IS NOT SHOWN ON
 ANY OTHER PLANS.
 E. THE FOOTPRINT OF THE BUILDING SHOWN ON SHEET A-101
 DOES NOT MATCH THE OTHER PLANS.
  
 13. THE LANDSCAPE PLAN DOES NOT MATCH THE CIVIL PLANS.
 SOME EXAMPLES INCLUDE, BUT ARE NOT LIMITED TO:
 A. CIVIL PLANS INDICATE THAT ONE OF THE OF THE EXISTING
 ALUMINUM BUILDING SOUTH OF THE EXISTING BUILDING IS
 BEING REMOVED; HOWEVER, THE LANDSCAPE PLAN ON SHEET LP1
 SHOWS ALL EXISTING BUILDINGS TO REMAIN.
 B. LANDSCAPE PLAN DOES NOT SHOW THE MECHANICAL
 EQUIPMENT, GENERATOR, ETC. THAT IS BEING PROPOSED EAST
 OF THE LOADING AREA.
  
 14. ADDITIONAL AREAS OF CONFLICT BETWEEN THE PLANS
 INCLUDE, BUT ARE NOT LIMITED TO:
 A. DEMOLITION PLANS SHOW THE FLAG POLE REMAINING, WHILE
 OTHER PLANS SHOW THAT IT IS BEING RELOCATED. PLEASE
 ENSURE THAT ALL PLANS ARE CONSISTENT.
 B. DEMOLITION PLANS SHOW AN EXISTING CONCRETE DECK
 REMAINING ON THE EAST SIDE OF THE EXISTING STRUCTURE,
 THIS IS NOT SHOWN ON THE LANDSCAPE PLANS.
 C. DEMOLITION PLANS SHOW THE EXISTING WOOD DECK AND
 ALUMINUM STAIRS ON THE EAST SIDE OF THE EXISTING
 BUILDING AS TO REMAIN WITH THE ADDITION OF A NEW DECK;
 HOWEVER OTHER PLANS SHOW THIS BEING REMOVED.
 D. DEMOLITION PLANS AND THE SITE PLAN SHOW THE 2 SETS
 OF CONCRETE STAIRS ON THE SOUTH SIDE OF THE EXISTING
 BUILDING AS TO BE DEMOLISHED. THE LANDSCAPE PLANS SHOW
 THESE STAIRS REMAINING AS-IS.
 E. DEMOLITION PLANS SHOW AN EXISTING WOOD FENCE NEAR
 THE SOUTHEAST CORNER OF THE BUILDING AS REMAINING, THIS
 FENCE IS NOT SHOWN ON ANY OF THE OTHER PLANS (I.E.
 LANDSCAPE PLANS).
 F. LANDSCAPE PLANS DO NOT SHOW ANY SIDEWALK, ETC.
 LEADING TO THE EASTERN-MOST ALUMINUM PORTABLE BUILDING
 AND THE SITE PLAN IS UNCLEAR.
  
 ALL PLANS NEED TO BE CONSISTENT AND REFLECT THE SAME
 SCOPE OF WORK. THERE ARE NUMEROUS INCONSISTENCIES
 BETWEEN THE SITE PLAN, LANDSCAPE PLAN, CIVIL PLANS,
 ETC.
  
 15. LANDSCAPE PLAN SHOWS THE ADDITION CONSISTING OF
 12,000 SQUARE FEET, HOWEVER THE PERMIT APPLICATION
 REFERENCES AN ADDITION OF 6,000 SQUARE FEET.
  
 16. PURSUANT TO SECTION 94-443(C)(3) OF THE CITY'S
 ZLDRS, EACH TERMINAL ISLAND SHALL CONTAIN A SHADE OR
 FLOWERING TREE. IN THE NORTHERN PARKING LOT, NO TREE IS
 SHOWN AT THE SOUTH END OF THE EASTERN ROW OF PARKING.
 ADDITIONALLY, NO PLANTING ARE SHOWN IN THE TERMINAL
 ISLAND IN THE NORTHEAST CORNER OF THE SOUTH PARKING
 LOT.
  
 17. PURSUANT TO SECTION 94-443(C)(3) OF THE CITY'S
 ZLDRS, INTERMEDIATE ISLANDS SHALL CONTAIN A SHADE OR
 FLOWERING TREE. NO PLANTINGS ARE SHOWN IN THE ISLANDS
 NEAR THE COVERED ENTRY ON WEST SIDE OF EXISTING
 BUILDING.
  
 18. LANDSCAPE PLAN SHALL PROVIDE A TABULATION TABLE
 INDICATING COMPLIANCE WITH ARTICLE XIV OF THE ZLDRS.
 THE ENTIRE LEASE AREA SHALL COMPLY WITH ALL OF THE
 PROVISIONS CONTAINED WITHIN ARTICLE XIV.
 A. ONE SHADE TREE SHALL BE PANTED FOR EVERY 1600 SQUARE
 FEET OPEN SPACE.
 B. ONE FLOWERING TREE SHALL BE PLANTED FOR EVERY 6400
 SQUARE FEET OF OPEN SPACE.
 C. ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET
 OF OPEN SPACE.
 D. A MINIMUM OF 30 POINTS SHALL BE PROVIDED IN
 ACCORDANCE WITH THE XERISCAPE REQUIREMENTS OF SECTION
 94-442(G) OF THE CITY'S ZLDRS.
  
 19. PLEASE CONSIDER RECONFIGURING THE FENCING AROUND
 THE EXISTING EDUCATION OFFICES, SOUTH PARKING LOT, ETC.
 I BELIEVE THERE ARE ALTERNATIVE LOCATIONS FOR THE FENCE
 THAT WOULD BE JUST AS SECURE, WHILE PROVIDE FOR A MORE
 AESTHETIC LOOK.
  
 20. THE LANDSCAPE PLAN SHOWS AN EXISTING FENCE CROSSING
 THE INGRESS/EGRESS DRIVE INTO THE SOUTH PARKING LOT. IS
 THIS GOING TO BE REPLACED WITH A GATE? IF SO, PLEASE
 PROVIDE DETAIL AS TO THE PROPOSED GATE?IS IT SLIDING?
  
 21. PLEASE ENSURE THAT THE LANDSCAPE PLAN SHOWS THE
 ENTIRE SITE AND THAT ALL CALCULATIONS ARE BASED UPON
 THE ENTIRE LEASE AREA.
  
 22. AT THE ONE-WAY EGRESS FROM THE NORTH PARKING LOT
 (ADJACENT TO EXISTING STORAGE)?HOW IS THIS GOING TO BE
 SIGNED, ETC.? IT NEEDS TO BE CLEAR THAT THIS IS AN EXIT
 ONLY AND THAT THERE IS NO ENTRANCE FROM THE EXISTING
 DIRT ROAD.
  
 23. PLEASE PROVIDE THE PERCENTAGE OF THE EXISTING AND
 PROPOSED BUILDING FOUNDATIONS THAT ARE PLANTED WITH
 SHRUBS/HEDGES.
  
 24. THE DEMOLITION PLANS SHOW THE PROPANE TANK
 REMAINING, WHILE OTHER PLANS SHOW THAT IT IS BEING
 RELOCATED. PLEASE CLARIFY. PURSUANT TO SECTION
 94-444(B) OF THE CITY'S ZLDRS, THE PROPANE TANK SHALL
 BE COMPLETELY SCREENED FROM VIEW. SCREENING SHALL BE
 CONSTRUCTED OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD AND
 STEEL. SHRUBS OR HEDGES SHALL BE PLANTED AROUND THE
 PERIMETER OF THE ENCLOSURE AT 2-FOOT INTERVALS.
  
 25. ON SHEET A-101, YOU REFERENCES TO DETAILS ON SHEET
 A-151 ARE INCORRECT. THE DETAIL NUMBERS ARE INCORRECT.
  
 26. SHEET A-101 SHOWS A CHAIN LINK FENCE CROSSING THE
 ACCESS TO THE LOADING AREA; THIS IS NOT SHOWN ON THE
 OTHER PLANS. THIS SHOULD BE A SOLID FENCE TO ENCLOSE
 THE LOADING AREA, MECHANICAL EQUIPMENT, GENERATOR, ETC.
 THE PLANS APPROVED BY THE ZBA INCLUDED A DECORATIVE PVC
 FENCE AND GATE.
  
 27. FINAL ORDER FOR ZBA CASE NO. 3258 REQUIRED THE
 FOLLOWING ITEMS PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT:
 A. ALL NECESSARY APPROVALS TO ACCOMMODATE ANY DRAINAGE
 THAT MAY BE REQUIRED OUTSIDE OF THE LEASE AREA.
 B. WAIVERS AND EASEMENT RELEASES FROM ALL APPLICABLE
 UTILITY COMPANIES (I.E. FPL) TO CONSTRUCT IMPROVEMENTS
 WITHIN THEIR EASEMENTS. IF SUCH APPROVALS ARE NOT
 GRANTED, THE SITE PLANS SHALL BE ADJUSTED ACCORDINGLY.
 TREES, FENCING, ETC. ARE PROPOSED WITHIN THESE
 EASEMENTS AND SHALL BE APPROVED BY THE EASEMENT
 HOLDERS. ADDITIONALLY, SOME OF FPL'S EQUIPMENT WILL BE
 ENCLOSED WITHIN A FENCE?IS THIS ACCEPTABLE TO FPL?
  
 28. PLEASE PROVIDE EVIDENCE THAT THE BUILD-OUT DATE FOR
 THE PALM BEACH COUNTY TRAFFIC CONCURRENCY APPROVAL HAS
 BEEN EXTENDED AND IS STILL VALID. THE ORIGINAL APPROVAL
 EXPIRED ON DECEMBER 31, 2011.
  
 29. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT APPLICATION AND SHALL BE ACCOMPANIED BY A
 CERTIFIED COST ESTIMATE.
  
 30. ALL LANDSCAPE AREAS SHALL BE IRRIGATED. IRRIGATION
 PLANS SHALL BE SUBMITTED UNDER A SEPARATE PERMIT
 APPLICATION AND SHALL CONFORM TO THE REQUIREMENTS OF
 ARTICLE XIV OF THE CITY'S ZLDRS.
  
 31. THERE ARE SEVERAL AREAS WHERE PROPOSED LANDSCAPING
 IS LOCATED ON TOP OF, OR IMMEDIATELY ADJACENT TO
 DRAINAGE PIPES ASSOCIATED WITH THE STORM WATER SYSTEM.
 PLEASE INDICATE IF THIS CAUSES ANY ISSUES.
  
 32. PURSUANT TO SECTION 94-443(B) OF THE CITY'S ZLDRS,
 NONRESIDENTIAL USES SHALL BE BUFFERED WHEN ADJACENT TO
 A PUBLIC THOROUGHFARE BY A LANDSCAPE AREA OF NOT LESS
 THAN 5 FEET IN WIDTH. THE BUFFER SHALL NOT BE
 INTERRUPTED BY MORE THAN 25 PERCENT OF ITS LENGTH BY
 ACCESS DRIVES, ETC. AND SHALL CONTAIN AT LEAST 1 SHADE
 OR FLOWERING TREE FOR EACH 30 LINEAR FEET.
  
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  